ML20066A239

From kanterella
Jump to navigation Jump to search
Amend 35 to License NPF-6,allowing Testing of Electrical Containment Penetration Conductor Circuit Breakers Per Manufacturer Recommendations
ML20066A239
Person / Time
Site: Arkansas Nuclear 
Issue date: 10/15/1982
From: Clark R
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20066A241 List:
References
NUDOCS 8211050184
Download: ML20066A239 (23)


Text

. _ _. _ __

y/

o,,

UNITED STATES p,

NUCLEAR REGULATORY COMMISSION 5

j WASHINGTON, D. C. 20555

~s*****/

ARKANSAS POWER & LIGHT COMPANY DOCKET NO. 50-368 ARYANSAS NUCLEAR ONE, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 35 License No. NPF-6 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Arkansas Power & Light Company (the licensee) dated August 23, 1982, as supplemented September 22, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in. conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical ~ to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

8211050184 821015 PDR ADOCK 05000368 P

PDR

O 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated-in the ' attachment to this license amendment, and paragraph 2.C(2) of Facility Operating License No. NPF-6 is hereby amended to read as follows:

j (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 35, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

- 3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION I

l g

w obert. Clark, Chief Operating Reactors Branch #3 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: October 15, 1982 6

4 e,e me'.t ee a

e 8

e

ATTACHMENT TO LICENSE AMENDKENT NO. 35 FACILITY OPERATING LICENSE NO. NPF-6 DOCKET NO. 50-368 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised p. ages are identified by Amendment number and contain vertical lines indicating the area of change.

Cor-responding overleaf pages are provided to maintain document completeness.

Remove Pages Insert Pages 3/4 8-11 3/4 8-11 through through 3/4 8-32 3/4 8-32 9

A e

l r

I

. S

' II T **W...DINM

.~ w,..,

.r j

, 4 l

l l

m r

n E

ELECTRICAL POWER SYSTEMS

/.

)

2 CONTAINMENT PENETRATION CONDUCTOR OVERCURilENT PROTECTIVE DEVICES LIMITING CONDITION FOR OPERATION f

3 3.8.2.5 All containment penetration conduttor overcurrent protective devices shown in Table 3.8-1 shall be OPERABLE.

T s

a APPLICABILITY:

MODES 1, 2, 3 and 4.

A ACTION:

x With one or more of the. containment penetration conductor overcurrent protective devices shown'in Table 3.8-1 inoperable:

De-energize the circuit (s) by tripping the associat'ed backup a.

=.

circuit breaker within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> and verifying the backup j

circuit breaker to be tripped at leas?. once per 7 days thereaft,er; the provisions of Specification 3.0.4 are not applicable to,overcurrent devices in circuits which have their backup circuit breakers tripped, or b.

Be in at least H0T $TANDBY vitHn the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the followir.g'30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

s SURVEILLANCE RE0VIREMENTS 4.8.2.5 All conCainment penetration conductor overcurrent protective

]

devices shown in Table 3.8-1 shall be demonstrat.ea OPERABLE in accordance sith the manufacturers' recommendations:.

a.

At least once per 18 months:

1. -

For at least one 6.9 kv reactor coolant pump circuit, such that

'~

all reactor coolant pump circuits are demonstrated OPEARABLE at 9

least once per 72 months, by performance of:

d i \\

(a) A CHANNEL CALIBRATION of the associated protective relays, and s,

4 2

\\

(b) An integrated system functional test which includesi 3

simulated automatic actuation of the system and verifying that each relay and associated circuit breakers and control circuits function as designed.

7 1

l 8

s t

)

4

-a ARKANSAS - UNIT 2 3/4 8-11 Amendman't No. 35 7

1 i

ELECTRICAL POWER SYSTEMS SURVEILLANCE REOUIREMENTS (Continued) 2.

For molded case circuit breakers, by performance of a functional test of a least one circuit breaker of each type, such that all circuit breakers.of each type are demonstrated OPERABLE at least once per N x 18 months, where N is the number of circuit breakers of each type.

The functional test shall consist of injecting a current input at the specified setpoint

.to the circuit breaker and verifying that the circuit breaker functions as designed.

If any circuit *ureaker fails to function as designed, all other circuit breakers of that type shall be tested.

b.

