ML20066B374

From kanterella
Jump to navigation Jump to search
Amend 112 to License NPF-6,deleting Exclusion of Type C Leakage Tests for Containment Isolation Check Valves in Table 3.6-1
ML20066B374
Person / Time
Site: Arkansas Nuclear 
Issue date: 12/31/1990
From: Quay T
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20066B375 List:
References
NPF-06-A-112 NUDOCS 9101070102
Download: ML20066B374 (4)


Text

-

UNITED STATES 8"

'o NUCLEAR REGULATORY COMMISSION

-S

. i-WMHING TON. D. C. 20565

[l-

/

c%

p ENTERGY 0'ERATIONS, INC.

DOCKEl NO. 50-368 ARKANSAS NUCLEAR ONE. UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.112 License No. NPF-6 l, _

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Entergy Operations, Inc.

(the licensee). dated October 9, 1990, complies with the standards and requirements'of the Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and regulations set forth in 10 CFR-Chapter I; 4

B.

The facility will operate _in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is. reasonable assurance:

(i) that the activities authorized by this amendment can be conducted without udangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with.the Commission's regulations; D.

.The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of=the public; and E.

The issuance o.

~his amendment is in accordance with 10 CFR Part 51

'of the Commission's regulations'and all applicable requirements have been satisfied.

l l-9101070102 901231 PDR ADOCK 05000360 P

PDR

.. ~.

~2-2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of facility Operating License No.

NPf-6 is hereby amended to read as follows:

2.

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No.112, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

The license amendment is effective 30 days after its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION h < h ny tcylc%

Theodore R. Quay, Director Project Directorate IV-1 Division of Reactor Projects 111, IV, and V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of issuance: December 31, 1990

F MTACHMENT TO LICENSE Af;EfMENT NO.112 FAClllTY OFERATING LIC_NSE NO. NPF E

.DOCJETNO.50-368 Revise-the f ollwirig page of the Appendix' A* Technical Specifications with

.the attacheo page. The revised page is identifieo by Amendment nurat,tr and -

contains vertic61 lines inciic6 ting the area of change.

1he corresponding overleef pages are also previded to maintain document completeress.

REMOVE PAGE-INSERT PAGE l..

3/4 6-21 3/4 6-21 I

4 i

i i

l

'l I

l l

I 1

l'

\\

l

)

i

. -...,, _,...,........ -- ~~

..a._..~....,,,.

, _,.. _ ~. -..

9 TABLE'3.6-1 (Cont.)

E C

CONTAINMENT ISOLATION VALVES h!

PENETRATION ISOLATION v'

NUMBER VALVE NUMBER FUNCTION TIME (SEC) g C. MANUAL (Cont.)

U 2C3 2CV-5432#

Fuel Transfer Tube Isolation (outside)

N.A.

D. OTHER (Check Valves) 2P9 2N -18 H.P. Nitrogen to SI Tanks (inside)

N.A.

2 2P39 2CVC-78 Quench Tank Makeup & Demin Water Supply (inside)

N.A.

2P40 2FS-37 Fire Water Isolation (inside)

N.A.

2P41 2N -1 L.P. Nitrogen Supply Isolation (inside)

N.A.

2 2P43 25A-69 Service Air Supply Isolation (inside)

N.A.

R>

2P46 2BA-216 Breathing Air Supply Isolation (inside)

N.A.

2P51 2AC-49 Chilled Water Supply Isolation (inside)

N.A.

2P52 2CCW-38 CCW to RCP Coolers Isolation. (inside)

N.A.

  1. Not subject to Type C leakage tests.
  • May be opened on an intermittent basis under administrative control.

E it a.

c

.O -

n2

_