Amend to Application to Amend Licenses DPR-44 & DPR-56, Revising & Updating List of Shock Suppressors Proposed for Inclusion in Tech Specs
ML20070D443
Person / Time
Site: Peach Bottom  
Issue date: 12/13/1982
From: Bauer E, Bradley E
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20070D434 List:
References
NUDOCS 8212150062
Download: ML20070D443 (12)


Text

1 4~

C BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION '

In the Matter of Docket Nos. 50-277 PHILADELPHIA ELECTRIC COMPANY 50-278 AMENDMENT TO MARCH 24, 1981 and AUGUST 6, 1981 APPLICATION FOR AMENDMENT OF FACILITY OPERATING LICENSES DPR-44 & DPR-56 Edward G. Bauer, Jr.

Eugene J. Bradley 2301 Market Street Philadelphia, Pennsylvania 19101 Attorneys for Philadelphia Electric Company 8212150062 B21213 PDR ADOCK 05000277 P

PDR E

3

  • s SEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION In the Matter of Docket Nos. 50-277 PHILADELPHIA ELECTRIC COMPANY 50-278 AMENDMENT TO MARCH 24, 1981 and AUGUST 6, 1981 APPLICATION FOR AMENDMENT OF FACILITY OPERATING LICENSES DPR-44 & DPR-56 i

on March 24, 1981, Philadelphia Electric Company, Licensee under Facility Operating License DPR-44 and DPR-56 for Peach Bottom Units 2 and 3, filed an Application for Amendment of the Licenses which requested that Table 3.ll.D.1, titled " Safety Related Shock Suppressors", of the Technical Specifications 1

contained in Appendix A of the Operating Licenses be amended to conform with the Standa,rd Technical Specifications as required by Mr. D. G. Eisenhut's [[letter::05000277/LER-1980-025-03, /03L-0:on 801103,setpoints on DPIS 2-13-83 & DPIS 2-13-84 (Redundant Reactor Core Isolation Cooling Turbine Steam Line High Flow DPIS Instrumentation) Exceeded Tech Specs.Caused by Setpoint Drift.Instruments Recalibr|letter dated November 20, 1980]].

Subsequently, licensee revised its application of March 24, 1981, by Amendment dated August 6, 1981 to reflect shock suppressor modifications.

Licensee has recently installed additional shock suppressors on the main steam relief valve discharge pipes to bring the pipe support design into conformance with the requirements of NUREG 0661, Safety Evaluation Report, Mark I Containment, Long Term Program.

The modification involves the installation of sixteen new mechanical snubbers to the main steam relief valve discharge piping.

Accordingly, the licensee hereby amends its application of March 24, 1981, as amended August 6, 1981, by revising Table 3.ll.D.1 for Unit 2 (revised pages 234r, and 234s) in accordance with the provisions of section 3.ll.D.5 of the Peach Bottom Technical Specifications to reflect the installation of additional shock suppressors.

Tbc proposed revisions to pages 234m (Units 2 and 3),

234o (Unit 2), and 234p (Unit 3), correct typographical errors in the designation numbers for shock suppressors (snubbers) listed in Table 3.ll.D.l.

2

r

's The Plant Operation Review Committee and the Operation and Safety Review Committee have reviewed these proposed changes l

to the Technical Specifications, and have concluded that they do not involve an unreviewed safety question or a significant hazard consideration and will not endanger the health and safety of the public.

Respectfully submitted, PHILADELPHIA ELECTRIC COMPANY By 1

Vice President i

l I

k

(

)

i 3

l i

l L

s l

i l

COMMONWEALTH OF PENNSYLVANIA i

ss.

COUNTY OF PHILADELPHIA S. L. Daltroff, being first duly sworn, deposes and sayst That he is Vice President of Philadelphia Electric Company, the Applicant herein; that he has read the foregoing Application for Amendment of Facility Operating Licenses and knows the conter.ts thereof; and that the statements and matters set forth therein are true and correct to the best of his 1

knowledge, information and belief.

l i

d?

L i s

Subscribed and sworn to before me this /O day af lh$'Y-Notary Public

, PATRICIA D. CCllOLC Noery FutJ c. PM1tristJa, P:.:!xdr.td3 Cn.