At least once per 60 months by subjecting each circuit breaker to an inspection and preventive maintenance in accordance with procedures prepared in conjunction with its manufacturer's recommendations.

I

~

1 1

4 is

!N

,RKANSAS - UNIT 2 3/4 8-12 Amendment No. b5 V

TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED l

A.

6900 KVAC 152-11 152-13, or Switchgear 2H1 RCP 2P32A 152-14, or 152-15 152-12 152-13, or Switchgear 2H1 RCP 2P32D 152-14, or l

152-15 t

152-21 152-23, or Switchgear 2H2 RCP 2P32B 152-24', or 152-25 152-22 152-23, or Switchgear 2H2 RCP 2P32C 152-24, or 152-25 B.

480 VAC 52-131 None, circuit 2B1 Containment shall not be Building energized Crane 2LM2 unless plant is shutdown 52-P501 52-523 Primary - 2PPS Pressurizer thru Backup - 2B5 Proportional 52-P504 Heater Bank 1 52-533 52-512 285 Hydrogen Recombiner 1 52-P601 52-623 Primary - 2PP6 Pressurizer thru Backup - 286 Proportional 52-P604 Heater Bank 2 ARKANSAS'- UNIT 2 3/4 8-13 Amendment No. 35

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

-PRIMARY BACKUP DEVICE-DEVICE LOCATION OF SYSTEM ENBER NUMBER DEVICES POWERED 52-633 52-612 286 Hydrogen Recombiner 2 52-731 52-732 2B7 MCC 2B71 52-824 52-823 288 MCC 2B81 52-P70f 52-922 Primary,2PP7 Pressurizer thru Backup 52-P706 Backup - 289 Heater Bank 3 5'2-P901 52-923 Primary - 2PP9 Pressurizer thru Backup 52-P906 Backup - 2B9 Heater Bank 5 52-P801 52-1022 Primary - 2PP8 Pressurizer thru Backup 52-P806 Backup - 2B10 Heater Bank 4 52-1001 52-1023 Primary - 2PP10 Pressurizer thru Backup 52-1006 Backup - 2810 Heater Bank 6 C.

480 VAC MCC 52-51A4 52-51H2 MCC 2851 Reactor Cavity Cooling Fan l

2VSF34A-1 l

52-51B2 52-51H3 MCC 2851 Containment l

Sump Isolation MOV 2CV-2060-1 l

52-5103 52-51H4 MCC 2B51 Containment l

Recirculating Fan 2VSF31A-1 ARKANSAS'- UNIT 2 3/4 8-14 Amendment No.35 i

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM RUMBEE NUMBER DEVICES POWERED 52-5104 52-51H5 MCC 2851 Containment Recirculating Fan 2VSF31C-1 52-51E2 52-51H6 MCC 2851 Reactor Drain Tank Drain Isolation Valve 2CV-2202-1 52-51FI 52-51H7 MCC 2851 RCP Controlled Bleedoff Isolation Valve 2CV-4846-l' 52-51F2 52-51H8 MCC 2B51 Safety Injection Tank 2T2A Discharge MOV 2CV-5003-1 52-51G2 52-51L2 MCC 2B51 Shutdown Cooling Return Header Iso.

Valve 2CV-5084-1 52-51G3 52-51H9 MCC 2851 Check Valve Leakage Drain Valve 2CV-5105-1 52-5H1 52-51L3 MCC 2B51 Safety Injection Tank 2T2B Discharge MOV 2CV-5023-1 52-51K1 52-51L4 MCC 2B51 Containment Sump Isolation MOV 2CV-5647-1 ARKANSAS - UNIT 2 3/4 8-15 Amendment No. 35

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED 52-51K3 52-51L5 MCC 2B51 Containment Air Purge Isolation Valve 2CV-8289-1 52-51K4 52-51L6 MCC 2B51 Containment Air Purge Isolation Valve 2CV-8291-1 52-51L1 52-51L7 MCC 2B51 Containment Vent Header Isolation Valve 2CV-2401-1 52-51M1 52-51L8 MCC 2B51 Regenerative Heat Exchanger Inlet Valve 2CV-4821-1 52-51N3 52-51L9 MCC 2B51 Reactor Cavity Cooling Fan Bypass Damper 2HC08243-1 52-53G1 52-53A5 MCC 2B53 Containment Cooling Fan Bypass Damper Motor 2VCDM8203-1 52-53G2 52-53A6 MCC 2B53 Containment Cooling Fan Bypass Damper Motor 2VCDM8209-1 52-53L1 52-53K5 MCC 2B53 Containment Cooling Fan 2VSF1A 52-53L2 52-53K6 MCC 2B53 Containment Cooling Fan 2VSF1B ARKANSAS - UNIT 2 3/4 8-16 Amendment No. 35

