November 1, 1978 Docket No. 50-267 Public Service Company of Colorado
. ATTN: Mr. C. K. Millen Senior Vice President of Operations P. O. Box 840 Denver, Colorado 80201 Gentlemen:
By letter P-78107, dated July 11, 1978, the Public Service Company of g
Colorado described a proposal for resolution of a requirement that calibration and/or testing of instruments and controls of the Helium Circulator Auxiliary System be fully implemented as one of several con-ditions which must be met prior to exceeding the currently authorized 70% rated power level.
Since receipt of the July 11 letter, the material contained therein has been reviewed, records of calibrations / functional tests have been examined and a number of discussions relative to this matter have been held with members of your staff. Based on this effort we have concluded that calibration and/or testing for all Class A, B and C instruments, as defined in your letter, has been completed with the exception of those instruments which can only be calibrated and/or tested during a refueling outage and those instruments which must' be modified to provide calibration and/or test-ing capability.
It is our understanding that t;hese instruments, identified below, are to be calibrated and/or functionally tested prior to resuming operation following the first refueling outage to occur... currently t
scheduled for early January, 1979.
INSTRUMENTS REQUIRING INSTRUMENTS REQUIRING MODIFICATION REFUELING SHUTDOWN PS 21358
)
PC 21105 LIS 21474
)
XEP 21105 LIS 21476
)
XPS 21105 LIS 21477
)
)
PS 21120 LS 21130 XSL 21185 CERTIFIED MAIL - RETURN RECEIPT REQUESTED
'I B i l 13 000\\
i
~
- v. o,,.
o Public Service Company of Colorado November 1, 1978 INSTRUMENTS REQUIRING REFUELING SH'JTDOWN XSL 21187 XPS 21189 LS 21385 LSH 21451 LSH 21452 LSH 21453 LS 21502 Based on the above, and upon our understanding that you will maintain the I-following four step program, we have no further questions regarding this matter.
1.
Calibration of all Class A and B instruments on an annual basis.
2.
Calibration of all Class C instruments as required by the Technical Specifications.
l 3.
Continuation of calibration of Class D instruments as required for local indications and diagnostic use.
4.
Functional testing of Class A and B instruments as outlined on the attachment to letter P-78107.
Class C instruments are functionally tested as required by Technical Specifications and is included in the surveillance procedures.
If your understanding of this matter is inconsistent with the above, please notify us within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of receipt of this letter.