6 Jersey Central P;wer & Light Company

[sC3Q.9l'$[-[r d j r

Mad. son Av nue at Punch Bowl Road Momstown, New Jersey 07960

~- =

(201)455-8200 December 19, 1978 Director Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555

^

s'

\\

Dear Sir:

('

{

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 Systematic Evaluation Program - Environmental Qualification of Electrical Equipment Your letter of September 6,1978, requested that we (a) complete as much of your qualification table as'possible, (b) identify appropriate re-ferences, and (c) confirm the accuracy and completeness of the table.

We have reviewed the table as requested and have also participated in the review con-ducted by the SEP Owners' Group.

The results of our review are enclosed.

We have completed as much of the table as possible including information developed after our original sub-mittals.

To our knowledge the attached table is accurate and as complete as possible.

(~

Very truly yours, j

uhA..a Ivan R. Fi ock Jr.

Vice Presi ent cp Enclosure 781227oW f Jersey Central Power & Light Company is a Member of the General Pubhc Utihties System 9

6 OYSTER CREEK SEP Submittal

References:

1.

Feb. 24, 1978 letter, I. R. Finfrock to Director, NRR 2.

May 8, 1978 Letter, I. R. Finfrock to Director, NRR 3.

March 15, 1978 letter, I. R. Finfrock to Director, NRR f

3 l

l l

l

BEACTOR: Oyster Creek SYSTEFIATIC EVAL.l!ATION PROGRAFI SEP SUBFilTTA l.

TIFIE ENVIRONMENT QUAL.

Nh!D-UIPMENT TYPE REFERENCE LOC PARAMETER SPEC.

QUAL.

Solcnoid Valves (MSIV )

I 1 min.

8,20,27,31,( 32, 23 1-3/all

_ TEMP ( F1 281 304 e of c 20 3CO Model Nos.

Ril ( ". )

100 100 c of c 20 PR(PSIA) 53 80 e of c 20 IIT 8302826 RU 8302C26 RU TIO Yes Evaluation 27 yes RAD. (RADS) 1.54x106 4x105 Vender Data / Eval.

8,27 SUB.

no Solenoid Valve (Rx sa np) 29,3U This valve installed 1-8/u11 TEMP ("F) 281 340 e of c 29 during '78 outage SCO model no.

PR. (PSTAT 53 77 c of c 29 Ril

(".)

100 8320A187fi CllliM.

yes Yes c of c 29 100 c of c 29

~ RAD. (RADS) 1.54x106 1,5x108 e of c 29 SUB.

no l_ _1__ min 4,10(T.R.),

11,(T.R.) 15, 17,20

~

Mntnr opcIntn<l valve 1-1 /7,8,11, &

17 to TEMP. ( F) 281 329 test /similar 10,11 imitorque models 1-2/3,4 cont.

PR.(PSIA) 53 Tid 5

' test /similar 10,11

~~ --

3MB-000 duty.

Ril ('.)

100 100 test /similar 10,11

}

!MB-0.1,2 CilEM.

yes -

~EAD- (RADS) 1.54xt66

~~-'"

-~

SUB.

no Elcetrical Penetrati ms I

cont 20,25,26,34 TEMP ( F) 281

'~ 352 Test 34 L;E type NS02 iot listed pn (psia) 53 139 Test 34 i

GE type NS03 all

( *. )

100 100 Test 34 lE type NSO4 Cill31 yes RAD (RADS) 1.54x106 SilB no l

Electrical Connectors 1-9 all I

cont ITT Cannon Model Nos.

_L.'20,24 fTR) 43106E-36A-46P-F80(plug)

TEMP f F) 281 32U Test 24 PR(PSIA) 53 62 Test 24 43100R-36A-465-F80(Rec opt)

Ril (*c.)

100 100 Test 24 106RX-36A-10 -A95(plug)

CllEM yes Yes Test 24 RAD. (RADS) 1.54x106 1.73x106 Test 24

$3100RX-36A-105-A95(Rezept) 7UB no l

REACTOR: Oyster Creek SYSTEFL\\ TIC EVAI.IJATION PROGRAM SEP SUBMITTA L TIME ENVIRONMENT QUAL.

"hgh"-

FIET110D REFERENCE

[UIPMENT TYPE REFERENCE LOC PARAMETER SPEC.

QIJAL.

i. Terninal Block 1-4/all I

Cont.

3,5,6,9,12,13 All safety related TEMP (* F) 281 340 Similarity 12 terminal blocks are pro-3E Model EB PR(PSIA) 53 118 Similarity 12 tected by gasketed Ril ( ". )

100 100 Similarity Iz enclosures with drain hol'e.

