_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _.
SEAB N S W H W IPUBLIC SERVICE Engineedng Office:
Companyof New Hampshsre 1671 Worcester Rood Framingham, Mossochusetts 01701 (617) - 872-8100 July 28, 1982 SBN-302 T.F. B 7.1.2 United States Nuclear Regulatory Commission Washington, D. C. 20555 Attention:
Mr. Frank J. Miraglia, Chief Licensing Branch No. 3 Division of Licensing
References:
(a) Construction Permit CPPP-135 and CFPR-136, Docket Nos. 50-443 and 50-444 (b) FSNH Letter, dated April 1, 1982, "Seabrook Station Fire Protection Program," J. DeVincentis to F. J. Maraglia
Subject:
Fire Protection System l
Dear Sir:
1 i
Af ter discussion with members of your staf f, we wish to make the following l
change in Exhibit 2, "Seabrook Station Fire Protection Program Evaluation and Comparison to ETP APCSB 9.5-1, Appendix A, Fevision 1, April,1982."
Exhibit 2 currently indicates that in the Fuel Oil Storage Tank Areas under the Diesel Generator Euilding, we plan to install a single automatic deluge system in each area, complete with ionization and thermal detection.
We plan to revise that inste11ation. We will install two redundant autcmatic deluge systems in each Fuel Oil Storage Tank Area. The detection will consist of a combination of smoke, heat, and flame detectors. A sketch of the piping layout for the two areas is attached here as are the revised pages of Exhibit 2.
We trust that the proposed change to the system will adequately respond to the concerns expressed by the Staf f during their review of the Seabrook Station fire protection systems.
Very truly yours, YllM J. DeVincentis Project Manager k