Attachment to TXX-94041 Page 1 of 13 COMANCHE PEAK STEAM ELECTRIC STATION, UNIT 1 NRC MONTHLY OPERATING REPORT DOCKET NO.:
50-445 UNIT:
CPSES 1 DATE:
02/14/1994 i
COMPLETED BY:
Janet Hughes TELEPHONE:
817-897 5331 OPERATING STATUS l
1.
REPORTING PERIOD: JANUARY 1994 GROSS HOURS IN REPORTING PERIOD: 744 2.
CURRENTLY AUTHORIZED POWER LEVEL (MWt): 3411 MAX. DEPEND. CAPACITY (MWe Net): 1150
- DESIGN ELECTRICAL RATING (MWe-Net): 1150 3.
POWER LEVEL TO WHICH RESTRICTED (IF ANY) (MWe-Net):
NONE 4.
REASON FOR RESTRICTION (IF ANY):
THIS MONTH YR TO DATE CUMULATIVE 5.
NUMBER OF HOURS REACTOR WAS CRITICAL 744 744 23,283 6.
REACTOR RESERVE SHUTDOWN HOURS O
O 2,354 l
7.
HOURS GENERATOR ON LINE 744 744 22.837 8.
UNIT RESERVE SHUTDOWN HOURS O
O O
9.
GROSS lHERMAL ENERGY GENERATED (MWH) 2,536,090 2,536,090 72,285,895
- 10. GROSS ELECTRICAL ENERGY GENERATED (MWH) 854,089 854,089 23,989,346
- 11. NET ELECTRICAL ENERGY GENE' ATED (MWH) 821,112 821.112 22,816,963
- 12. REACTOR SERVICE FACTOR 100.0 100.0 76.5
- 13. REACTOR AVAILABILITY FACTOR 100.0 100.0 84.3
- 14. UNIT SERVICE FACTOR 100.0 100.0 75.1
- 15. UNIT AVAILABILITY FACTOR 100.0 100.0 75.1
- 16. UNIT CAPACITY FACTOR (USING MDC) 96.0 96.0 65.2
- 17. UNIT CAPACITY FACTOR (USING DESIGN MWe) 96.0 96.0 65.2
- 18. UNIT FORCED OUTAGE RATE 0.0 0.0 5.9
- 19. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) :
- 20. IF SHUTDOWN AT END OF REPORTING PERIOD, ESliMATED DATE OF STARTUP:
- 21. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
ACHIEVED COMMERCIAL OPERATION 900813 j
ESTIMATED 9402240142 940131 DR ADDCK 05000445 PDR
.j
. -. -.. -..~.-..
...~. - -
. ~. -
l
.4
?.
l 4
i f
i l
Attachment to TXX-94041 i
Page 2 of 13 l
AVERAGE DAILY UNIT POWER LEVEL I
i DOCKET NO.:
50-445 UNIT:
CPSES 1 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331-MONTH : JANUARY 1994 4
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) l
]
1 1105 17 1099 4
2 1105 18 1102 i
3 1105 19 1105 c
4 1104 20 1105 i
1 5
1104 21 1107 I
I i
i 1
6 1104 22 1105 1
7 1104 23 1105 4
8 1103 24 1106 l
i j
9 1103 25 1105 10 1104 26 1105 i
11 1105 27 1106 12 1111 28 1106 l
13 1098 29 1102 14 1105 30 1105 I
15 1076 31 1105 t
a 16 1110 i
h 8
u, -
e.--e.~
-.,r we,
,.e.-w-,---.r-we
--w~---
- .--------------=~-r
- - ~ ~ - * - - - - -
'=
l
~. _.
k e
?
l i
Attachment to TXX-94041 Page 3 of 13
SUMMARY
OF OPERATING EXPERIENCE FOR THE MONTH DOCKET NO.:
50-445 UNIT:
CPSES 1 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331 MONTH : JANUARY 1994 DAY TIME REMARK / MODE 01/01 0000 Unit started month in MODE 1.
1 1
01/08 2245 Protection inverter IV1PC1 failed, instrument bus re-energized from alternate power.
01/09 1808 inverter IV1PC1 returned to OPERABLE status following replacement of f ailed i
resistor.
l 01/31 2400 Unit ended month in MODE 1.
i
Attachment to TXX-94041 Page 4 of 13 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.:
50-445 UNIT:
CPSES 1 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331 REPORT MONTH : JANUARY 1994 METHOD OF TYPE SHUTTING DOWN F: FORCED DURATION THE REACTOR OR NO DATE S: SCHEDULED (HOURS)
REASON REDUCING POWER CORRECTIVE ACTIONS / COMMENTS l
1 a
- 1) REASON
- 2) METHOD A: EQUIPMENT FAILURE (EXPLAIN)
E: OPERATOR TRAINING AND LICENSE EXAMINATION 1: MANUAL B: MAINT OR TEST F: ADMINISTRATIVE 2: MANUAL SCRAM C: REFUELING.
G: OPERATIONAL ERROR (EXPLAIN) 3: AUTOMATIC SCRAM D: REGULATORY RESTRICTION H: OTHER (EXPLAIN) 4: OTHER (EXPLAIN)
I
l Attachment to TXX.94041
, Page 5 of 13 COMANCHE PEAK STEAM ELECTRIC STATION, UNIT 7
{
NRC MONTHLY OPERATING REPORT DOCKET NO.:
50-446 I
I UNIT:
CPSES 2 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897 5331
- i OPERATING STATUS
)
1.
