ML20065L825

From kanterella
Jump to navigation Jump to search
Forwards Evaluation of Facility Concerning Applicable Requirements of 10CFR50,App R.Device Locations & Cable Routes Omitted Due to Similarity W/Unit 1
ML20065L825
Person / Time
Site: Mcguire
Issue date: 10/12/1982
From: Tucker H
DUKE POWER CO.
To: Adensam E, Harold Denton
Office of Nuclear Reactor Regulation
References
NUDOCS 8210190740
Download: ML20065L825 (8)


Text

h:

g, DUKE POWER GOMPAhT P.O. Box 33180 CHARLOTTE, N.C. 28242 HALH. TUCKER TELEPHONE rets reassonwy

-(704) 373-4531 wies. man,munumon October ~12, 1982

.'M Mr..llarold R. Denton,. Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Attention:

Ms. E. G. Adensam, Chief

' Licensing Branch No. 4 Re: McGuire Nuclear Station Docket No.-50-370

Dear Mr. Denton:

Attached are five copies of an evaluation of McGuire Unit 2 concerning the applicable requirements of 10 CFR 50, Appendix R.

This supplements the letter of October 21, 1981, by William O. Parker, Jr.

Please note that the device locations and cable routes for Unit 2 are omitted due to their similarity to those provided in the referenced letter for Unit 1.

Very truly yours, h8. Y lg]

Hal B. Tucker REH:j fw Attachment cc: James P. O'Reilly, Regional Administrator P. R. Bemis U. S.-Nuclear Regulatory Commission Senior Resident Inspector Region II McGuire Nuclear Station 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 c-e

'8210190740 821012 PDRADOCK05000g

RESPONSE TO APPENDIX R NcGUIRE NUCLEAR STATION UNIT 2 s

i

.e T.

^.SECTION lll.G '--FIRE PROTECTION OF SAFE SHUTDOWN CAPABILITY As' outlined in our March 1980 submittal of the design description for the McGuire Standby Shutdown Facility, Duke plans to exercise the option of a dedicated shutdown capability referenced in Section lil.G.3 of Appendix R.

The March 1980 submittal did not address the assaciated circuits' referenced in SectionL III.G.3 or separation of cables in _ noninerted containments.

referenced in Section il1.G.2 These.were addressed for Unit 1 in the October 21,:1981. submittal. This submittal addresses these items for' Uni t 2.

The information for. associated circuits,Is identical to that. for Unit 1.

The separation of ~circui'ts for Unit 2 is. reviewed to provide the appropriate

-' valve numbers, etc.

Associated Circuits ~

With regard.to associated circuits as outlined in Section Ill.G.3 of Appendix R, Duke has conducted a review of associated circuits.at McGuire.

The results

'of-this review are provided in the foilowing:

Shutdown capabilities are assured by separating.the shutdown divisions by fire

~ barriers outside' of the Reactor Building.

Circuits which may be associated with the redundant shutdown divisions, have not had the same fire barrier re-quIrements applled.

The subject associated circuits' can be divided into two categories as follows:

1.

Those circuits considercd associated by being electrically connnected to a shutdown d,Ivision's power busses.

2.

Those circuits considered associated by proximity by sharing raceways,

-ets. - The 'first category of associated circuits can be addressed by use of the following " worst case" litustration.

A fire zone was postulated which contained both Division A and Standby Shutdown Facility (SSF) shutdown cables.

By the Duke criteria Division B Shutdown cables

.would not be present in this fire zone.

However, the criteria does not p'rohibit

[

Division B associated cables (which are connected to the Division B power busses) from being present in the subject fire zone.

(See Figure Ifor pictorial represen ta tion).

. For the case of an all consuming fire l'n the fire zone no degradation of the i

Division' B shutdown division would occur since the associated circuit breaker (or fuse) lwill operate to clear. the fault provided this breaker is coordinated with the bus incoming breaker. This breaker 'coordinaton is'provided as part i

of the Duke design, I

~

~

[

The~ second catego'ry of associated circuits are those which-are routed in the s

same raceways as shutdown circui ts but are not supplled power from the shut-

?down busses.

In this instance the goal is to contain or interrupt the fault l

current in the associated circuit to prevent it from propagating to a redundnat shutdown division cable (see Figure 2).

For this case breaker coordination.is j

l notJa concern since the power source to the associated, cable is not from a shut-

[

down division bus.

lr t.

1 -

-i-

1

.e Interruption of the fault current is accomplished by the breaker feeding the associated circuit. The breaker is adequately sized to protect the cable per standard Duke Power design practice.

1 Additionally the cable used by Duke Power is of the armored type. Duke has performed tests that demonstrate a fault within a cable will not propagate into an adjacent cable, even if the breaker feeding the faulted cable falls to trip.

Hence as shown above, the presence of associated circuits in a fire zone with a shutdown division will not propagate the effects of a fire in that zone in such a way as to prevent the other shutdown division from performing its intend-ed function.

With installation of the Standby Shutdown Facility (SSF) there will be two in-dependent areas from which a hot standby condition can be achieved and main-tained. As indicated in the previous submittal, cabling for these two indepen-dent systems are routed through a switchgear room and penetration room to the Reactor Building.

Since. cabling for the SSF is routed directly through a switchgear room and penetration room to the Reactor Building and does not Interface with any other plant areas, Duke Power-Company requests an exemption to Section Ill.G.3 of the rule which requires that "a fixed fire suppression system...be Installed in the... zone under consideration." The zone under consideration, the Control Room, is separated by physical separation and 3-hour fire barriers from the 4

penetration room, where redundant SSF cabling enters Auxiliary Building and routes to Reactor Building. Fire detection devices are presently Installed in the Control Room. A fixed fire suppression system in the control room is not deemed necessary '(or desirable) in light of the existing commitment to install the SSF.