Clltibi ves R AD. (RADS) 1.54x106 Evaluation 33

  • Well above expected LOCA SUB.

no

7. Junction Boxes 1-4/all I
Cont,

~

lladdam Neck Pliint TEMP ("F) 231 Conducted testing of boxes 191. (PSIA) 53 with terminal strips.

' Ril (t) 70 Oyster Creek has steel or CllEM.

yes galvanized iron boxes whici

~ RAD. (RADS) 1.54x10 can be expected to perform 6

SUB.

no as in lladdam Neck tests.

1. Cable 1-7/all

._I_ Cont.

7,12(T.R.),

16,20,24 (T. R. )

TEMP. ( F) 281 320 Test 24 PR.(PSIA) 53 -

62 Test 24

~ ~ ~ ~ ~ ~

Ril ("6) 100 11)F Test 24 CIIFFl.

yes

~~Yes

~ RAD. (RADS) 1.54x106 ~1,'73xid6

~

Test 24 Test 24 SUB.

no

).

Electromatic Relif talve 1-6/al l I Cont 14(T.R.)l6, 19,21 GE Model 213CA12 TEMP ( F) 281 300 Test 14 PR (PSIA) 53 77 Test 14

~

gg

("r,)

100 100 Test 14 I

CllEM ves RAD (RADS) 1.54x106 l

sun no l0. Splices

_L _ Cont

_2_4 (T. RI.

Two splicss_were_discneret None TEMP (*F) 231 320 Test 24 by inspection as a result l Raycem PR(PSIA) 53 62 Test 24 of I.E. Cir. 78-08.

j Ril (%)

100 100 Test 24 Replaced with Raycem Yes Test 24 Sp11ces.

CilEM yes I

IIAD. (RADS) 1.54x106

).73x10 Test 24 6

i.,

7UB no g

1 1

OYSTER CREEK a

y DOCUMENTATION

REFERENCES:

1.

Dec. 15, 1977 letter, NRC to JCP6L 2.

Feb. 2, 1978 letter, F. E. Funk to P. H. Henrikson 3.

Feb. 2, 1978 letter, G. E. to D. Ross 4.

Feb. 2, 1978 letter, P. H. Henrikson to J. S. Gay 5.

Feb. 10, 1978 letter, D. A. Ross to B. H. Grier 6.

Feb. 13, 1978 letter, Burns 6 Roe to R. Pinelli 7.

Feb. 16, 1978 letter, P. H. Henrikson to J. S. Gay I

8.

Feb. 24, 1978 letter, T. R. Hays, Jr. to P. Procacci 9.

Burns 6 Roe spec. S-2299-51 10.

FIRL F-C2232-1 11.

FIRL F-C3441 12.

GE Test Report" Terminal Block for LOCA Test for Electrical Penetration Assemblies" 13.

G.E. Qual. Test Summary #994-75-001 14.

Results of Dresser Test, June 11,-1968 15.

Amd. 7 6 8 to D2 6 3 FSAR 16.

Amd. 13 to Quad. Cities FSAR 17.

Amd 15 to Quad Cities FSAR 18.

Amd 11 to Oyster Creek FSAR j

19.

Amd. 20 to Oyster Creek FSAR 20.

Amd. 62 to Oyster Creek FSAR

21. " Supplementary Information to Special Report of Incident of 6/5/70" July 27,1970 22.

JCPSL Response to I.E. Bul. 77-05 and 7705A, Dec. 1, 1977.

23.

Engineering Request EA-3 24.

March 15, 1978 letter, I. R. Finfrock to Director, NRR,

?

Electrical Connector Test Report.

25.

Amendment 15 to Oyster Creek FSAR j

26.

Burns 6 Roe Spec 5-2299-52 27.

Engineering Evaluation No. 255-78-1, Jersey Central Power 6 Light, "0yster Creek Nuclear Generating Station MSIV Solenoid

(

Valves".

28.

GE Qualification Test Summary 994-75-011 29.

JCPSL Purchase Order 21141 dated 11/9/78 and associated certificate of compliance, l

30.

ASCO catalog No. NP-1"3 and 4 way solenoid valves'!.

31.

Amend. 48 to Oyster Creek FDSAR 32.

Purchase Order 96473 dated 1/2/76 and associated c of c.

33.

February 24, 1978 letter, W. Popow to D. A. Ross 34.

Parts Test Data Sheets attached to e of c dated February 24, 1967.

1 h

a e

b O

.