ML20065Q223

From kanterella
Jump to navigation Jump to search
To Effluent & Waste Disposal Semiannual Rept, Jan-June 1982
ML20065Q223
Person / Time
Site: Crane Constellation icon.png
Issue date: 10/15/1982
From:
GENERAL PUBLIC UTILITIES CORP.
To:
Shared Package
ML20065Q218 List:
References
NUDOCS 8210260505
Download: ML20065Q223 (1)


Text

TABLE 2B y

EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT (1982)

LIQUID EFFLUENTS Continuous Mode Batch Mode Nuclides Released strontium-89 Ci

<5.00 E-8

<5.00 E-8 3.10 E-6 <5.00 E-8 strontium-90' Ci

<5.00 E-8

<5.00 E-8 7.52 E-6 2.09 E-5 cesium-134

, Ci

<5.00 E-7

<5.00 E-7 1.24 E-3 6.32 E-4 cesium-137 Ci

<5.00 E-7

<5.00 E-7 7.23 E-3 3.21 E-3 iodine-131 Ci

<l.00 E-6

<l.00 E-6

<1.00 E-6 <l.00 E-6 cobalt-58 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 cobalt-60 Ci

<5.00 E-7

<5.00 E-7 1.16 E-3 6.31 E-4 iron-59 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 zinc-65 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 manganese-54 Ci

<5.00 E-7

<5.00 E-7 1.21 E-5 <5.00 E-7 chromium-51 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 zirconium-niobium-95 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 molybdenen-99 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 technetium-99m Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 barium-lanthanum-140 Ci cerium-141 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 l

Other (specify)

Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 <5.00 E-7 Iron-55 Ci

<1.00 E-6

<1.00 E-6 3.32 E-4 1.94 E-4 I

Autimony-125 Ci

<5.00 E-7

<5.00 E-7

<5.00 E-7 2.39 E-4 l

Phosphorus-32 Ci

<1.00E-6l<l.00E-6l<1.00E-6 <l.00 E-6 l

t i

Total for period (above)

Ci l

N/A l

N/A 9.98 E-3 4.73 E-3 Eo

> RJ ct>

OO h$

xenon-133 Ci

<1.00E-5!<1.00E-5l<l.00E-4 <1.00 E-4

\\

un xen n-135 Ci l<l.00E-5.!<1.00E-5)<1.00E-4I<l.00E-4 m

l b.

2) yyy Note: All less than (< ) values are in pCi/ml.

20 l

The T.S. LLD of SE-8tci/ml was not achieved during this quarter, due to lack of d

sufficient volume to obtain required LLD.

Backup sample had already been disposed.

._. _