Monthly Operating Rept for Aug 1982
ML20064N301
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 09/30/1982
From: Jackie Cook
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20064N293 List:
References
NUDOCS 8209080302
Download: ML20064N301 (7)


Text

.

OPERATING DATA REPORT DOCKET NO. J0-331 DATE _J. Rt_.).982 SO Cook C051PLETED BY TELEPilONE 131313.42-3840 OPFRAllNG STATUS Note 5 FitzPatrick

1. Unit Name:

820801 - 820831

2. Reporting Period:

2436

3. Licensed Thermal Power (51Wt):

883

4. Nameplate Rating (Gross 51We):

821

5. Dnign Electrical Rating (Net 51We):

830

6. Sf aximum Dependable Capacity (Gross SlWe):

810

7. Sf aximum Dependable Capacity (Net 51We).
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report,Gise Reasons:

NONE

9. Power Lesel To Which Restricted,If Any (Net 51We).
10. Reasons For Restrictions,if Any:

This 51onth Yr.-t o-Da t e Cumulatise 744 5831 6210E__

i1. Ilours In Reporting Period 744 4162.4.

43713.6

12. Number Of flonrs Reactor Was Critical 0

0 0

13. Reactor Resene Shutdown flours 744 4059.6 42503.2
14. Ilours Generator On-Line 0

0 0

15. Unit Resene Shutdown llours 1791480 9321336 87722650
16. Gross Thermal Energv Generated (5f WII) 590440 3165440 2992605.0_
17. Gross Electrical Energy Generated (51Wil, 573130 3071200 28975930
18. Net Electrical Energy Generated (51Wil) 100%

69. 6*L 68J%

19. Unit Senice Factor 100%

69.6%

68.3%

20. Unit Asailabihty Factor 95 2 _

65.0%

61J%

I Unit Capacits Factor IUsing $1DC Net) 93.8%_

64.2%

56.7%

Unit Capacity Facior IUsing DER Net!

0%

3.3%

15.8%

23. Unit Forced Outage Rate
1 Shutdowns Scheduled Oser Next 6 51onths (Type. Date.and Duration of Each Maintenance outa_ge scheduled for 29 Octoher_1982 for n period _of 10 days.
25. If Shut Down At End Of Report Period. Estimated Date of Startup:
26. Omts in Test Status IPrior io Commercial Operation):

l' orecast Achiesed INillA L CRITICAllrY INITI A L ELECT RICITY CON 151ERCI A L OPER ATION 8209080302 820903 PDR ADOCK 05000333 R

pon

AVER AGE DAILY UNIT POWER LEVEL DOCKETf0.

50-333 UNIT JAFNPP DATE September 1982 J. Cook CON!Pl.ETED BY TELEPilONE (315)342-3840 AUGUST, 1982 MONm DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POW.5R L EVEL (MWe Net)

(MWe Net) 774 17 775 775 2

773 18 3

776 19 775 4

575 20 774 755 21 777 5

6 772 780 22 773 782 7

23 774 s

24 784 775 9

25 782 773 785 10 26 ji 775 27 783 774 12 28 785 13 774 707 29 774 787 34 3o 775 786 15 3

775 16

SUMMARY

Unit operated at near 1007. rated thermal powe.r for this reporting period. On August 4, 1982 power was i

reduced due to unidentified leakage in the drywell.

D

50-333 UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT N AME JAFNPP DATE Sept. 1982 REPORT MONTil Aunust COMPLETED BY J_

Cook TELEPilONE (315T 167_1940 r.

C P8 EU h'"E g4 Cause & Currectise N...

Dat e E.

k$

? g ec Event g

gg Action to y

32

.c CO i E7) j Report a mV Prevent Recurrence g

l C

\\

C l

NONE I

2 3

4 F: Forced Reason:

Method:

Exhibit G Instructio,*s S: Sched uled A Equipment Failure (Explain) 1 -Manual for Preparation of Dati B Maintenance of Test 2 Manual Scram.

Entry Sheets for Licensee C Refueling 3 Automatic Scram.

