Amend 138 to License DPR-20,revising Tech Specs Table 2.3.1 to Delete Wording That Does Not Apply to Replacement Steam Generator
ML20070D668
Person / Time
Site: Palisades Entergy icon.png
Issue date: 02/22/1991
From: Marsh L
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20070D670 List:
References
NUDOCS 9103010067
Download: ML20070D668 (4)


Text

. _ _ _ _ _

/'o ueg#e, s

UNITED STA1Es

'8'

~%

NUCLEAR REGULATORY COMMISSION I

. j' wAswiwoTon, o. c. roess CONStlMERS POWER COMPANY PALISADES PLANT DOCKET NO. 50-255 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 138 License No OPR-20 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Consumers Power Company (the licensee) dated Aug'ast 21, 1990, complies with the standards and requirementsoftheAtomicEnergyActof1954,asamended(the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commissioni C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public; and (ii) that such activities will be conducted in compliance with the Commission't regulations; D.

The issuance of this amendment will not be inir.ical to the conanon defense and security or to the health and safety of the public; and j

E.

The issuance of this amendment is in acct.Qnce with 10 CFR Part 51 of tha Commission's regulations and all 4plicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and Paragraph 3.B. of Facility Operating License No. DPR-20 is hereby amended to read as follows:

9103010067 910222 i

DR ADOCK 0000 5

2 Technical Seccifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.138, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION

d. B. y s'h, Director Project Directorate !!!-!

Division of Reactor Projects Ill/IV/V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

February 22, 1991 9

l l

l

__. _._ ~.. _.. _ - _. _

ATTACHMENT TO LICENSE AMENDMENT NO. 138 FACILITY OPERATING LICENSE NO. DPR-20 DOCKET NO. 50 255 Revise Appendix A Technical Specifications by removing the page identified below and inserting the attached page. The reyt;ed page is identified by the amendment number and contains marginal lines indicating the area of change.

REMOVE INSERT 2-5 2-5 e

i

,n-

.+-,

,p

,-,.4-m...

,.m.wm-,

e-

-w.--v ven'>-

y+,

,.-e,g----,-

,,---,-e

s TABLE 2.3.1 Reactor Protective System Trip Setting Limits Four Primary Coolant ThreePrimaryCoogt Pumps Operating Pumps Operatine 1.

Varin g High 510% above core power, 110% above core power Power with a minimum setpoint with a minimum setpoint j

of $30% of rate ' power of 515% rated. power and a maximut-4 5106.5%

and a maximup,of 549%

of rated power of rated power 2.

Primary 295% of Primary Coolant 260% of Primary Cool-Coolant Flow (2)

Flow With Four Pumps ant Flow With Four Operating Pumps Operating 3.

High Pressure 52255 Psia 52255 Psia Pressurizer 4.

Thermal g gjn/Lov P,.g 2 Applicable Limits Replaced by Variable g

Pressvre High Power Trip and 1750 Pain Minimum Low-Pressure Setting Steam Generator Not Lower Than the Cen-Not Lover Than the Cen-Low Water Level ter Line of Feed-Water ter Line of Feed-Water Ring Ring

/

/

/

6.

SteamGenerag 2500 Psia 2500 Psia Low Pressure 7.

Containment High 53.70 Pr')

53.70 Paig Pressure (1) The VHPT can be 30% of rated power for power levels 5 20% of rated power.

(2) May be bypassed below 10"4% of rated power provided auto bypass removal circuitry is operable.

For low power physics tests, thermal margin / low pressure, primary coolant flow and low steam generator pressure trips may be bypassed until their react points are reached (approximately 1750 psia psia, respectively), provided automatic bypass removal circuitry and50g%ratedpowerisoperable.

at 10 (3) Minimum trip setting shall be 1750 psia.

(4) Operation with three pumps for a maximum of 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> is permitted to provide a limited time for repair / pump restart, to provide for an orderly shutdown or to provide for the conduct of reactor internals noise monitoring test measurements.

2-5 Amendment No 71. F0, llS s----m,~