~

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM HUMBER NUMBER DEVICES POWERED

$2-54J2 52-54J3 MCC 2B54 Containment Elevator Motor 2MM6 52-54K2 52-54J4 MCC 2854 Containment

{

Building Lighting Panel 27 LA 52-54K3 52-54J8 MCC 2B54 RCP 2P3A Oil Lift Pumps 2P63Al & A2 52-54K4 52-54F3 MCC 2854 RCP 2P32B Oil Lift Pumps 2P63B1 & B2 52-61A4 52-61H3 MCC 2861 Reactor' Cavity Cooling Fan 2VSF34B-2 52-6103 52-61H4 MCC 2B61 Containment Recirculating Fan 2VSF313-2 52-6104 52-61H5 MCC 2861 Containment Recirculating Fan 2VSF31D-2 52-61F2 52-61H6 MCC 2B61 Safety Inject.

Tank 2T2C Discharge MOV 2CV-5043-2 52-61G2 52-61K8 MCC 2B61 Check Valve Leakage Drain Valve 2CV-5106-2 ARKANSAS - UNIT 2 3/4 8-17 Amendment No. 35

TABLE 3.8-1 (Continued)

~

' CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY-BACKUP

~ DEVICE

-DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED 52-61G3 52-61H7 MCC 2B61 Reactor Cooling System Charging Line MOV 2CV-4831-2 52-61G4 --

52-61H8 MCC 2B61 Reactor Cooling System Charging Line MOV 2CV-4827-2 52-61H1 52-61K,3 MCC 2B61 Safety Inj.

Tank 2T2D Dis.

MOV 2CV-5063-2 52-61H2 52-61K7 MCC 2B61 Containment Sump Iso.

MOV 2CV-5E48-2 52-61L3.

52-61K4 MCC 2B61 Letdown Line Stop Valve 2CV-4820-2 9

52-61N2 52-61K6 MCC 2B61 Reactor Cavity Cooling Fan Damper 2HC0 8244-2 52-62E5 52-62C2 MCC 2B62 Shutdown Cooling Return Header Iso. Valve 2CV-5086-2 52-63F2 52-63E1 MCC 2B63 Containment Chilled Water Isol. Valve 2CV-3850-2 ARKANSAS - UNIT 2 3/4 8-18 Amendment No. 35

. TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES z

PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER

-DEVICES POWERED' 52-63G4 52-63E2 MCC 2863 RCP Cooler.

Iso. Valve 2CV-5254-2 52-63L1 52-63J1 MCC 2B63 Containment Cooling Fan 2VSFIC 52-63L2, 52-63J2 MCC 2B63 Containment Cooling Fan 2VSF1D 52-6404 52-64B3 MCC 2B64 Containment Cooling Fan Bypass Damper Motor 20CDM 8216-2 52-64E3 52-64B4 MCC 2B64 Pressurizer Auxiliary Spray MOV 2CV-4824-2 52-64E4 52-64C2 MCC 2B64 Containment Cooling Fan Bypass Damper Motor 20CDM 8222-2 52-64J1 52-64B1 MCC 2B64 RCP 2P32C Oil Lift Pumps 2P63C1 & C2 I

52-64K1 52-64H2 MCC 2B64 RCP 2P32D Oil Lift Pumps 2P63D1 & D2 ARKANSAS - UNIT 2 3/4 8-19 Amendment No. 35 6.

r TABLE 3.8-1 (Centinued)

' CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED D.

480 /277 21P'A-19 52-15C1 Primary - 21PA Space Heater Backup - 2B15 for RCP 2P32A 21PA-25 52-15C1 Primary - 21PA Space Heater Backup - 2B15 for RCP 2P32B 21PA-31' 52-15C1 Primary - 21PA Space Heater Backup - 2B15 for RCP 2P32C 2,1PA-20 52-15C1 Primary - 21PA Space Heater Backup - 2B15 for RCP 2P32D E.

