ML20069K283

From kanterella
Jump to navigation Jump to search
Revised Table 7-1 to Summary of Info in Support of Increasing Spent Fuel Storage Capacity at North Anna Units 1 & 2
ML20069K283
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 10/21/1982
From:
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
Shared Package
ML20069K274 List:
References
NUDOCS 8210260136
Download: ML20069K283 (1)


Text

_

TABLE 7-1 (Rev. 1)

SPENT FUEL P0OL COOLING SYSTEM HEAT" LOAD AND OPERATING TEMPERATURES WITH STORAGE OF SURRY SPENT FUEL Ih THE NORTH ANNA 1 AND 2 FUEL P0OL Fuel Pool Temperature, OF Decay Heat MBTU/HR 1P2C 2P2C No Surry Fuel High Density Racks (966)

Normal 19.4 135.4 130.4 Abnormal 35.9 159.5 154.0 No Surry Fuel Neutron Absorber Racks (1737)

Normal 23.1 138.5 135.0 Abnormal 39.2 156.5 151.0 Surry Fuel (500)

High Density Racks (966)

Normal 20.5 136.0 132.5 Abnormal 36.3 153.0 147.5 Surry Fuel (500)

Neutron Absorber Racks (1737)

Nonnal 24.1 140.0 136.0 Abnormal 40.0 160.0~ 148.5 1P2C - 1 Pump 2 Coolers 2P2C - 2 Pumps 2 Coolers

~

8210260136 821021 PDR ADOCK 05000338 P PDR