Text

1 POWER AUTHORITY OF THE STATE OF NEW YORK 10 CoLUMaus CincLE NEW YoRM. N. Y.1o019 42128 397 6200 LERoy w S LAsR oes e.v.a.o se e c o m TRUSTEES W A LTE R T. KICINSKI 9

April 22,1983

,OHNS.DYSOM g..'.'.".'..".'[........

"j"8,,,

,,, g G ORGE6 M M W JOSEPH R.SCHMIEDER

= = = = = =

,v,',';;;'g,,,

JPN-83-34 RCwARDw.,LvNN

-'a===

STEPHEN L. D AUM ROBERT I. MILLON Et J AMES L LAROCCA Director of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Attention:

Mr. Domenic B. Vassallo c

Operating Reactors Branch No. 2 Division of Licensing

Subject:

James A. FitzPatrick Nuclear Power Plant Docket No. 50-333 Proposed Changes to the Technical Specifications Related to Reactor Protection System Electricical Protection Assemblies

References:

1.

August 7, 1978 letter, T. A.

Ippolito (NRC) to G.T. Berry (PASNY).

2.

September 24, 1980 letter, T.A.

Ippolito (NRC) to G.T.

Berry (PASNY).

3.

July 28, 1982 letter, D.B. Vassallo (NRC) to L.W.

Sinclair (PASNY), same subject.

4.

February 18, 1981 letter, R.J. Pasternak (PASNY) to B.H. Grier (NRC) (JAFP-81-0132).

Dear Sir:

Enclosed for filing are three (3) signed originals and nineteen (19) copies of a document entitled, " Application for Amendment to Operating License", together with forty (40) copies of Attachments I and II thereto, comprising a statement of the proposed changes to the Technical Specifications and the associated Safety Evaluation.

hC I

IJ&

SBA4PD88PSSUl5g y yeao o P

This proposed amendment was prepared to assure operability of plant modifications made in response to NRC letters. dated August 7, 1978 and September 24, 1980 (References 1 and 2 respectively), in which you identified deficiencies in the design of the Hatch 2 regulator system for the motor generator sets which supply power to the Reactor Protection System (RPS).

In general, the problem involved the possibility of the motor generator producing power of a quality outside acceptable limits for the RPS.

These changes are proposed as a result of our review of the sample Technical Specifications enclosed with Reference 3.

Two new Sections, 3.9.G and 4.9.G, add operability and surveillance requirements for RPS electric power monitoring on pages 222c and 222d.

Corresponding Bases Sections have been added on pages 224a and 226, which describe the purpose of each limiting condition or surveillance requirement.

In accordance with Reference 1, the Authority has been conducting a program of augmented surveillance since August 11, 1978 (Reference 4) on the RPS power supply system.

The installation of this protective equipment and the attached technical specifications eliminate the need for this additional surveillance.

Therefore, we will discontinue this surveillance upon approval of these changes.

The proposed changes are Attachment I included with this letter.

Attachment II is the associated Safety Evaluation.

The Authority has classified this Application for Amendment to the Operating License as Class III, as it involves a single safety issue.

Enclosed is a check in the amount of $4,000 as the filing fee per 10 CFR Section 170.22, which the Authority pays under protest pending a final determination of the legality of the fee schedule.

Very truly yours, v

a

.P. Bayne Executive Vice President Nuclear Generation cc: Mr. J.

Linville Resident Inspector U.S. Nuclear Regulatory Commission P.O.

Box 136 Lycoming, NY 13093