ML20064J623

From kanterella
Jump to navigation Jump to search

Tech Spec Change Request 102 to License DPR-72,revising Tech Specs to Allow 72 H to Determine Whether Actual Station Battery Degradation Had Taken Place or If Indication Is Result of Outside Factors Influencing Test
ML20064J623
Person / Time
Site: Crystal River 
Issue date: 01/12/1983
From: Westafer G
FLORIDA POWER CORP.
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20064J624 List:
References
3F-0983-07, 3F-983-7, TAC-49498, NUDOCS 8301180147
Download: ML20064J623 (5)


Text

. _

l,y??;%

6%
  • {iC ( h;%

\\

)

bfya<j> @w es.

r

Cyr, Q y,e s

M Power January 12,1983 3F-0183-07 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555

Subject:

Crystal River Unit 3 Docket No. 50-302 Operating License No. DPR-72 Technical Specification Change Request No.102 Station Battery Electrolyte Specific Gravity

Dear Mr. Denton:

I Florida Power Corporation hereby submits three (3) original and forty (40) copies of Technical Specification Change Request No.102, requesting amendment to Appendix A of Operating License No. DPR-72. The Crystal River Unit 3 Technical Specifications presently

(

require that the plant be shut down within two (2) hours if the specific gravity of the electrolyte on a station battery has decreased by more than 0.01 since the previous t

l quarterly test. Florida Power believes that factors such as temperature and electrolyte l

stratification can influence the test results enough to show wi apparent decrease of 0.01 l

when no true battery degradation has taken place. The proposed amendment would allow 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> to determine whether actual battery degradation had taken place or if the indication is the result of outside factors influencing the test.

Proposed replacement pages to the Technical Specifications and a copy of the Certificate of Service to the Chief Executive Of fice of Citrus County are enclosed.

l Florida Power has determined that the requested action is a Class til amendment per 10 CFR 170.22 in that it involves a single safety issue. Accordingly, a check in the amount l

of four thousand dollars ($4,000)is enclosed.

I' od L

Sincerely,

/bk

/

O.@

G. R. Westafer t]OO Manager Nuclear Licensing and Fuel Management EFW/mm 8301180147 830112 Enclosure FDR ADOCK 05000302 P

PDR General Office 3201 in.rty tourtn street sourn. P O Box 14042. st Petersburg, Fbrda 33733 e 813-86G-5151

STATE OF FLORIDA COUNTY OF PINELLAS i

G. R. Westafer states that he is the Manager, Nuclear Licensing and Fuel Management, of Florida Power Corporation; that he is authorized i

on the part of said company to sign and file with the Nuclear Replatory Commission the information attached hereto; and that all such statements made and matters set forth therein are true and correct to the best of his knowledge, information, and belief.

G. R. Westafer /

l Subscribed and sworn to before me, a Notary Public in and for the State and County above named, this 12th day of January,1983.

b 7)LA. h__

f.D1

~

Notary Public Notary Public, State of Florida at Large, My Commission Expires: November 19, 1986 i

ITOTAlt? MTBLIC STATE Of FLORIDA MY ECMMISSION EOIRIS NOV 17 iV85 BONDED THRU CENf t At INWR ANCE UND i

UNITED STATE 5 OF AMERICA NUCLEAR REGULATORY COMMISSION IN THE MATTER OF

)

)

DOCKET NO. 50-302 FLORIDA POWER CORPORATION )

CERTIFICATE OF SERVICE G. R. Westafer deposes and says that the following has been served on the Chief Executive of Citrus County, Florida, by deposit in the United States mail, addressed as follows:

Chairman, Board of County Commissioners of Citrus County Citrus County Courthouse Inverness, FL 32650 One (1) copy of Technical Specification Change Request Nc. 102 requestirg amendment to Appendix A of Operating License No. DPR-72.

FLORIDA POWER CORPORATION Y

G. R. Westafer Manager Nuclear Licensing and Fuel Management SWORN TO AND SUBSCRIBED BEFORE ME THIS 12th DAY OF 3ANUARY 1983.

4Y)d/

Notary Public Notary Public, State of Florida at Large My Commission Expires: November 19,1936 (NOTARIAL SEAL) l NOTAt? PUBl!C STATE OF FLOR!D T MY COMMIS$lON EXPKH NOy 37 m RONDr0 THRU GENEUL INS'JUNCE UNO

O fECHNICAL SPECIFICATION CHANGE REOUEST NO.102 Replace pages 3/4 8-10 and B 3/4 8-1 of Appendix A with proposed pages 3/4 8-10 and B 3/4 3-1 enclosed.

PROPOSED CHANGE 1)

Revise ACTION "b" of Specification 3.8.2.3 to read as follows:

b.

With one 250/125 volt D.C. battery and/or a charger inoperable for reasons other than a decrease in battery cell electrolyte specific gravity greater than 0.01 from the value observed in the previous quarterly test, restore........

2)

Add a new ACTION 'c" to Specification 3.8.2.3 which reads as follows:

c.

With one or more battery cells which show a decrease in electrolyte specific gravity greater than 0.01 from the value observed in the previous quarterly test, within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, perform an Engineering Evaluation to determine the reason (s) for the decrease, and perform appropriate corrective measures, if any, to restore the inoperable battery (ies) to OPERABLE status within the next 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

3)

Add a new section to the second paragraph of page B 3/4 8-1 which reads as follows:

The operating restrictions placed upon the batteries also recognize that basing the judgement of a cell's condition upon the measurement of electrolyte specific gravity may not be entirely appropriate. The specification allows time to determine whether true degradation or an artifact of measurement technique is the cause of a decrease in specific gravity and allows appropriate corrective measures to be taken following this determination.

REASON FOR PROPOSED CHANGE The p esent Technical Specifications require that the plant be shut down if an inoperable station battery cannot be restored to OPERABLE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. One of the SURVEILLANCE REQUIREMENTS used to demonstrate operability of the batteries requires that the specific gravity of an individual cell not be lower than 0.01 below the value observed in the previous quarterly test.

Specific gravity of the electrolyte in a battery cell is influenced by many factors (e.g.,

state-of-charge, stratification, temperature) and its determination is subject to these I

influences as well as measurement errors. While a true decrease in specific gravity of a cell's electrolyte is cause for conan, an observed decrease may be due to one or more of the influencing factors above. The proposed revision to the ACTION of Specificatic.n 3.8.2.3 will allow time to evaluate the cause of a decrease in specific gravity and help avoid needless plant shutdown.

l t

t SAFETY EVALUATION OF PROPOSED CHANGE Plant safety will not be compromised. This change allows time to evaluate whether an observed decrease in specific gravity of battery electrolyte is actually degradation of the battery or an artifact of other influencing factors. The extra time introduced by this change is insignificant since the requirement that specific gravity is maintained above the manufacturers recommended minimum value remains unchanged; this assures that the batteries will be capable of performing as required. A change in the e!ectrolyte specific gravity is considered to be an indication that there may be battery degradation taking piace, but is not cause for immediate plant shutdown in itself.

r

-4