Proposed Tech Specs Re Emergency Diesel Generator Starting Air Sys
ML20059M429
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/20/1990
From:
ENTERGY OPERATIONS, INC.
To:
Shared Package
ML20059M428 List:
References
NUDOCS 9010040172
Download: ML20059M429 (2)


Text

,

4 P

PROPOSED TECHNICAL SPECIFICATION CHANGES ANO-1 i

u i

i 9010040172 900920 fDR ADOCK 05000313 PDC

~~

A e.

Diesel fuel from the emergency storage tank shall be sampled and found to be within acceptable limits specified

-in Table 1 of ASTM D975-68 when checked for viscosity, water, and sediment.

5.

Once every 31 days the pressure in the required starting air receiver tanks shall be verified to be 2 175 psig.

Once every 18 months, the capacity of each diesel oil transfer pump shall be verified to be at least 10 gpm.

4.6.2 Station Batteries and Switchyard Batteries 1.

The voltage, temperature and specific gravity of;a pilot cell in each bank and the overall battery voltage of each bank shall be measured and recorded daily.

2.

Measurements shall be made quarterly of ' voltage of each cell to the nearest 0.01 volt, of the specific gravity of each cell, _

and of the temperature of every fifth cell in each bank.

The level of the electrolyta shall be checked and adjusted as required. All data, including the amount of water added to any cell, shall be recorded.

3.

Once every 18 months, a performance discharge test shall be conducted in accordance with the manufacturer's1 instructions, the purpose of determining battery capacity.

4.

Any battery charger which has not been loaded while connected to its 125V d-c distribution system for at:1 east 30 minutes during every quarter shall be tested and' loaded while; connected to its bus for 30 minutes.

The third battery charger, which is capable of being connected to_either of the two 125V d-c distribution systems, shall be loaded while-connected to each bus for at least 30 minutes every quarter.

4.6.3 Emargency Lighting The correct functioning of the emergency lighting system shall be verified once every 18 months.

L l

l Amendment No. JE, 2E 100a 1

.