My Comrn. mon Es;.res ivarury 10,12S I

a$

l' 4

w-

)

CERTIFICATE OF SERVICE i

I certify that service of the foregoing Application was made upon the Board of Supervisors, Peach Bottom Township, York County, Pennsylvania, by mailing a copy thereof, via first-class j

mail, to Albert R. Steele, Chairman of the Board of Supervisors, R.D. No. 1, Delta, Pennsylvania 17314; upon the Board of Supervisors, Fulton Township, Lancaster County, Pennsylvania, by mailing a copy thereof, via first-class mail, to George K.

{

Brinton, Chairman of the Board of Supervisors, Peach Bottom, Pennsylvania 17563; and upon the Board of Supervisors, Drumore Township, Lancaster County, Pennsylvania, by mailing a copy thereof, via first-class mail, to Wilmer P. Bolton, Chairman of the Board of Supervisors, R.D. No. 1, Holtwood, Pennsylvania l

17532; all this 13th day of December 1982.

/

?

)Yhlh EugepeJ. Bradley I

Attorney for Philadelphia Electric Company a

l i

i

}

4 a

PBAPS Unit 2 TABLE 3.ll.D.1 Safety Related Shock Suopressors (Snubbers)

~

HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUMBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.ll.D.4.b.

6-DDNL-S-12 Feedwater Drywell 155 Y

Y H

6-DDNL-S-13 Feedwater Drywell 155 Y

Y H

6-DDNL-S-14 Feedwater Drywell 155 Y

Y H

9-HB-H51 Torus Vac. Bkr.

116 N

N M

m 9-HB-H54 Torus Vac. Bkr.

116 N

N M

10-HB-S-1 RHR Torus Room 93 N

N H

l 10-HB-S-2 RHR Torus Room 93 N

N H

)

10-HB-S-7 RHR B RHR Room 124 N

N H

10-HB-S-8 RHR Torus Room 93 N

N H

10-GB-S-12 RHR C RHR Room 98 N

N H

10-GB-S-43-1 RHR Torus Room 130 Y

N H

l 10-GB-S-43-2 RHR Torus Room 130 Y

N H

10-GB-S-44 RHR Torus Room 128 Y

N H

10-GB-S-48 RHR B RHR Room 124 N

N H

i 10-GB-S-49 RHR B RHR Room 124 N

N H

10-GB-S-50 RHR B RHR Room 98 N

N H

10-GB-S-51 RHR C RHR Room 98 N

N H

PBAPS Unit 2 TABLE 3.ll.D.1 Safety Related Shock Suppressors (Snubbars) i HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUliBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.11.D.4.b.

12-DCN-S-2 RWCU Iso. Valve Rm 173.5 "

Y N

H 12-DCN-S-5 RWCU Drywell 165 Y

Y H

12-DCN-S-7 RWCU Drywell 165 Y

Y H

12-DCN-S-8A RWCU Dryvell 165 N

Y M

14-DCN-S-23 Core Spray Drywell 168 Y

Y H

14-DCN-S-24 Core Spray Drywell 168 Y

Y H

14-DCN-S-26 Core Spray Drywell 168 Y

Y H

14-DCN-C-27 Core Spray Drywell 168 Y

Y H

13-HB-S-1 RCIC RCIC Room 107 Y

N H

13-DDN-S-13 RCIC RCIC ROOM 96 N

N H

13-HB-S-14 RCIC RCIC Room 102 Y

N H

13-DBN-S-15 RCIC RCIC Room 107 Y

N H

13-DBN-S-16 RCIC Torus Room 140 Y

N H

23-DBN-S-1 HPCI HPCI Room 112 Y

Y H

23-DBN-S-2 HPCI HPCI Room 112 Y

N H

PBAPS Unit 2 TABLE 3.ll.D.1 Safety Related Shock Suppressors (Snubbers)

HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUMBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.11 0,4.b.

