_.

. (;

s

,a h

lowa Electric Light and Ibwer Company t-c August 27, 1982 DAEC 595

?

1-PRINCIPAL STAFF 0,L[

l l

Mr. James Keppler, pg Office of Inspection and Enforcement o/PA

$f---

[f U. S. Nuclear Regulatory Commissi5n A/RA D "'""

Region III j

St o fE i 799 Roosevelt Road kN^0

  1. es Glen Ellyn, Illinois 60137 RL FILE L

, Ag at j

SUBJECT:

Semiannual Effluent Release Report

/

for the Duane Arnold Energy Center, Unit N0'. 1 1

FILE:

A-118e I

Dear Mr. Keppler:

Please find enclosed a copy of the Semiannual Regort for the Duane Arnold Energy Center, Unit No.1, for the period January 1,1982 through June 30,1982. This report satisfies the requirements for the Semiannual Effluent Release Report as stated in the Radiological Technical Specifications, ( Appendix'B to the Operating License DPR-49).

y

' daniel L. Mineck Plant Superintendent-Nuclear Duane Arnold Energy Center DLM/KDY/lh

/,

Encl o's'ure

"/

/

cc: L. Root w/o

/,-

I R. McGaughy w/o e

U

_,/

p 9209000643 820827 PDR ADOCK 05000331

/

R PDR Ikume Anwhl Energv Center

  • RO. Ilok 351
  • Cnlar ifapkis, Inn 52406
  • 319/851-5611 j: '

l 4

l O

f f

t i

i

?

I SEMI-ANNUAL REPORT t

i i

Radioactive Effluent Releases

[

O i

January 1,1982 through June 30, 1982 l

i h

l

[

t i

P i

t

+

h t

i q.

i 6

6 h

O i

^

V

, ;' %3 7f l

RADIATION EFFLUENT REPORT e

January 1, 1982 through June 30, 1982 O:.

ITEM UNITS IST QUARTER 1982 2ND QUARTER 1982 A. Gaseous Effluents

1. Gross Radioactivity curies 2.25 El 2.07 El
2. Maximum I hour Release Rate pCi/sec 2.57 El 2.37 E1 i
3. Nuclides Released Xe-138 curies 4.74 E0 1.02 El Kr-87 curies 7.40 E-2 5.00 E-3 Kr-88 curies 2.01 E-1 3.40 E-1 Kr-85m curies 3.34 E-1 2.51 E-1 Xe-135 curies 8.20 EO 5.26 EO Xe-133 curies 4.89 E0 2.22 E0 Kr-85(cal.)

curies

<2.4 E-2

<1.2 E-2 Xe-135m curies 3.78 E0 2.08 E0 Ar-41 curies 1.01 E-1 7.10 E-2 N-13 curies 1.59 E-1 3.17 E-1 4.' Tritium Released curies 1.48 EO 4.00 E-1 O

tj

5. Percent of ETS 0.074 0.031 (l'6% of Limit) 1

.m.-

.e.

_ _ _ - - ~.....,,.., _... -

.._.___m_.____

.~

RADIATION EFFLUENT REPORT January 1, 1982 through Juns 30, 1982 t

c ITEM UNITS IST QUARTER 1982 2ND QUARTER 1982 B. Iodine Releases

1. Total I-131 Released curies 3.46 E-3 1.35 E-3

(

2. Total I-133 Released curies 4.87 E-3 1.58 E-3
3. Total I-135 Released curies 5.64 E-3 1.13 E-3
4. Percent ETS Limit (I-131) Note 2 0.95 %

0.26 %

C. Particulate Releases

1. Total Released curies 2.19 E-3 9.24 E-4 l
2. Gross Alpha Released curies 8.27 E-6 2.76 E-5
3. Nuclides Released Ba-140 curies 1.58 E-4 4.78 E-5 Cs-138 curies 9.22 E-4 5.98 E-4 Co-6 curies 9.65 E-5 2.72 E-5 Mn-54 curigs 2.00 E-5 1.86 E-6 Cs-137 curies 3.50 E-6 None Rb-89 curies 4.87 E-6 None ps,

%)

K-40 curies 2.91 E-5 None

RADIATION EFFLUENT REPORT January 1,1982 through June 30, 1982 y;...

~

ITEM UNITS IST QUARTER 1982 2ND QUARTER 1982 Co-58 curies 2.41 E-6 None Cr-51 curies None 1.79 E-5 Bi-214 curies None 6.24 E-5 Hb-95 curies None 8.40 E-7 Sr-89 curies 6.53 E-5 1.65 E-5 4.54 E-6 2.71 E-6 Sr-90 curies

=

Unidentified curies 8.8 E-4 1.49 E-4

4. Percent ETS Limit (Part.) Note 3 1.52 %

.62 %.

