Text

_

TABLE 7-1 (Rev. 1)

SPENT FUEL P0OL COOLING SYSTEM HEAT" LOAD AND OPERATING TEMPERATURES WITH STORAGE OF SURRY SPENT FUEL Ih THE NORTH ANNA 1 AND 2 FUEL P0OL Fuel Pool Temperature, OF Decay Heat MBTU/HR 1P2C 2P2C No Surry Fuel High Density Racks (966)

Normal 19.4 135.4 130.4 Abnormal 35.9 159.5 154.0 No Surry Fuel Neutron Absorber Racks (1737)

Normal 23.1 138.5 135.0 Abnormal 39.2 156.5 151.0 Surry Fuel (500)

High Density Racks (966)

Normal 20.5 136.0 132.5 Abnormal 36.3 153.0 147.5 Surry Fuel (500)

Neutron Absorber Racks (1737)

Nonnal 24.1 140.0 136.0 Abnormal 40.0 160.0~

148.5 1P2C - 1 Pump 2 Coolers 2P2C - 2 Pumps 2 Coolers 8210260136 821021

~

PDR ADOCK 05000338 P

PDR