Event Repori (LER) File (NUREG-D Regulatory Restriction 4 Other (Explain) 0161)

E Operator Training & License Examination F-Administ rative 5

G Operationat Error (Explain)

Exlubit I Same Source 11 Othe r ( E xplain) i I

r POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE

AUGUST, 1982 The unit operated at near full thermal power during this reporting period.

Power was reduced on 820804 due to unidentified leakage in the drywell.

At the end of the reporting period the unit is operating at approximately 786 Mwe.

I f

,...n,---.~,-a,,.v.-.

-.-----,g a-,,,

,---n-

,n,,,.

,-,,--a,--w--

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

AUGUST 1982 REO S DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T

7/14 01-107 11336 OPS Leaking joints Torqued joints 9

Off-gas drying tower 7/10 03 20492 OPS Dried packing 'u' cup Replaced valve 3

HCU-46-19 on III valve 7/14 03 18407 OPS Dried packing 'u' cup Replaced valve 1

HCU-42-47 on III valve 7/14 03 14345 OPS Dried packing 'u' cup Replaced valve 1

HCU-30-43

.,on III valve 7/14 03 21864 OPS Dried packing 'u' cup Replaced value 1

HCU-22-07 on III valve 7/13 03 20488 OPS Air leaks due to loose Torqued cover plates 8

HCU-42-15 cover plate on 117 and 118 valves 7/15 03 19649 OPS Directional' control Replaced directional control 3

HCU-02-23 valve stuck open valve 123 7/13 27 11223 N/A N/A Installed hanger for conduit 6

Mod fl-81-19 1CC098AA per ECR 81-19-00c 7/15 27 14304 SURVEILLANCE Drifting module RP-2C Replaced per J.Cronk Tech.

54 RM-104A Services 7/21 66 18525 OPS Fitting leak Re-swept elbow 4

SOV-100A

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

AUGUST 1982 0"

I DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T

0 ENT 7/9 70 21990 OPS Low oil pressure due Overhauled compressor 160 RWC-2B to worn internals 7/9 71 14839 N/A Preventative Cleaned cells, cleaned inter-cell 126 LPIC maintenance connectors, added water Battery i

8/4 08 16399 VISUAL Aged hoses cracked Replaced hoses 6

Refuel Bridge 7/27 24 16417 OPS Bent linkage Replaced link arms 12 EOD-2 7/28 24 16226 OPS Broken latch bolt Replaced latch bolt 2

EOD-2 7/28 24 17713 OPS Electric interlock Replaced electric door strike, 18 EOD-1, 2 inoperable due to door latch release coil, switches misuse S15, 16, 17 & 18 i

8/5 71 14846 PREVENTATIVE Preventative Cleaned battery 30 SB-1A, B MAINTENANCE maintenance

..-- ~ _--._. -. _ _ _-_ _..

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

f I&C August 1982 E

ES

^

E DATE SYS TEM HOW DETECTED CO NENT MA FU C ON MA C1 O

j 20875 Out of Out of Adjusted core j 8/17 07 D-Tip JIC adj ustment adjustment top and bottom 10 r

limits Defective X-Y plotter Replaced i

20876 switch and not switch and 8/20 07 A-Tip JIC relay operational relay 25 i

Loss of 20879 continuity Replaced light

! 8/4 11 ll-14A OPS Age of bulb alarm bulb 10 valve did not Pressure 20992 allow flow to switch not Repaired valve 20 8/25 13 LS'77B JIC switch working i

20394 Defective Can't calibrate Replaced electronic

/ erratic defective 8/31 17 Spare RM I&C components 62 comoonents 20823 Inspected for 8/30 17 Misc RMS I&C N/A N/A loose relays 3

20946 Relay partly Hi-Hi trip Inserted relay i8/11 17 RIS-456B JIC ut of would not and calibrated 1

socket function i

21883 Flat spot on Indicating up C*fd 8/9 23 LR=202B OPS drive wheel scale a

t calibrated 18 12931 Out of Switch doesn't Adjusted for 8/18 76 76C-ll OPS adj ustment control pressureproper operatior.

60 4

20925 Pressure Not starting at Calibrated ggfgatorreads proper pressure 8/24 93 Cl-Air Com OPS indicator 34 4

.-