ML20059F517
| ML20059F517 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 10/25/1993 |
| From: | FLORIDA POWER CORP. |
| To: | |
| References | |
| AR-401, NUDOCS 9311040336 | |
| Download: ML20059F517 (180) | |
Text
.
~
I DOCUMENT TRANSMITTAL 3701
.j FOR DOCUMENT NOTIFICATION AND/OR TRANSMITTAL i
TO: NRC(DC DESK)
MAC:
(
DATE:
Tue Oct 26 07:51:31 1993 l
t I
CPY COPY TOTALS DOCUMENT REV COMMENTS INFO CNTL MSTR I
1 AR0401 11 24 1
0 0
.)
1 I
i i
i
'l i
1 1
l a
l I
l l
l ESTRUCTIDNSTDTHE ADDRESSEE:
I IF TDU ARE A HDLDER of A MARD CDPV,PLEASE VERIFY THE DOCUMENTIS) RECEIVED AGREES WITH1HE ABDVE DESCRIPTION.
DE SURE TD DISTRDY DDCUMENTIS) DR PDRTtDNS OF DDCUMENTISI SUPERSEDED BY THE ABDVL i
THE SIGNATURE INDICATES THAT TDU HAVE RE AD AND UNDERSTAND THESE INSTRUCTIDNS AND THE CHANGES TO THE DDCUMENTS.
l CETURN SIGNED AND DATED TRANSMITI AL TD MAK CDDE:
~~ NR2B I
SAIS
~ NA1C
[ Fiende Power Corporaties P.D. Seu T19 Crystal Rieer,fL 34423 0210 l
SIGNATURE OF ADDRESSEE DATE-I 03000; EDEPENDENT VERIFICATIDN (Dperstiene Dald v
DATE I
I i
9311040336 931025 g
l PDR ADOCK 05000302 O l
F PDR j
l
5 Rev. 11 10/14/93 i
/d!88 98 Effective Date i
- - ~ = " " '
__ m _ me-m ~
Document Section I,
NPORM ATION ONL
.-r---
ANNUNCIATOR RESPONSE AR-401 i
FLORIDA POWER CORPORATION CRYSTAL RIVER UNIT 3 PSA F ANNUNCIATOR RESPONSE THIS PROCEDURE ADDRESSES SAFETY RELATED COMPONENTS t
APPROVED BY:
In er ation Contact O
A b UMh DATE:
/0-25 -9 3 v
INTERPRETATION CONTACT: Manager, Nuclear Plant Operations
TABLE OF CONTENTS s
SECTION PAGE 4
1.0 PURPOSE............................
I l
t 2.0 REFERPsil 1
l 2.1 INPLENENTING REFERENCES...............
I 2.2 DEVELOPNENTAL REFERENCES I
j 3.0 PERSONNEL INDOCTRINATION 1
l 4.0 INSTRUCTIONS 1
i 5.0 FOLLOW-UP ACTIONS.......................
I l
ENCLOSURES 1
Annunciator Response......................
2 1
t i
i t
t i
i l
i i
l I
AR-401 Rev. 11 Page i 1
I
i 1.0 PURPOSE i
i 1.1 Establish a reference document for each Annunciator Window on the l
PSA-X Lampbox.
}
1.2 Establish operator status for valid Annunciator alarms on the PSA-X Lampbox.
r 1.3 Establish a reference to other ' procedures which address operator i
actions for valid Annunciator alarms on the PSA-X Lampbox.
[
l
2.0 REFERENCES
L 1
3 I
i 2.1 IMPLEMENTING REFERENCES l
2.1.1 OP-409 - Plant Ventilation 2.1.2 OP-417 - Containment Operating Procedure 2.1.3 OP-703 - Plant Distribution Syste.m 2.1.4 AP-250 - Radiation Monitor Actuation 2.1.5 AP-513 - Toxic Gas l
2.1.6 AP-880 - Fire Protection 2.2 DEVELOPMENTAL REFERENCES i
1 2.2.1 INP0 90-021, Good Practice OP-217, Alarm Response Procedures
[
1 i
2.2.2 Annunciator Window Engraving Drawing E-224-048 i
d 3.0 PERSONNEL INDOCTRINATION i
j 3.1 The Annunciator System is powered from VBDP-5 Breaker 28.
l i
l 4.0 INSTRUCTIONS 4.1 Respond to alarms on the PSA-X Lampbox as indicated on Enclosure 1, Annunciator Response.