1-GG-S-10 8--B MSRV Drywell 145 Y

Y M

l-GG-S-109-A MSRV Drywell 145 Y

Y M

l-GG-S-109-B MSRV Drywell 145 Y

Y M

l-GG-S-110-A MSRV Drywell 145 Y

Y M

l-GG-S-110-D MSRV Drywell 145 Y

Y M

l-GG-S-lll-A MSRV Drywell 145 Y

Y M

l-GG-S-lll-B MSRV Drywell 145 Y

Y M

l-GG-S-ll2-A MSRV Drywell 145 Y

Y M

l-GG-S-112-B MSRV Drywell 145 Y

Y M

l-GG-S201 MSRV Drywell 160 Y

Y M

l-GG-S202 MSRV Drywell 160 Y

Y M

l-GG-S203-A MSRV Drywell 160 Y

Y M

l-GG-S203-B MSRV Drywell 160 Y

Y M

l-GG-S204-A MSRV Drywell 130 Y

Y M

Y Y

M l-GG-S204-B MSRV Drywell 130 Y

Y M

l-GG-S205-A MSRV Drywell 160 Y

Y M

1-GG-S205-B MSRV Drywell 160 Y

Y M

l-GG-S206-A MSRV Drywell 160

PBAPS Unit 2 TABLE 3.ll.D.1 Safety Related Shock Suppressors (Snubbers)

HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUMBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.ll.D.4.b.

1-GG-S206-B MSRV Drywell 160 Y

Y M

l l-GG-S207-A MSRV Drywell 125 Y

Y M

l-GG-S207-B MSRV Drywell 125 Y

Y M

l-GG-S208-A MSRV Drywell 125 Y

Y M

l-GC-S208-B MSRV Drywell 125 Y

Y M

l-GG-S209-A MSRV Drywell 125 Y

Y M

l-GG-S209-B MSRV Drywell 125 Y

Y M

Notes for Table 3.ll.D.1 1)

Yes (Y) or No (N) 2)

Hydraulic (H) or Mechanical (M) l l

l

m... ~ _. _ -.. _ _ _ _ _ _ _ _ _

PBAPS Unit 3 TABLE 3.11.D.1 4

Safety Related Shock Suppressors (Snubbers)

HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUMBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.ll.D.4.b.

6-DDNL-S-8 Feedwater Drywell 168 Y

'Y H

6-DDNL-S-9 Feedwater Drywell 168 Y

Y H

6-DDNL-S-10 Feedwater Drywell 168 Y

Y H

6-DDNL-S-ll Feedwater Drywell 155 Y

Y H

6-DDNL-S-12 Feedwater Drywell 155 Y

Y H

y 6-DDNL-S-13 Feedwater Drywell 155 Y

Y H

6-DDNL-S-14 Feedwater Drywell 155 Y

Y H

9-HB-H51 Torus Vac. Bkr.

116 N

N M

9-HB-H53 Torus Vac. Bkr.

116 N

N M

10-HB-S-1 RHR Torus Room 93 N

N M

10-HB-S-2 RHR Torus Room 93 N

N H

10-HB-S-7 RHR B RHR Room 124 N

N H

10-HB-S-8 RHR Torus Room 93 N

N H

10-GB-S-12 RHR C RHR Room 98 Y

N H

1C-GB-S-43-1 RHR Torus Room 130 Y

N H

10-GB-S-43-2 RHR Torus Room 130 Y

N H

10-GB-S-44 RHR Torus Room 128 Y

N M

PBAPS Unit 3 TABLE 3.ll.D.1 i

Safety Related Shock Suppressors (Snubbers)

HIGH (1)

RADIATION AREA ESPECIALLY (1)

INACCESSIBLE (1)

SNUBBER SYSTEM DURING DIFFICULT DURING NORMAL NUMBER LOCATION AND ELEVATION SHUTDOWN TO REMOVE OPERATION TYPE (2)

See 4.ll.D.4.b.

13-HB-S-23 RCIC RCIC Room 103 Y

Y H

23-DBN-S-1 HPCI Torus Room 121 Y

Y H

23-HB-S-1A HPCI HPCI Room 103 Y

Y H

l23-HB-S-2A HPCI HPCI Room 103 N

Y H

23-HB-S-3A HPCI HPCI Room 100 Y

Y H

23-DBN-S-6-1 HPCI Torus Ecom 121 Y

N H

23-DBN-S-6-2 HPCI Torus Room 121 Y

N H

23-DBN-S-22 HPCI Drywell 155 Y

Y H

23-DBN-S-23 HPCI Drywell 155 Y

Y H

23-DDN-S-29 HPCI HPCI Room 117 N

N H

23-DDN-S-33 HPCI HPCI Room 93 N

N H

23-DDN-S-47 HPCI Torus Room 121 N

N M

27-HCR-S-187 HPCI B/D Core 127.5 N

N M

Spray 27-HCR-S-188 HPCI Torus Room 122.8 N

N M

"