4 Northem States Power Company 414 Nicollet Mall Minneapohs, Minnesota 55401-1927 Telephone (612) 330-5500 February 28, 1994 10CFR 20.407 and Technical Specification Sections 6.7.A.1.a, 6.7.A.1.b and 6.7.A.1.c US Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket Hon. 50-282 License Nos. DPR-42 50-306 DPR-60 Annual Report of Occupational Radiation Exposure and Safety Relief Valve Challences - January 1 throuah December 31, 1993 i

Attached are three reports for 1993:

1)

Annual Report of Occupational Exposure (Required by Technical Specification 6.7.A.1.a and 10 CFR Part 20, Section 20.407) 2)

Annual Report of Safety and Relief Valve Failures and Challenges (Required by Technical Specification 6.7.A.l.b) 3)

Annual Primary Coolant Iodine Spike Report (Required by Technical Specification 6.7.A.1.c)

This letter contains no new NRC commitments, nor does it modify any prior commitments.

'O1]Il

~ ' ' ' '

9403100003 931231 W

PDR ADOCK 05000282 M

R PDR 9

4 1

Northern States Power Company USNRC February 28, 1994 Page 2

)

Please contact Jack Leveille (612-388-1121, Ext. 4662) if you require additional information concerning these reports.

I

/

pff

/

lRoerOAnderson Director Licensing and Management Issues cc: Director, Office of Nuclear Regulatory Research Regional Administrator-III, NRC NRR Project Manager, NRC Resident Inspector, NRC l

State of Minnesota, Attn Kris Sanda Attachments: 1-Occupational Exposure Report (4 pages) 2-Report of Safety / Relief Valve Failures and Challenges (1 page) 3-Primary Coolant Spike Report (1 page)

I l

I l

amust.emp

1 ATTACHMENT 1 PRAIRI2 ISLAND NUCLEAR GENERATING PLANT ANNUAL REPORT OF OCCUPATIONAL RADIATION EXPOSURE 1993 i

l l

I i

1 i

i 1

4 ammlexp

1 l

NORTHERN STATES POWER COMPANY Prairie Island Nuclear Generating Plant 1717 Wakonade Drive East Welch, MN 55089 License No. DPR-42/DPR-60 & SNM-2506 (Unit 1, Unit 2 & ISFSI)

Number of Personnel and Man-Rem by Work and Job Function 1993 Number of Persons > 0.100 Total Man-Rem Work / Job Function Station Utility Contract Station Utility Contract Reactor Ops /Surv Operators 0

0 0

1.003 0.0 0.0 Maintenance 1

0 0

0.760 0.430 0.026 Supv & Engr 0

1 0

0.358 0.421 0.220 Health Physics 4

0 0

1.664 0.006 0.141 Instr & Control 0

0 0

'0.256 0.0 0.0 Security 0

0 0

0.0 0.0 0.0 Routine Maintenance l

Operators 0

0 0

0.073 0.0 0.0 l

Maintenance 7

16 1

2.287 4.721 0.136

}

Supv & Engr 2

1 0

0.835 0.154 0.018 Health Physics 0

0 0

0.188 0.0 0.020 Instr & Control 2

0 0

0.808 0.0 0.008 Security 0

0 0

0.0 0.0 0.0 l

l Special Maintenance Operators 2

0 0

2.844 0.0 0.0 Maintenance 18 68 9

4.234 21.523 2.438 Supv & Engr 6

3 13 1.899 1.198 4.869 I

Health Physics 5

2 11 1.884 0.424 2.706 l

Instr & Control 4

0 0

1.161 0.0 0.008 j

Security 0

0 0

0.0 0.0 0.0 Page 1 of 2 l

DPR-42/DPR-60/SNM-2506 Number of Persons > 0.100 Total Man-Rem Work / Job Function Station Utility Contract Station Utility Contract Waste Processing Operators 0

