b SEWOOK STATION LJ PUBLIC SERVICE Engineering Offic :
Companyof NewHampshire 1671 Worcester Road Framinoham, Mossochusetts 01701 (617) - 872-8100 March 3,1983 SBN 484 T.F. B4.2.7 United States Nuclear Regulatory Gmmission Region I 631 Park Avenue King of Prussia, PA 19406 Attention:
Mr. Richard W. Starostecki, Director Division of Project and Resident Programs Re f e re nce s :
(a) Construction Permit CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) USNRC letter, datc.d February 3,1983, " Combined Inspection Nos. 50-443/82-16 a nd 50-444/82-14," R. W. Starostecki to W.
C. Tallman
Subject:
Response to Inspection Nos. 50-443/82-16 and 50-444/82-14 Dea r Sir:
In response to the violations reported in the subject inspection, we of f er the f ollowi ng:
NRC Notice of Violation (443/82-16-01):
10CFR50, Appendix B, Criterion X and Section 17.1.1.10 of the Seabrook Station FSAR require establishment of an inspection program which verifies the conformance of activities to specific quality criteria. With regard to criteria f or the physical independence of electrical systens, the FSAR endorses IEEE Standard 384 by prescribing, i n Sec tions 1.8 a nd 8. 3.1.2. b. 5, general conformance to Regulatory Guide 1.75 (Revision 2).
IEEE Std 384 requires that the independence of Class 1E systems be maintained subsequent to the design basis f ailure of non-Category I components.
Additional c riteria are provided by Fischbach Procedure FECP-504, which prohibits the installation of Class 1E cable in non saf ety raceways.
Co nt ra ry t o t he a bove, as of January 7,1983, the inspection program f or cable i nstallation f ailed to identify nonconformance to certain criteria in both IEEE 384 and Fischbach Procedure FECP-504, in that a Class IE cable
( A47-F16) was i nstalled i n a non-Ca tegory I, non safety raceway.
The overall program of inspection of Cable A47-F16, to include design and routing checks and quality cont rol exami nation, lacked suf ficient definition to preclude such a case of improper installation.
This is a Severity Level IV Violation (Supplement II).
8303220148 g30317
{DRADOCK 05000443 PDR
Unit'ed States Nuclear Regulatory Commission Ma rch 3, 1983 Attention:
Mr. Richard W. Starostecki Page 2
Response
Corrective Action Taken and Results Achieved:
Cable routings are controlled by a UE&C program entitled "CASP."
In the case noted, UE&C engineering input into CASP incorrectly requested a red-jacketed (saf ety-related) cable to be routed to a non-saf ety area.
The FBM (cable installer) inspection program, at the time, did not address possible CASP errors relative to the routing of safety-related cable into non-saf ety a reas.
Subsequent to the NRC inspection, FBM issued an interim procedure change requiring that cable pull slips f or saf ety-related cable with mixed raceway (qualified and non qualified) be returned to engineering for evaluation and resolution.
Corrective action was implemented on January 13, 1983.
Very truly yours, YANKEE ATOMIC ELECTRIC CONTANY J. DeVincentis Project Manage ALL /f sf cc: Atomic Safety and Licensing Board Service List 5
ASLB SERVICE LIST Philip Ahrens, Esquire Assistant Attorney General Department of the Attorney General Augus ta, ME 04333 Representative Beverly Hollingworth Coastal Chamber of Commerce 209 Winnacunner Road Hampton, NH 03842 William S. Jordan, III, Esquire Harmon & Weiss 1725 I Street, N.W.
Suite 506 Washington, DC 20006 E. Tupper Kinder, Esquire Assistant Attorney General Office of the Attorney General 208 State House Annex Concord, NH 03301 Robert A. Backus, Esquire 116 Lowell Street P.O. Box 516 Manchester, NH 03105 Edward J. McDermott, Esquire Sanders and McDermott Professional Association 408 Lafayette Road Hamp ton, NH 03842 Jo Ann Shotwell, Esquire Assistant Attorney General Environmental Protection dureau Department of the Attorney General One Ashburton Place, 19th Floor Boston, MA 02108
. -