l g4 OPER.ATING DATA REPCRT DOCKET NO.50-23s i
DATE 2-1-83 COMPLETED SY I. Kelly r
TELEPHONE
'S'a'
" *-8200 OPERATING STATUS Notes
- 1. Unic Name:
Indian Point ?:o. 3 Nuci.ar rev.y et. :
Janu wr 1993
- 2. Reporting Period:
3025
- 3. Licensed Thermal Power (MWt):
1013
- 4. Nameplate Rating (Gross MWe):
j 965 S. Desis Electrical Rating (Net MWe):
926
- 6. Maximum Dependable Capacity (Gross MWe):
'891'
- 7. Maximum Dependable Capacity (Net MWi):
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Sir.co Last Report. Give Reasor:s:
- 9. Pow:r Level To Which Restricted,If Any (Net MWe):
- 10. Reasons For Restrictions. !f Any:
Yr to-Date Cumulative This Month 744 744
' 56,305.0
- 11. Heurs in Reporting Period 0
0 34.090.a
- 12. Number Of Hours Reactor Was Critica!
0 O'
0
- 43. Reactor Resene Shutdown Hours
~
0 32,913.1 0
- 14. Heurs Generster On.Line 0
0 0
l-15. Unit Reserve Shutdown Hours o
n an.141.an1
- 16. Gross Thermal Energy Genersted (MWH) 0 0
26,298,300 I 17. Gross Electrical Energy Genersted (MWH) 0
-0 25,183.443
- 15. Nst Electrical Energy Generated (MWH) 0 0
58.5
- 19. Unit Se:vice Fsetor 58.5 0
0
- 20. Unit Availability Factor 0
0 50.2 I 21. Unit Capacity Factor (Using MDC Net:
0 0
46.3
- 22. Unit Capacity Factor (Using DER Net) 0 0
14.3
- 23. Unit Forced Outage Rate
- 24. Shutdowns Scheduled Over Next 6 Months IType.Date.and Duration of Esch):
Refuelina Outace in Proaress upon compie non or ococculec
- taintenance EST. date (April 83) 25, if Shut Down At End Of Report Period. Estimated Date of Startup:
Forecast Achieved
- 26. Units la Test Status (Prior to Commercial Operation):
8303150536 830209 INITIAL CRITICALITY PDR ADOCK 05000286 R
PDR INTTIAL ELECTRICITY COSIMERCIA L OPERATION
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.
50-286 Indian Point UNIT Ma 3 DATE Pobruary 1.
1983 COMPLETED BY L Kallv TELEPHONE (914) 739-8200 MONiil January 1983 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL i
(MWe-Net)
(Mwe. Net) 1 0
0 17 2
n 33 0
3 0
0 39 4
0 20 0
5 0
21 0
6 0
22 0
7 0
0
~
~
23 8
0 0
24 9
0 0
25 10 0
0 26 11 0
0 27 12 0
0 28 13 0
0 29 14 0
0 30 15 0
o 3;
16 0
INSTRUCHONS On this format. list the average daily unit power level in MWe Net for each day in the reporting month. Cornpute to the nearest whole rnegawatt.
(9/77)
~
~,w r---
e
==*
UNIT Sif0TDOWNS AND POWER REDUCI10NS DOCKET NO.
50-286 UNITNAME Indian Point No. 2 DATE 2-1-83 REPORTMONTIf January 83 COMPT.ETED BY L KelIV TELEPfl0NE f 914) 719-n200 "L
's e 2 5
e re 2 _e g
gEX Licensee P
Me.
Date g
gg g
,, g E Event u$
O"',,
Cause & Corrective c
j'8 Acti,m to F
~$E, 5
j5g Report
- iNG 3
Prevent Recturence f
04 820325 S
744 B&C N/A N/A N/A Unit in a scheduled cycle III-IV refueling and maintenance outage.
1 i
I 1
t 1
1 2
3 4
F: Finced Reason:
Method:
Enhibit Instructions 4
S: Scheduled A-Equipment Failure (Explain) 1 Manual for Preparation of Data B Maintenance of Test 2-Manual Scrsm.
.C. Refueling 3-Automatic Scram.
Entry Sheets for Licensee Event Repori ILER) File (NUREG-D-Regniatory Restriction 4-Other (Explain)~
0161)
E Operator Training & License Examination
~
F. Administrative 5
G-Operatiemal Error (Explain) 19/77) 11-01her (Explain)
Exhibit,
- Same Source
MONTHLY I & C CATEGORY I REPORT January 1983 Month Date W.R.
Equipment Malfunction Corrective Action IC-1-1625-02 1-15-83 Fan Cooler Unit #32 Recirculation fan air low flow, Replaced defective air flow alarmed continuously switch IC-1-1787-02 11-22-82 Fuel storage building Improper reading.
Repaired broken wire at Area Radiation Monitor detector.
R-5.
IC-1-1877-02 11-19-82 Waste Gas Compressor Transmitter inoperative Replaced transmitter Pressure Transmitter IC-1-1914-02 1-15-83 Control Room Air Air conditioner does not func-Replaced agastat time delay Conditioning tion in automatic mode.
relay in automatic control circuit.
IC-1-1917-02 12-2-82 Containment Atmosphere Improper reading.
Replaced GM tube in detector Radiation Monitor R-12 IC-1-1940-02 1-15-83 Reactor Coolant Drain Tan k Control room override switch Corrected wiring to Relay to gas analyzer isolation inoperative.
R-1.
valve 1788.
N e
0 0
HONTitLY MAINTENANCE REPORT 9.=
1983 3, ni,m,
" Month WR 9 DATE EQUIPMENT MALFUNCTION CORRECTIVE ACTION I-2999 l-6-83 Blow in door, Fan Cooler Door cable broken Replaced cable Unit #31 I-3180 1-10-83 Accumulator #34 Nitrogen Defective limit switch
. Replaced switch fill valve 891D I-3181 1-25-83 Plant vent sample pump to Gasket leak Replaced gasket and retorqued R-13 housing I-3239 l-6-83 Fan Cooler Unit #34 Motor cooler leak Soldered leak I-3282 1-15-83 Sampling pump to containment Damaged carbon vanes Replaced vanes and belts atmosphere radiation monitor R-11/R-12 I-3288 1-20-83 Spent fuel pool pump #32 Seal leak Replaced mechanical seal I-3297 l-7-83 Fan Cooler Unit #34 SWN-41 Body to bonnet gasket leak on idlet Replaced gasket on valve isolation valve I-3336 1-15-83 Steam Generator #34 Sampling Solenoid coil malfunction Replaced coil Valve 1226 Replaced valve assembly I-3346 1-20-83 Spent Fuel Pool Pump #32 Body to bonnet leak casing vent valve e
e e e O
h e e
. =..
i-
SUMMARY
OF OPERATING EXPERIENCE I
Indian Point Unit 3 remained shutdown for the entire reporting period.. Unit repairs, modifications and preventive maintenance are proceeding as scheduled.
j Steam generator sleeving has been completed.
girth weld repairs are in progress.