ML20069H344
| ML20069H344 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 09/29/1982 |
| From: | Diederich G COMMONWEALTH EDISON CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| Shared Package | |
| ML20069H346 | List: |
| References | |
| NUDOCS 8210190509 | |
| Download: ML20069H344 (2) | |
Text
-
,/ ^ N Commonwealth ECoon
/
\\ LaSalleCountyNucitarStation
(
Rural Route #1, Box 220 g
Marseilles, Illinois 61341 Telephone 815/357-6761 September 29, 1982 7
Mr. James G. Keppler Regional Administrator Director of Regulatory Operations Region ill U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137
Dear Sir:
In accordance with LaSalle County Station Unit 1 Facility Operating License HPF-il, Appendix B, Section 3.2, we are submitting to you a copy of the NPDES noncompliances for LaSalle County Huclear Generating Station Permit No. ILOO48151.
J. Diederich Superintendent LaSalle County Station GJD/FRL/J0W/Irw Enclosure l
cc:
DVR Report j
i d.
sato190so9
R OCT.1 5 E POR ADOCM O 373 1-O PDR _ _
A Commonwealth Edison e.**
y LaSallaCountyNuclearStatior:
1:
Rural Route #1, Box 220
.,t 4
Marseilles,Illin2is 61341 Telephone 815/357 6761
.,4 U.S. Environmental Protection Agency Region V, Enforcement Division ATTN:
Chief, Compliance Unit 230 South Dearborn Street Chicago, Illinois 60604 tilinois Environmental Protaction Agency Division of Water Pollution Control Compliance Management Unit 2200 Churchill Road Springfield, Illinois
SUBJECT:
NPDES Noncompliances For LaSalle County Nuclear Generating Station - Permit No. ILOO48151 i
Dear Sir:
In accordance with Standard Condition 12, we wish to submit the following notice of noncompliances, which are listad chronologically in the attached table.
A correction to a previously submitted notice of noncompliance is also enclosed.
If there are any questions, please contact Joe Williams of my staff at (815) 357-6761, extension 201.
J. Dieder ch Mt. 30 GJF/FRL/JDW cc:
Director of Water quality, Environmental Affairs Manager, Nuclear Stations Division
f..
^6 LASALLE COUNTY NUCLEAR GENERATING STATION N.P.D.E.S. PERMIT NO:
ILOO48151 NONCCMPLIANCE REPORT DISCHARGE NUMBER AND DESCRIPTICji:
001c - Lov Volume Waste Radwaste Discharge Tanks PARAMETER AND PERMIT LIMIT:
Total Suspended Solids - 15 mg/l Total Iron - 1.0 mg/l NONCOMPLIANCE, DATE, AND DURATION:
TSS, 22 mg/1, August I, 1982, 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br /> Total Iron, 6.0 mg/1,' August 1, 1982, 13 hours1.50463e-4 days <br />0.00361 hours <br />2.149471e-5 weeks <br />4.9465e-6 months <br /> CAUSE OF NONCOMPLIANCR:
N Hechanical problems with the Radwaste evaporators resulted^ poor quality water being processed to this out fall. This water was known to have been of poor quality prior to processing forward, but was not acted upon due to high water inventories in Radwaste. Once the water was discharged to this out fall tank, it could not be reprocessed, and must be discharged to the cooling Pond Blowdown line.
J CORRECTIVE ACTION:
Operating personnel were notified of the need to reprocess poor quality water, instead of processing it forward. Operating personnel agreed with this, and will reprocess poor quality water. They are also attempting to correct the. problems with the evaporators, which will alleviate the r
need for reprocessing.
{
August 3, 1982 DATE RECOGNIZED AS,A VIOLATION:
August 3, 1982 DATE INVESTIGATED:
)[ O oDj 0 l^ E
?
.