125 VAC 72-0318 72-0320 DC Control Containment Center Bldg 125 VDC 2003 Lighting Panel 22DA 72-26A3 72-26A2 DC MCC-Pressurizer 2026 Vent Valve 2CV-4697-2 72-27A3 72-27A2 DC MCC Pressurizer 2D27 Vent Valve 2CV-4698-1 6 amp fuse 2D21BKR26 DC MCC RCS Sample in 2C116 2021 Line Solenoid Valves 2SV-4632, 39 & 65 F.

240 VAC CEA 1 CB3021 2C72 CEA 1 CB101 CB3022 ARKANSAS - UNIT 2 3/4 8-20 Amendment No. 35

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUEBER DEVICES POWERED CEA 2 CB3001 2C70 CEA 2 CB101 CEA 3 CB3001 2C70 CEA 3 CB102 CEA 4 CB3001 2C70 CEA 4 CB103 CEA 5 CB3001 2C70 CEA 5 CB104 CEA 6 CB3002 2C70 CEA 6 CB101 CEA 7 CB3002 2C70 CEA 7 CB102 CEd'8 CB3002 2C70 CEA 8 CB103 CEA 9 CB3002 2C70 CEA 9 Cet04 CEA 10 CB3002 2C70 CEA 10 CB101 CEA 11 CB3003 2C70 CEA 11 CB102 CEA 12 CB3003 2C70 CEA 12 CB103 ARKANSAS - UNIT 2 3/4 8-21 Amendment No. 35

TABLE 3.8-1 (Continu d)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE-LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED CEA 13 CB3003 2C70 CEA 13 CB104 CEA 14 CB3004 2C70 CEA 14 CB101 CEA 16 CB3004 2C70 CEA 16 CB102 CEA 18 CB3004 2C70 CEA 18 CB103 CEA 20 CB3004 2C70 CEA 20 CB104 CEA 15 CB3005 2C70 CEA 15 CB101 CEA 17 CB3005 2C70 CEA 17 CB102 J

CEA 19 CB3005 2C70 CEA 19 CB103 CEA 21 CB3005 2C70 CEA 21 CB104 CEA 22 CB3006 2C70 CEA 22 CB101 CEA 23 CB3006 2C70 CEA 23 CB102

~

ARKANSAS - UNIT 2 3/4 8-22 Amendment No. 35 l

~

TABLE 3.8-1 (Continuad)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES f

l PRIMARY

. BACKUP DEVICE DEVICE LOCATION OF SYSTEM

. NUMBER NUMBER DEVICES POWERED CB24 CB3006 2C70 CEA 24 CB103~

CEA 25 CB3006-

-2C70 CEA 25 CB104 CEA 26 CB3007 2C70 CEA 26 CB101 CEA 27 CB3007 2C70 CEA 27 CB102 CEA 28 CB3007 2C70 CEA 28 CB103 CEA 29 CB3007 2C70 CEA 29 CB104 CEA 30 CB3008 2C70 CEA 30 CB101 CEA 32 CB3008 2C70 CEA 32 CB102 CEA'34

. CB3008 2C70 CEA 34 CB103 CEA 36 CB3008 2C70 CEA 36 CB104

' CEA 31 CB3009 2C70 CEA 31 CB101 ARKANSAS - UNIT 2 3/4 8-23 Amendment No. 35 L._._.

TABLE 3.8-1 (Continued)

' CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED CEA 33 CB3009 2C70 CEA 33 CBl.02 -

CEA 35 CB3009 2C70 CEA 35 CB103 CEA 37 CB3009 2C70 CEA 37 CB104 CEA 38 CB3010 2C70 CEA 38 CB101 C'EA 40 CB3010 2C70 CEA 40 CB102 CEA 42 CB3010 2C70 CEA 42 CB103 CEA 44 CB3010 2C70 CEA 44

~

CB104 CEA 39 CB3011 2C71 CEA 39 CB101 CEA 41 CB3011 2C71 CEA 41 CB102 CEA 43 CB3011 2C71 CEA 43 CB103 CEA 45 CB3011 2C71 CEA 45 CB104 ARKANSAS - UNIT 2 3/4 8-24 Amendment No. 35 I

o

4 TABLE 3.8-li(Continutd)-

E.-

' CONTAINMENT. PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES.