A review of routings for circuits inside the Reactor Building necessary for hot standby has been conducted utilizing the criteria in Section 111 G of Appendix R.

Due to design considerations, the Reactor Building is divided into the annulus and inner containment.

For analysis purposes the annulus.is being considered part of the containment.

The criteria for review of the cable routings was to provide separation of cables and equipment of redundant shutdown functions by a horizontal distance of more than 20 feet with no intervening combustibles.

Since the PVC Jacket has been stripped frem the arn,ored cable located in the Inner containment, the intervening area between cables and equipment of redundant shutdown functions is considered to be devoid of combustibles (note that there are a iimited number of cases where the function of the dircuits-required Jacketed s

cables).

1 in the annulus area the PVC Jacket has been lef t on the armored cable. This situation will be addressed by upgrading the Installed manually actuated sprinkler system to a preaction sprinkler system. The installed detectors will j

be left in place.

'wi

Several cable routes and devices are eliminated from this review based on the similarity of device location and cable routes noted in the review on Unit 1.

These results, noted in our October 21, 1981 submittal, as they apply to Uni t 2 are categorized in the following six groups:

Group I contains S$F devices which h' ave alternates outside the containment.

(Reactor Building).

l. The steam generator secondary side isolation valves 2BB5A 2BB6A, 2BB7A and 2BB8A have as their alternates 2BBIB, 2BB28, 2BB3B, and 2BB48, respectively.
2. The nuclear sampling system SSF isolation valves 2NH25A and 2NH22A have as their alternate 2NM26B. The other nuclear sampling sysetm SSF isolation valve's 2NM3A and 2NM6A have as their al ternate 2NH7B.
3. The chemical volume control system (CVCS)/ reactor coolant system (RCS)

SSF isolation valve 2NVIA has as an alternate 2NV78.

Group 2 contains valves which isolate as an SSF function because of the low flow capabilities of the standby makeup pump.

Because a fire inside containment will not effect equipment outside, a much larger flow is available from the centrifugal charging pumps and the reciprocating charging pumps. Therefore, these PORV isolation functions are not necessary.

1. The SSF power operated relief valves 2NC328, 2NC34A, and 2NC36B have as their alternate valves 2NC318, 2NC33A, and 2NC35B respectively located inside containment.
2. The reactor coolant system letdown SSF valves 2NC272A and 2NC273A have no al ternate valves.
3. The reactor coolant system SSF isolation valves 2NC274B and 2NC2758 have no al terna te valves.
4. The normal reactor coolant pump seal water return SSF isolation valve 2NV94A does not have an al ternate valve.
5. The chemical volume control system / reactor coolant system ;

' solation valves, 2NV24B and 2NV25B can act as alternates to each other and 2NV26B can serve as a second alternate, but the cables associated with these valves are located in the same area.

l l

6. The standby makeup pump test SSF valve 2NV1012C does not have an alternate.
7. The standby makeup pump SSF isolation vlave 2NV1013C does not have an alternate.

f Group 3 contains the pressurizer spray SSF isolation v'alves 2NC27 and 2NC29 l

which have no alternate devices.

If these valves cannot.be closed due to a l

fire, the corresponding reactor coolant pump can be tripped.

Group 4 contains the residual heat removal system SSF isolation valve 2ND2A which has as an alternate valve 2NDIB.

Both val'ves are located inside contain-ment, therefore, will not be available with a postulated fire. The existing control' cable for 2ND2A will be separated into two control cables to ensure no internal shorts would open the valve. _-

~~

~. -

1 1

' Group 5 contains the cables for ter erature moni toring for the SSF by means of five incore thermocouples. An alternate for the incore thermocouples is a hot-leg, cold-leg RTD pair from one reactor coolant loop.

Ilowever, the cable routes of the RTD coincide with the incore thermocouples. The incore thermocouples will be separated by a, minimum of twenty feet.

Group 6 contains the SSF power cable to the pressurizer heater.

If a fire renders this equipment inoperable, the necessary shutdown function can be performed without the use of the pressurizer heater.

Other cables that were examined were' either associated ~with a device inside in.;sr containment or an alternate device located in the annulus.

For devices located in inner containment the cables are routed through the annulus. As was previously stated, the criteria for review of the cable routings was to provide separation of cables and equipment of redundant shutdown functions by a horizontal distance of more than 20 feet with no inte'rvening combustibles.

In the annulus area the PVC Jacket remains on the cable, therefore, the existing manually actuated sprinkler system will be upgraded to a pre-action sprinkler system.

W'e conclude that this meets the Intent of Appendix R Section Ill.G.2.

o l

4-w_.

r..%..

B PlVl510d Od5 l)

)

I) o B SWdfp0WL LDAP 7

-B ASSOC CABLE.

PlVl5100 A4 RAY l

dok SAFEfY 1' RAY l

1 FAdLT t

SSF FRAY f

'.\\rieraAnnica.

l

\\

'..FlQdRE 1

..=.u

f +

,' ~

d0d SWdfPOWd Bd5 l)

)

B, ASS,06 CABLE

.PlVISI0d B (RAY

~

i

).

1

(

\\

\\B PlVl51'Od CABLE

'FAlll.f Md51 dOf PROPA6AfE BEfLIEEd 14ESE GABLES.

PlVISI0lj A FRAY l

d0d SAFEfY FRAY Y

FAdLf/'

SSrfRAY L

\\flRE'FARRIEP;.

~

s 4

7 O

.e

..y--

~

.