Forwards LERs 82-116/03L-0,82-117/03L-0 & 82-112/03L-0. Detailed Event Analysis Encl
ML20069G923
Person / Time
Site: San Onofre 
Issue date: 10/08/1982
From: Ray H
SOUTHERN CALIFORNIA EDISON CO.
To: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
Shared Package
ML20069G928 List:
References
NUDOCS 8210190309
Download: ML20069G923 (2)


Text

_

CEC 2VED tlEC Southern California Edison Company p h5 S AN ONOFRE NUCLE AR GENC A A TING ST A TION P.O. B O X 12 8 S AN CLEMENTE. C ALIFORNI A 92672

- H. B. R AY

,ete,woNe October 8, 1982 SimTiON = AN Aac.

U. S. Nuclear Regulatory Commission Office of Inspectlon and Enforcement Reglon V 1450 Maria Lane, Suite 210 WaInut Creek, Caiifornla 94596-5368 Attention:

Mr. R. H. Engelken, Regional Administrator

Dear Sir:

Subject:

. Docket No. 361 30-Day Reports Licensee Event Reports Nos.82-112, 82-116 and 82-117 San Onofre Nuclear Generating Station, Unit 2

Reference:

Letters, H. B. Ray (SCE) to R. H. Engel ken (NRC),

dated September 24, 1982, August 27, 1982 and August 13, 1982.

The referenced letters transmitted 30-day written reports and ' Licensee

. Event Reports (LER's) for occurrences involving the Condensate Storage Tank T-121 low water level. As noted in those letters, violations of Technical Specification 3.7.1.3_ continue to occur. A Technical Specif-ication change has been submitted to NRC to alleviate this problem.

Pursuant to Section 6.9.1.13b of Appendix A, Technical Specifications to Operating License NPF-10, for San Onofre Unit 2, this submittal provides the required 30-day written reports and copies of' LER's for three simiIar occurrences.

Limiting Condition for Operation (LCO) 3.7.1.3 requires that while in Modes 1-3,. the Condensate Storage Tank T-121 must be operable with a contained volume of at least 144,000 gallons. The associated Action Statement requires that with the tank declared inoperable, it must be returned to operable status within four. hours or be in at least hot shutdown (Mode 4) within the following six hours. The-Surveil lance Requirement 4.7.1.3 requires verification of the contained water volume at least ~once.cach 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

g7 g

gg j~ g&,

~~

y,g, m

.ADOCK 090003 n

'p?

G_.,

fDE S.M

$ -MY-

r._

R. H. Engelken. -

October 8, 1982 l

i On September 10,1982, with the plant in Mode 2, while feeding the steam

. generators using.the Auxiliary Feedwater Pumps, the water level in Tank T-121 fell below the allowable Ilmit. This tank has its overflow set ebout 5,000 gallons above the Technical Specification limit of 144,000 gallons. Thus, prompt operator action is required to prevent entering the LCO Action Statement.

. The'cause and corrective action of these events were identified in the referenced letters and remain unchanged, it should be noted that modifications have been made to the level indications available to the operators to facilitate precise control.

The violations of Technical Specificalon 3.7.1.3 occurred numerous times and may continue to occur until the proposed Technical Specification change is approved, 'notwithstanding the very best ef forts of the operators to maintain tank level within the 5,000 gallons deadband.

LER 82-112 addresses the occurrence on September 10, 1982. LER's82-116 and 82-117 address the same type of occurrences.

If there are any questions, please contact me.

Sincerely, k

Enclosures:

LER's82-112, 82-116 and 82-117 cc:

A. E. Chaf fee.(USNRC Resident inspector, San Onof re Unit 2)

U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Office of Management Information & Program Control Institute of Nuclear Power Operations

\\