PRIMARY BACKUP DEVICE

. DEVICE.

LOCATION OF SYSTEM NUMBER

' NUMBER DEVICES POWERED CEA'46-

.CB3012

.2C71 CEA 46 CB1,01 CEA 47 CB3012.,

_2C71 CEA 47-CB102.

.CEA'48 CB3012 2C71.

CEA 48-CB103 CEA 49 CB3012 2C71 CEA 49 CB104 CEA 50 CB3013 2C71 CEA 50 CB101

'CEA 52 CB3013 2C71 CEA 52 CB102 i

CEA 54 CB3013 2C71 CEA 54

CB103 CEA 56 CB3013 2C71 CEA 56 CB104 CEA 51 CB3014 2C71 CEA 51 5,

CB101 CEA 53 CB3014 2C71 CEA 53 CB102 CEA 55 CB3014 2C71 CEA 55 CB103 ARKANSAS - UNIT 2 3/4 8-25 Amendment No. 35

_ - _ _ _ _ - - _ - _ _ _ _ _ _ - _ _.. _ _ _ - _ =.

TABLE 3.8-1 (Continued)--

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE DEVICE LOCATION OF SYSTEM' NUMBER NUMBER DEVICES POWERED bEA57 CB3014 2C71 CEA 57 CB104 CEA 58 CB3015 2C71

.CEA.58 CB101 CEA 59 CB3015 2C71 CEA 59 CB102 CEA 60

CB3015, 2C71 CEA 60 CB103 CEA 61 CB3015 2C71 CEA 61 CB104 CEA 62 CB3016 2C71 CEA 62 CB101 CEA 64 CB3016 2C71 CEA 64 CB102 CEA 66 CB3016 2C71 CEA 66' CB103 CEA 68 CB3016 2C71 CEA 68 CB104 CEA 63 CB3017 2C71 CEA 63 CB101 CEA 65 CB3017 2C71 CEA 65 CB102 ARKANSAS - UNIT 2 3/4 8-26 Amendment No. 35

-TABLE 3.8-1 (Centinutd)

CONTAINMENT PENETRATION CONOUCTOR OVERCURRENT PROTECTIVE DEVICES-PRIMARY BACKUP 2 DEVICE DEVICE LOCATION OF.

LSYSTEM NUMBER NUMBER DEVICES POWERED CEA 67 CB3017 2C71' CEA'67 CB103 CEA 69

'CB3017 2C71-CEA 69 CB104-CEA 70 CB3018 2C71 CEA 70 CB101 CEA 73 CB3018 2C71 CEA 73 CB102 CEA 76 CB3018 2C71 CEA 76 4I' CB103 CEA 79 CB3018 2C71 CEA 79 CB104 CEA 71 CB3019 2C71 CEA 71 CB101 CEA 74 CB3019 2C71 CEA 74 CB102 CEA 77 CB3019 2C71 CEA 77 CB103 CEA 80-CB3019 2C71 CEA 80 CB104

-CEA 72-CB3020 2C71 CEA 72 CB101.

~

ARKANSAS - UNIT 2 3/4 8-27 Amendment No. 35 x

TABLE'3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES PRIMARY BACKUP DEVICE-DEVICE LOCATION OF SYSTEM NUMBER NUMBER DEVICES POWERED

~CEA 75.

CB3020 2C71 CEA 75

.CB102 -

CEA 78 CB3020 2C71 CEA 78 CB103 CEA 81 CB3020 2C71 CEA 81 CB104 ARKANSAS - UNIT 2 3/4 8-28 Amendment No. 35 I

4 TABLE 3.8-1 TABLE NOTATION DELETED S

9 e

0 e

1 ARKANSAS - UNIT 2 3/4 8-32 Amendment No. 35 i

PAGES 3/4 8-29 THROUGH 3/4-8-31 ARE LEFT BLANK INTENTIONALLY

. s. }%,2%.e 9f966YN9N' ARKANSAS - UNIT 2 3/4 8-29 Amendment No. 39 Next page is 3/4 8-32

_-