ML20069K737

From kanterella
Jump to navigation Jump to search
Telecopy RO 50-259/83020:on 830418,leakage Rate for Line a MSIV Found Above Tech Spec Limit.Caused by Leakage Past Main Valve Seat.Corrective Maint & long-term Mod Planned
ML20069K737
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 04/18/1983
From: Coffey J
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
RO-50-259-83020, NUDOCS 8304260467
Download: ML20069K737 (1)


Text

. ..- . . - . -

L52 880418 808 xc: NUC PR' ARMS, 1520 CST 2-C iMRCPEgtgN TELECOPY TO NRC T. G. Campbell, ' 1760 CST 2-C

, .4 3HTj;,C,h iiGi,s Apr. 18, 1983 G. L. Paulk, NRC T. L. Chinn, BFN C. W. Crawford, 670 CST 2-C

_ U. g Region g g a g Commission A. W. Crevasse, 401 UBB-C G. 3. Harrison, Plt Supt Off(

101 Marietta Street, NW L.'M. Mills, 400 CST 2-C Suite 3100- Shift Engineer Atlanta, Georgia 30303 F. A. Szczepanski,'417 UBB-C W. C. Themison, BFN BFRO-50-259/ 83020 D. L. Williams, W10B85C-K Reported under Technical Specification 6.7.2.a.2 Date of Occurrence: 4/18/83 Time of occurrence: 0400 hours0.00463 days <br />0.111 hours <br />6.613757e-4 weeks <br />1.522e-4 months <br /> Unit 1 Technical Specification Involved: 4.7.A.2.1 and 4.7.A.2.g Conditions Prior to Occurrence

, Unit 1 - Cold shutdown for refueling Unit 2 - at 1045 We Unit 3 - at 1091 WE Identification and Descriotion of Occurrence Performance of Surveillance Instruction'4.7.A.2.g-3 revealed that the leakage rate for "A" line MSIV's was a total of 4883.3806 SCFH. Using conservative assumptions, the leak rate applicable to each valve is 2441.6903 SCFH. This causes the total type B and C tests to exceed 60% La or 655.9 ' SCFH (T. S. 4.7 a.2.g) and causes the technical specification limit of 11.5 SCFH (T. S. 4.7.a.2.1) to be exceeded.

Annarent Cause of occurrence Leakage past the main valve seat.

Other Related Events BFR0 50-259/77023, 78034, 80003, 81014 BFR0 50-260/79007, 80042, 82032 BFR0 50-296/78025, 79014, 80058, 80059, 81073, Corrective Action Taken or Planned Corrective maintenance to valve seating surfaces along with long-term modification on MSIV's.

I. A.6ryyy A. Coffey cting Power Plant Superintendent Browns Ferry Nuclear Plant ovv, 8304260467 830418 gDRADOCK05000 yp

.