REPORTING PERIOD: JANUARY 1994 GROSS HOURS IN REPORTING PERIOD: 744 l
2.
CURRENTLY AUTHORIZED POWER LEVEL (MWt): 3411 MAX. DEPEND. CAPACITY (MWe-Net): 1150
- DEStGN ELECTRICAL RATING (MWe-Net): 1150 3.
POWER LEVEL TO WHICH RESTRICTED (IF ANY) (MWe-Net):
NONE 4.
REASON FOR RESTRICTION (IF ANY):
THIS MONTH YR TO DATE CUMULATIVE 5.
NUMBER OF HOURS REACTOR WAS CRITICAL 744 744 4,033 6.
REACTOR RESERVE SHUTDOWN HOURS 0
0 327 7.
HOURS GENERATOR ON LINE 744 744 3,989 8.
UNIT RESERVE SHUTDOWN HOURS 0
0 0
9.
GROSS THERMAL ENERGY GENERATED (MWH) 2,471,383 2,471,383 13.089,341
- 10. GROSS ELECTRICAL ENERGY GENERATED (MWH) 840,410 840,410 4,427,637
- 11. NET ELECTRICAL ENERGY GENERATED (MWH) 808,488 808,488 4,240,294
- 12. REACTOR SERVICE FACTOR 100.0 100.0 92.5 4
- 13. REACTOR AVAILABILITY FACTOR 100.0 100.0 100.0
- 14. UNIT SERVICE FACTOR 100.0 100.0 91.5
- 15. UNIT AVAILABILITY FACTOR 100.0 100.0 91.5
- 16. UNIT CAPACITY FACTOR (USING MDC) 94.5 94.5 84.6
- 17. UNIT CAPACITY FACTOR (USING DESIGN MWe) 94.5 94.5 84.6
- 18. UNIT FORCED OUTAGE RATE 0.0 0.0 1.4
- 19. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH) :
- 20. IF SHUTDOWN AT END OF REPORTING PERIOD, ESTIMATED DATE OF STARTUP:
- 21. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
ACHIEVED COMMERCIA'. O?ERATION 930803 2
1 i
ESTIMATED I
or
Attachment to TXX-94041
. Page 6 of 13 AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.:
50-446 UNIT.
CPSES 2 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331 MONTH : JANUARY 1994 1
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
(MWe-Net) l 1
1120 17 1118 2
1120 18 1097 j
3 1118 19 1092 I
4 1118 20 1095 5
1121 21 1070 I
6 1119 22 1096 7
1119 23 1100 8
1120 24 1100 9
1121 25 1101 10 1120 26 1099 11 1119 27 1100 12 1121 28 1095 1
I 13 1120 29 873 14 1120 30 867 15 1121 31 870 16 1118
1 i
i Attachment to TXX 94041 J
, Page 7 of 13
SUMMARY
OF OPERATING EXPERIENCE FOR THE MONTH DOCKET NO.:
50-446 UNIT:
CPSES 2 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331 1
MONTH : JANUARY 1994 DAY TIME REMARK / MODE 01/01 0000 Unit started month in MODE 1.
01/06 The electric governor, governor booster servo motor, motor operated potentiometer and normal voltage regulator for Unit 2 Emergency Diesel Generator (EDG) 01 was replaced. The diesel generator had experienced f ailures on two occasions. See Special Reports 2-SR-93-004 and 2-SR-94-001.
01/19 1500 Due to intermittent problems associated with Turbine Spt > s input to electro-hydraulic control (EHC) causing minor turbine load swirgs, reduced power to 98% with EHC at 98% and mechanical hydrauhc control (MHC) at 100%.' With MHC at 100%, an upward load swing weutd be hmited by the MHC control system and mainta:ned at 100%
01/29 0600 Commenced operation at 80% power for fuel cycle optimization purposes.
01/31 2400 Unit ended month in MODE 1.
1 1
l w
-+v4 Y'we s-
Attachment to TXX-94041 Pege 8 of 13 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.:
50-446 UNIT:
CPSES 2 DATE:
02/14/1994 COMPLETED BY:
Janet Hughes TELEPHONE:
817-897-5331 REPORT MONTH : JANUARY 1994 METHOD OF TYPE SHUTTING DOWN F: FORCED DURATION THE REACTOR OR NO DATE S: SCHEDULED (HOURS)
REASON REDUCING POWER CORRECTIVE ACTIONS / COMMENTS 1
940129 S
0.00 H
4 Fuel cycle optimization purposes.
- 1) REASON 2)- METHOD A: EQUlPMENT FAILURE (EXPLAIN)
E. OPERATOR TRAINING AND LICENSE EXAMINATION 1: MANUAL B: MAINT OR TEST F: ADMINISTRATIVE 2: MANUAL SCRAM C: REFUELING.
G: ' OPERATIONAL ERROR iEXPLAIN) 3: AUTOMATIC SCRAM D: REGULATORY RESTRICTION H: OTHER (EXPLAIN) 4: OTHER (EXPLAIN)