5 Duke Powen CoMewy a*

P.O. ISOX 33180 CH ARLOTTE. N.C. 28242 Wt IAM A.HALLER MA%AGER MTLt. AM TLCHNICAL ELHYK18 1704:373skau November 26, 1990 Division of Environmental Management Water Quality Section Attention:

Central Files P.O. Box 27687 Raleigh, NC 27611 Subjects Duke Power Company NPDES Monitoring Report for McGuire Nuclear Station - NC0024392 Files HC-702.25 Dear Sir In accordance with Part II, C(2) of the above referenced NPDES permit, duplicate copies of the monthly monitoring report for october, 1990 are i

enclosed.

McGuire -Nuclear Station's outfall 003- (Domestic Wastewater Treatment Facility) exceeded the permit value for focal coliform on October 16, 1990.

The upper limit for fecal coliform at outfall 003 is 400.0/100 ml.

The value obtained on October 16, 1990 was 920/100 ml.

Because this outfall does not discharge directly into waters of the state, but discharges into another NPDES permitted system, no input to the environment resulted.

Duke Power is evaluating the conditions surrounding the fecal coliform excursion.

Duke Power has increased chlorination to alleviate the problem.

One explanation of the fecal coliform excursion has been related to increased solide carryover from the lagoon.

These solids exert an additional chlorine demand, while acting as a barrier betweer. the bacteria and the chlorine thereby affecting disinfection.

Because of

this, additional short range plans to rectify this condition includes (1) The installation of new aerators, which will permit shorter aerator run times allowing the solide more time to settle, and less carryover and (2) The installation of a sand filter for solide removal.

The new aerators are expected to be on-site by the end of January, 1991 with installation shortly thereafter.

The request for Authorization to Construct for the addition of a Dynasand Filter has been submitted to Ms. Carolyn McCaskill, State Engineering Review Group Permits and Engineering, NCDEHNR on November 16, 1990.

In this request for Authorization to Construct, Duke Power has indicated its desire to start installation of this sand filter February 1,

[

l 1991.

901207027/ WIIM osooga j

h

c 1

[;r O

,q.

L' o

Division of.. Environmental Ha'nagement

' Water Quality ~Section.

November 26, 1990 Page 2:

3 Please direct any correspondence 'or questions concerning the McGuire Nuclear' Station. NPDES Program to M.C.

Griggs (704) 373-7080, Nuclear

-Environmental compliance.

Very truly yours,

,3..

W.A. Haller,: Manager._

T

. Nuclear Technical Services

=MTK/djei1237.mtk-

. Attachments.

.:,i ce s l.

lIRGAmeusenticent. cot * '

i

)

t-

{,'

. I.i e

.;)

\\

i i

i.

1.

t'-

==

t i.

ill

.s 6

be w/ Attachments:

R. P. Michael R. W.

Eaker D. W.

Phillips M.

E. Bridges J. S. Carter M. C. Griggs M.E. Kowalewski Staff (Route) e l

l