ML20069J172

From kanterella
Jump to navigation Jump to search
Errata & Addenda Sheet 5 to NEDO-24088-1, LOCA Analysis for Browns Ferry Nuclear Plant,Unit 2
ML20069J172
Person / Time
Site: Browns Ferry 
Issue date: 08/31/1982
From:
GENERAL ELECTRIC CO.
To:
Shared Package
ML18025B889 List:
References
77NED360, NEDO-24088-1, NEDO-24088-1-N05-ERR, NEDO-24088-1-N5-ERR, NUDOCS 8210250078
Download: ML20069J172 (2)


Text

.

p NUCLEAR ENERGY BUSINESS GROUP

  • GENER AL ELECTRIC COMPANY SAN JOSE, CALIFORNI A 95125 GEN ER AL h ELECTRIC APPLICABLE TO:

NEDO~24088-1 ER M M Ad ADDMDA PUB LICATiON NO.

77NED360 T.1. E. NO.

SHEET LOCA Analysis for Browns TITLE 5

NO.

Ferry Nuclear Plant Unit 2 August 1982 DATE NOTE: Correct allcopies of the applicable February 1978 publication as specified below.

ISSUE DATE REFERENCES INSTRUCTIONS PARAG APH L NE)

(CORRECTIONS AND ADDITIONS) 01 Page 4-11 Replace with new page 4-11.

NOTE:

Brackets in right-hand margin indicate areas of revision.

l l

i l

1 Of I 8210250078 821015 PAGE DR ADOCK 03000260 PDR

o EEDO-24088-1 Table 4F MAPLHCR VERSUS AVERAGE PLANAR EXPOSURE Fuel Type:

P8DRB265H

]

Average Planar Exposure MAPLHGR PCT 0xidation (Mwd /t)

(kW/ft)

( F)

Fraction 200 11.5 1674 0.003 1,000 11.6 1672 0.003 5,000 11.9 1638 0.003 10,000 12.1 1623 0.003 15,000 12.1 1633 0.003 20,000 12.0 1638 0.003 25,000 11.6 1607 0.002 l

l 30,000 11.2 1561 0.002

(

35,000 10.9 1523 0.002 40,000 10.5 1480 0.001 45,000 10.0 1438 0.001 i

l l

l l

1 l

1 l

l 4-11 i