Text
xc: NUC PR ARMS, 1520 CST 2-C T. G. Campbell, 1760 CST 2-C
- 0. L. Paulk, NRC TELECOPY TO NRC T. L. Chinn, BFN Feb. 9, 1983 C. W. Crawford, 670 CST 2-C A. W. Crevasse, 401 UBB-C G. S. Harrison, Plt Supt Office U. S. Nuclear Regulatory Commission L. M. Mills, 400 CST 2-0 Region II Shift Engineer 101 Marietta Street, NW F. A. Szczepanski, 417 UBB-C Suite 3100 W. C. Thomison, BFN Atlanta, Georgia 30303 D. L. Williams, W10B85C-K BFRO-50-260-8302 Reported under Technical Specification 6.7.2.a.2 Date of Occurrence: 2/8/83 Time of Occurrence: 1400 Unit 2 Technical. Specification Involved: 3 2.B Conditions Prior Aq_Qc_currence E
Unit 1 - Maintenanca outage f
'O Unit 2 - Refuel outage Unit 3 - 3283 MWt
.c Identification and Descrintion of Occarrence During performance of Surveillance Instruction (SI) 4.2.B-7 (Instrumentation That Senses Reactor Low Pressure) prassure switches (PS-682 96 Switch No. 1, PS-3-74A. Switch No. 1, PS-3-74B Switch No. 1 and 2 ) were found out of technical specification limits by 1 7.15.
PS-68-96, PS-3-74A and 74B, Switch No. 1, actuates the recirculation discharge valve, and PS 74B Switch No. 2 is a CSS and LPCI admicsion valves permissive.
Anoarent Cause of Occurrence The pressure switches setpoints had drifted.
Other Related Events BFR0 50-259/81038, 81064, 77002, 82006, 82038 260/81059, 78018, 81033, 82003, 82013 296/82021, 80018, 79010, 79028 Corrective Action Taken or Planned The switches were recalibrated, functionally tested, and returned to service. The switches will be replaced with an analog transmitter and trip unit system (Design Change Request (DCR) 1398) at a later date.
pp1CIAL cod G.
ones Pw Plant Superintendent B owns Ferry Nuclear Plant
] g' A 6LJ 8302170048 830209 PDR ADOCK 05000260 S