e VIHOINIA EI,1 C*THIC AND POWER COMI%NY H iciiu on n, VIHOINI A 23261-January 14, 1994 j
Nuclear Regulatory Commission Serial No.94-015 Attention: Document Control Desk NL&P/MAE: R1 Washington, D.C. 20555 Docket Nos. 50-339 License Nos. NPF-7 Gentlemen:
I VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT 2 MINIMUM BOLTING REQUIREMENT VOLUME CONTROL TANK MANWAY -
In our letter dated January 7,1994 (Serial No.94-008), we committed to performing a calculation to determine the minimum bolting required to maintain the structuralintegrity of the volume control tank manway. Attached is that calculation, CE-1126 Revision 0.
The manway cover is a blind flange consisting of 16 bolts (1-1/8~ diameter A-193 Grade B7). The calculation determined that based on a design pressure of 75 psig, the equivalent of one bolt, same diameter and material, is adequate to withstand the design i
pressure load. We have determined that these 16 bolts would be structurally adequate if they were 1/4~ diameter of the same material. Additionally, in the calculation we-determined that assuming all the top half of the flange bolts are non-functional, the eight bolts on the bottom half of the flange with cross sectional area equal to 3/4" diameter A-193 Grade B7 bolts would be adequate for structural integrity.
If you have any further questions, please contact us.
Very truly yours,
/)'I/ ht w)J M. L. Bowling, Manager Nuclear Licensing and Programs r
Attachment cc:
United States Nuclear Regulatory Commission t
Region 11 Suite 2900 101 Marietta Street, N. W.
-l Atlanta, Georgia 30323 i
Mr. R. D. McWhorter NRC Senior Resident inspector North Anna Power Station 94o124o283 94o114 s
g01 PDR ADOCK 05000339 Y
P PDR i,
Ifg
'