0 0

0.050 0.0 0.0 Maintenance 2

0 0

1.066 0.196 0.029 Supv & Engr 0

0 0

0.015 0.037 0.0 Health Physics 3

0 0

1.161 0.0 0.048 Instr & Control 0

0 0

0.002 0.0 0.0 Security 0

0 0

0.0 0.0 0.0 Refueling Operators 0

0 0

0.550 0.0 0.0 Maintenance 21 14 0

5.410 4.890 0.024 Supv & Engr 0

0 0

0.394 0.081 0.0 Health Physics 1

0 0

0.492 0.019 0.154 Instr & Control 0

0 0

0.0 0.0 0.103 Security 0

0 0

0.0 0.0 0.0 Inservice Inspection Operators 0

0 0

0.0 0.0 0.0 Maintenance 0

38 20 0.638 9.049 10.615 Supv & Engr 0

0 12 0.167 0.095 4.684 Health Physics 2

0 4

0.527 0.001 1.073 Instr & Control 0

0 19 0.0 0.0 4.910 Security 0

0 0

0.0 0.0 0.0 Unassigned 0.0 0.0 0.182 Sub totals Operators 2

0 0

4.520 0.0 0.0 Maintenance 49 136 30 14.395 40.712 13.268 Supv & Engr 8

5 25 3.668 1.986 9.791 Health Physics 15 5

15 5.916 0.450 4.142 Instr & Control 0

0 19 2.227 0.0 5.029 Security 0

0 0

0.0 0.0 0.0 Grand Total 80 143 89 30.726 43.148 32.412 Total Dose 106.286 Page 2 of 2

l l

NORTHERN STATES POWER COMPANY i

l Prairie Island Nuclear Generating Plant I

1717 Wakonade Drive East Welch, MN 55089 License No. DPR-42/DPR-60/SNM-2506 1

(Unit 1, Unit 2 & ISFSI)

ANNUAL 10CFR PART 20.407 REPORTING 1993 DOES RANGE (REM)

NUMBER OF INDIVIDUALS IN EACH RANGE N o Me asu rable........................................

687 Measurable exposure less than 0.10.

215 0.1 t o 0. 2 5..........................................

154

0. 2 5 t o 0. 5 0...........................................

117 0.50 to 0.75.............

40 0.7 5 t o 1.00................

6

1. 00 t o 2. 0 0........................................

0

2. 0 0 t o 3. 0 0..........................................

O t

l

3. 0 0 t o 4. 0 0.........................................

0 l

4. 0 0 t o 5. 0 0........................................

0 l

5. 0 0 t o 6. 0 0.........................................

0 l

6. 0 0 t o 7. 0 0......................................

0 1

l 7.00 t0 8.00 O

j

8. 0 0 t o 9. 0 0...........................................

0 1

9.0010 10.0......

O i

10.0 t 0 11.0.............................

0 1 1. 0 t o 1 2. 0.........................................

O Greater than 12.0.........

O Total number of individuals reported 1219 1

Total Dose.........

106.286 i

..... -- i

ATTACHMENT 2 l

PRAIRIE ISLAND NUCLEAR GENERATING PLANT ANNUAL REPORT OF SAFETY / RELIEF VALVE FAILURES AND CHALLENGES 1993 This report is made in accordance with NUREG-0737, Item II.K.3.3 and Prairie Island Technical Specification 6.7.A.l.b and covers the period from January 1 through December 31, 1993.

Unit 1 -

No failures or challenges Unit 2 -

Failures None.

Challences 12/19/93 Pressurizer Power Operated Relief Valves lifted automatically when the turbine generator control system caused power swings (generator megawatts suddenly went from 486 MW to 515 MW followed by a l

sudden drop of 100 megawatts). This resulted in a reactor coolant system pressure increase above the setpoints for the relief valves. The valves closed with no problems upon the subsequent decrease in reactor coolant system pressure.

l

\\

t l

smaast exp i

l l

l ATTACHMENT 3 PRAIRIE ISLAND NUCLEAR GENERATING PLANT ANNUAL REPORT OF OCCUPATIONAL RADIATION EXPOSURE 1993 This report is made in accordance with Prairie Island Technical Specification 6.7.A.1.c and covers the period of January 1, 1993 through December 31, 1993.

Prairie Island Technical Specification 3.1.D.1 was not exceeded during 1991.

I 1

l I

l l

l l

l r

l I

amumlexp

- -.