f 5.0 FOLLOW-UP ACTIONS
{
i None I
i AR-401 Rev. 11 Page 1 i
,._,.,_,,,,I
ENCLOSURE 1 (Page 1 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP EVENT POINT 0466 INDICATED CONDITION:
o AHF-17A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION
()
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 2DERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-17B o RESTORE VENTILATION PER OP-409 o REFER TO AP-250 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-80 SENSING ELEMENT: CS/SC, CS/0, 42B
(}
i AR-401 Rev. 11 Page 2 l
i ENCLOSURE 1 (Page 2 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX l
FAN I
TRIP l
l l
EVENT POINT 0467 i
INDICATED CONDITION:
o A:!F-17B HOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250
(
o START AHF-17A o RESTORE VENTILATION PER OP-409 DISCUSSION:
t
REFERENCES:
DRAWING 208-005 SHEET AH-81 SENSING ELEMENT:
CS/SC, CS/0, 42B O
AR-401 Rev. 11 Page 3
I ENCLOSURE 1 (Page 3 of 182) i i
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 j
i CNTRL COMPLEX FAN TRIP EVENT POINT 0470 INDICATED CONDITION:
o AHF-18A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-18A CONTROL STATION 8
i OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-18B o RESTORE VENTILATION PER OP-409 DISCUSSION:
l REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
i
REFERENCES:
DRAWING 208-005 SHEET AH-82 SENSING ELEMENT: CS/SC, CS/0, 42B O
.AR-401 Rev. 11 Page 4
2 I
ENCLOSURE 1 O
(Page 4 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 i
CNTRL COMPLEX FAN TRIP EVENT POINT 0471-INDICATED CONDITION:
t o AHF-18B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-ISB CONTROL STATI0:1 l
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP i
o START AHF-18A o RESTORE VENTILATION PER OP-409 DISCUSSION:
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS I
REFERENCES:
DRAWING 208-005 SHEET AH-83 SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 11 Page 5
... l
i ENCLOSURE 1 O
(Page 5 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX
. FAN I
TRIP I
I l
l EVENT POINT 0478 INDICATED CONDITION:
o AHF-19A MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER
[
START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-19A CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 t
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250 o START AHF-19B o RESTORE VENTILATION PER OP-409 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-86 SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 11-Page 6
ENCLOSURE 1
('g i/
(Page 6 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 CNTRL COMPLEX FAN TRIP EVENT POINT 0479 INDICATED CONDITION:
o AHF-19B MOTOR IS NOT ENERGIZED WITH CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-19B CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o START AHF-19A o RESTORE VENTILATION PER OP-409 o REFER TO AP-250 DISCUSSION:
REFERENCES:
DPAWING 208-005 SHEET AH-87 f]
SENSING ELEMENT:
CS/SC, CS/0, 42B x_-
AR-401 Rev. 11 Page 7
i i
j ENCLOSURE I (Page 7 of 182) 4 PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01
)
)
{____
l CNTRL COMPLEX I
FAN I
TRIP I
i l
i I
l EVENT POINT 0482 l
I
)
INDICATED CONDITION:
o AHF-20A MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN l
THE PUSHED IN NORMAL AFTER START POSITION I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 i
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 o REFER TO AP-250 DISCUSSION:
IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION
REFERENCES:
DRAWING 208-005 SHEET AH-88 SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 42B AR-401 Rev. 11 Page 8 I
i 2
ENCLOSURE 1 O
(Page 3 of 182) l l
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l
t CNTRL COMPLEX FAN TRIP EVENT POINT 0483 l
INDICATED CONDITION:
o AHF-20A MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN THE PULLED OUT NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-20A CONTROL STATION l
OPERATOR ACTIONS FOR A VALID ALARM:
i o INVESTIGATE THE CAUSE OF 1 RIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-88 SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 42B O
i AR-401 Rev. 11 Page 9
l ENCLOSURE 1 O'
(Page 9 of 182) j PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l
l CNTRL COMPLEX l
l FAN i
R I
TRIP R
I 2
ll l
H I
EVENT POINT 0484 4
INDICATED CONDITION:
o AHF-20B MOTOR FAST SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN l
THE PUSHED IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
1 o GREEN FAST SPEED LIGHT ON WITH A RED FLAG ON AHF-20B CONTROL STATION o RADIATION HIGH RAD ALARM RM-A-5 4
5 l
{
OPERATOR ACTIONS FOR A VALID ALARM:
i o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED o REFER TO OP-409 o REFER TO AP-250 1
DISCUSSION:
IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION 4
REFERENCES:
DRAWING 208-005 SHEET AH-89 SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 42B d
AR-401 Rev. 11 Page 10
l ENCLOSURE 1 (Page 10 of 182)
{
4 l
f PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 ll i
l l
CNTRL COMPLEX FAN TRIP J
i j
i i
s EVENT POINT 0485 i
1 I
INDICATED CONDITION:
l o AHF-20B MOTOR SLOW SPEED WINDINGS ARE NOT ENERGIZED, CONTROL HANDLE IN i
i THE PULLED OUT NORMAL AFTER START POSITION l
i j
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O J
o GREEN SLOW SPEED LIGHT ON WITH A RED FLAG ON AHF-20B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
I o INVESTIGATE THE CAUSE OF TRIP o NOTIFY CHEMISTRY SAMPLE HOOD VENTILATION IS SECURED 3
o REFER TO OP-409 J
)
i l
DISCUSSION:
IT MAY BE POSSIBLE TO OPERATE AHF-20A/B IN SLOW SPEED WITH AHF-44A/B IN OPERATION TO PROVIDE CHEMISTRY SAMPLE HOOD VENTILATION
REFERENCES:
DRAWING 208-005 SHEET AH-89
]
SENSING ELEMENT: CS/SC, CS/0, NC/LAT, 42B I
AR-401 Rev. 11 Page 11 i
. -..,.,, ~.
