ML20059G035

From kanterella
Jump to navigation Jump to search
Advises That Util Intends to Modify Tech Specs Re Emergency Diesel Generator Surveillance Testing.Util Will Continue to Follow Testing Prescribed by Plant Tech Specs Until Such Time as Approval Received
ML20059G035
Person / Time
Site: Yankee Rowe
Issue date: 09/06/1990
From: Papanic G
YANKEE ATOMIC ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
BYR-90-120, NUDOCS 9009120099
Download: ML20059G035 (2)


Text

y i

1 4

' 9' p

[ YANKEE ATOMICELECTRIC COMPANY "CW".s*s];*;*l" 580 Main Street, Bolton, Massafhusetts 01740-1398 v.-

September 6, 1990 BYR 90-120 s

United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20553 j

Reference:

(a)

License No. DPR-3 (Docket.No. 50.29)

Subject Emergency Diesel Generator Surveillance Testing

Dear Sir:

'l The purpose of this letter is'to inform you of our intent and commitment

i to modify the Technical Specifications for the Yankee Nuclear Power Station" (YNPS). As you may be aware, Yankee -is' currently. replacitig thetthree j

Emergency Diesel Generators with' units having approximately 50% greater.

standby capability. This modification-is being performed 1under.the provisions of.'10CFR50.59 and the Safety Evaluation for the change has concluded that'the q

provision of the present Technical Specifications are satisfied following this.

j change.

Yankee's position, however, is that there.may be a benefit associated.

with acknowledging the increased capacity by modifying theLTechnical' Specifications and performing routine.~ surveillance testing.to prove this capability. This position.has been discussed with the Resident inspe: tor at-1 YNPS and it has been agreed to outline the changes anticipated in advanceLof j

the formal Proposed Change process.

!l The changes would be made to Specification 3/4 8.1 in accordance with' guidance provided by Westinghouse Standard Techn{r'el Spec { fication.

Revision 4, November 1981 as follows:

1.

Specification 4.8.1.1.2.a.4 would be modifled to, test the.three Emergency -

't Diesel Generators quarterly on a staggered basis at' greater'than 450:kW.

(continuous rating) for a period of one hour.

2.

Specification 4.8.1.1.2.d.4 would be modified to test.the-three' Emergency Diesel' Generators during each refueling' outage interval for a; period of '

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at loads of at least 495 kW (110% of continuous rating) for~the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />;and at least 450 kW for the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br />.

l 1

\\.

O'0?3 9009.120099 900906

~

PDR ADOCK 05000029 OO/

P PDC

/

2

4 3-

,.s',

i United States Nuclear Regulatory Commission:

-September 6,;1990 Bocument Control Desk Page-2a BYR 90-120 i

These changes are curre*.itly being prepared-and, reviewed for submittal under the provisions of 100FR50.90. Until such time as these changes receive final Commission review and approval, Yankee will continue to follow the testing prescribed by: Plant Technical Specifications. Additionally, we.will-develop procedures and begin the new' quarterly' surveillance program outlined; i

in.1 above.. Testing'in accordance with 2 above isibeing performed as part of-i the preoperational test program for the new Emergency Diesel Generator sets' l

and will also be performed at'the next scheduled refueling outage-(currently.

March - April'1992).

l We trust that tiils clarifics our intentions with'regards= to revisions -to our Emergency. Diesel Generator testing programs.

Should you'have any.

questions, please do not hesitate to contact us.

Very truly yours,

.i YANKEE ATOMIC ELECTRIC COMPANY' s

Georg apanic, Jr.

Senior Licensing Engineer Yankee Project I

CP/gjt/WPP72/94

~

l cet USNRC Region I USNRC Resident Inspector I

I

... _,