5. Percent ETS Limit (I-131 a Part.) Note 4 2.50 %

0.89 %

6 0

i NOTE 1 QSE Q-

+

5 0.21 (1.4 X 10 )(MPC)

% ETS X 100 f

=

0.16 l

i NOTE 2 f

QS Q

+

t 1.3 X 10-6 1.8 X 10 -7

%ETS(I-131)

X 100

=

0.08

[

i NOTE 3 Qs Q

O

+

1.3 X 10-6 1.8 X 10 -7 ETS(PART)

X 100

=

0.08 NOTE 4 l

Qs Q

+

i 1.3 X 10-6 1.8 X 10 -7 ETS(PaI-131)

=

X 100 0.08 I

i i

{

O i

i

i i

l l

l l

l l

i f

l r

l l

LIQUID EFFLUENTS P

l i

I l

i No Liquid Releases I

January 1, 1982 through June 30, 1982 l

i

[

O l

[

i f

l l

i

?

I k

l s

5 O

I e

m mm emp*

p y _w e pe_

.,,_m,

,n.

SOLID RADI0 ACTIVE WASTE January 1, 1982 through June 30, 1982

?

I Date Volume (ft )

Activity (C1)

Type of Waste j

3 m.

t 1/8/82 85 25.3 Solidified Resin 1/12/82 85 13.5 Solidified Resin 4

j 1/14/82 85 33.75 Solidified Resin 1/19/82 180

.3528 Trash 1/20/82 85 6.75 Solidified Resin f

1/27/82 85 6.0 Solidified Resin i

1/27/82 562.5

.2709 Trash

[

1/29/82 85 12.0 Solidified Resin

(

~

2/2/82 85 30.0 Solidified Resin 2/4/82 85 23.9 Solidified Resin 2/8/82 85 15.7 Solidified Resin 2/17/82 85 9.9 Solidified Resin 2/19/82 85 57.4 Solidified Resin 2/22/82 85 50.8 Solidified Resin 2/24/82 472.5

.2418 Trash O

3.88 Seitdified aesi-3/1/82 8s 3/3/82 85 5.174 Solidified Resin 3/5/82 85 4.39 Solidified Resin 3/8/82 85 2.576 Solidified Resin 3/10/82 85 5.815 Solidified Resin 3/12/82 85 9.454 Solidified Resin l

3/15/82 85 6.061 Solidified Resin 3/17/82 85 4.921 Solidified Resin 3/19/82 85 2.210 Solidified Resin 3/24/82 85 2.711 Solidified Resin 3/26/82 85 2.743 Solidified Resin 3/29/82 165

.1014 Trash

.3/31/82 85 24.1 Solidified Resin 4/7/82 85 4.487 Solidified Resin 4/12/82 85 3.792 Solidified Resin 4/15/82.

85 8.165 Solidified Resin j

4/19/82 85 6.824 Solidified Resin f

4/21/82 85 46.94 Solidified Resin f

l

SOLIO RADI0 ACTIVE WASTE

~

January 1,1982 through June 30, 1982 O

o te veie e<<t )

Activits (ci)

Trae er w ste 3

4/23/82' 85 16.88 Solidified Resin 4/27/82 442.5

.2688 Trash 4/30/82 85 21.96 Solidified Resin 5/3/82 85 23.0 Solidified Resin 5/5/82 85 20.5 Solidified Resin 5/7/82 85 18.27 Solidified Resin 5/12/82 85 2.972 Solidified Resin 5/18/82 35 25.0 Solidified Resin 5/20/82 85 3.69 Solidified Resin 5/24/82 85 47.22 Solidified Resin 5/25/82 532.5

.2904 Trash 5/26/82 85 2.487 Solidified Resin 6/3/82 85 9.570 Solidified Resin 6/7/82 85 2.63 Solidified Resin 6/11/82 85 3.808 Solidified Resin 6/14/82 85 6.451 Solidified Resin 6/16/82 85 3.278 Solidified Resin 6/18/82 85 16.2 Solidified Resin 6/23/82 247.5

.215 Trash 6/25/82 85 4.63 Solidified Resin 12.9 Solidified Resin 6/28/82 85 All shipments sent to Barnwell, South Carolina.

3 1.7411 curies Compacted Trash 2602.5 F Solidified Resin 4080.0 F3 674.471 curies TOTAL 6682.5 F3 676.2121 curies O

-