ML20069K689

From kanterella
Jump to navigation Jump to search
Significant Deficiency Rept SD 413/83-06 Re Metallurgical Defects in Limitorque Motor Pinion Gear.Initially Reported on 830318.Failure Could Preclude Active Valve Completing Safety Function.Defective Gear Replaced
ML20069K689
Person / Time
Site: Catawba 
Issue date: 04/15/1983
From: Tucker H
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8304260448
Download: ML20069K689 (2)


Text

s.

.j DUKE POWER GOMPANY P.O. BOX 33180 CHARLOTTE, N.O. 28242 HAL B. TUCKER retzpuowz VICE P, EBIDENT (704) 373-4531 NUCLEAR PRODUCTION April 15, 1983 D

Mr. James P. O'Reilly, Regional Administrator Q

19 U. S. Nuclear Regulatory Connission

o Region II 101 Marietta Street, NW, Suite 2900
.gi Atlanta, Georgia 30303 3

.O C

Re: Catawba Nuclear Station CD Unit 1 Docket No. 50-413

Dear Mr. O'Reilly:

i Pursuant to 10 CFR 50.55e, please find attached Significant Deficiency Report SD 413/83-06.

Very truly yours, C <-J Hal B. Tucker RWO/php Attachment cc: Director INP0 Records Center Office of Inspection and Enforcement Suite 1500 U. S. Nuclear Regulatory Connission 1100 Circle 75 Parkway Washington, D. C. 20555 Atlanta, Georgia 30339 Mr. P. K. Van Doorn Mr. Robert Guild, Esq.

NRC Resident Inspector Attorney-at-Law Catawba Nuclear Station P. O. Box 12097 Charleston, South Carolina 29412 Palmetto Alliance 213515 Devine Street Columbia, South Carolina 29205 OhW 8h4260448830425 ADOCK 05000413 g

PDR A t~.-

S

W e

DUKE POWER COMPANY CATAWBA NUCLEAR STATION SIGNIFICANT DEFICIENCY

~ REPORT' NUMBER:

SD 413/83-06 REPORT DATE:

April 15,1983 FACILITY:. Catawba Nuclear Station, Unit 1 IDENTIFICATI0N'0F DEFICIENCY:

Metallurgical defects in motor pinion gear. identified February 1.7,1983.

INITIAL REPORT:

Initial report was made to Mr. A.'Ignatonis, Region II NRC, on March 18, 1983 by Messrs. W. O. Henry.and J. K. Berry, Duke Power Company.

DESCRIPTION'0F' DEFICIENCY:

Motor pinion gear on.Limitorque actuator serial number 249637, Westinghouse valve serial number 10000GM88FME01D04S740002, has metallurgical defects in the form of cracks and porosity in two gear teeth. Valve is a ten inch gate valve, Duke. item number 9J-209, tag number 1NIO88B. This active valve was supplied per Duke Power Desig'n Specification CNS-1205.00-0008 and Mill. Power Order A-98524. The valve is a low pressure accumulator tank discharge isolation valve.

' ANALYSIS OF SAFETY IMPLICATIONS:

Failure of motor pinion gear could preclude this active valve completing its safety function.

CORRECTIVE' ACTION:

Defective gear has been replaced. Duke considers this defect to be an isolated case.