~,. -.
l ENCLOSURE 1 O
(Page 11 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01
%ZZZZZ CNTRL COMPLEX l
FAN I
TRIP I
i I
EVENT POINT 0489 1
i i
a INDICATED CONDITION:
I o AHF-21A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER i
START POSITION i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-21A CONTROL STATION o RADIATION HIGH RAD RM-A-5 i
OPERATOR ACTIONS FOR A VALID ALARM:
I o INVESTIGATE THE CAUSE OF TRIP i
o REFER TO AP-250 o START AHF-21B o RESTORE VENTILATION PER OP-409 i
l DISCUSSION:
i
REFERENCES:
DRAWING 208-005 SHEET AH-91 4
SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 11 Page 12
-.-.-.--.--...-..1
j ENCLOSURE 1 O
(Page 12 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 j
CNTRL COMPLEX FAN TRIP
)
EVENT POINT 0490 i
INDICATED CONDITION:
l i
o AHF-21B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-21B CONTROL STATION o RADIATION HIGH RAD RM-A-5 OPERATOR ACTIONS FOR A VALID ALARM:
1 o INVESTIGATE THE CAUSE OF TRIP o REFER TO AP-250 o START AHF-21A o RESTORE VENTILATION PER OP-409 1
l v
DISCUSSION:
4 4
- i
REFERENCES:
DRAWING 208-005 SHEET AH-92 SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 11 Page 13
ENCLOSURE 1 (Page 13 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-01-01 F-01-01 l
i CNTRL COMPLEX FAN TRIP EVENT POINT 0491 INDICATED CONDITION:
o AHF-30 MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-30 CONTROL STATION 4
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TRIP o REFER TO OP-409 DISCUSSION:
i
REFERENCES:
DRAWING 208-005 SHEET AH-93 i
SENSING ELEMENT: CS/SC, CS/0, 42B AR-401 Rev. 11 Page 14 I
ENCLOSURE I (Page 14 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW F-LOW I
I I
I EVENT POINT 0308 INDICATED CONDITION:
o AIR FLOW FROM "A" BATTERY ROOM IS LOW AS SENSED BY AH-734-FS 1
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o POSSIBLE FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR H, CONCENTRATIONS o
DISCUSSION:
i THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPERS IN THE CORRECT POSITION. THIS LOSS OF FLOW FROM THE BATTERY ROOM COULD RESULT IN A BUILD UP 0F HYDR 0 GEN INSIDE THE BATTERY ROOM.
CONSIDERATION SHOULD BE GIVEN TO VENTILATING THE AREA TO PREVENT THE i
POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.
REFERENCES:
DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-734-FS AR-401 Rev. 11 Page 15
ENCLOSURE 1 O
(Page 15 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 l
I CNTRL COMPLEX AIR FLOW LOW I
1 EVENT POINT 0309 l
INDICATED CONDITION:
o AIR FLOW FROM "B" BATTERY ROOM IS LOW AS SENSED BY AH-735-FS i
t i
]
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FIRE DAMPER ALARMS i
OPERATOR ACTIONS FOR A VALID ALARM:
}
l o INVESTIGATE THE CAULE OF ALARM o CHECK FOR FIRE DAMPER OPERATIO.,
o HAVE CHEMISTRY SAMPLE BATTERY ROOM FOR H CONCENTRATIONS l
z l
l DISCUSSION:
l l
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPERS IN THE CORRECT POSITION. THIS LOSS OF FLOW FROM THE BATTERY ROOM COULD RESULT IN A BUILD UP OF HYDROGEN INSIDE THE BATTERY ROOM.
CONSIDERATION SHOULD BE GIVEN TO VENTILATING-THE AREA TO PREVENT THE POSSIBILITY OF AN EXPLOSIVE MIXTURE DEVELOPING.
REFERENCES:
DRAWING 208-005 SHEET AH-131
(}
SENSING ELEMENT: AH-735-FS AR-401 Rev. 11 Page 16
ENCLOSURE 1 (Page 16 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0442 INDICATED CONDITION:
o AHF-16A CONTROL HANDLE IN NORMAL AFTER START, AND DIFFERENTIAL PRESSURE ACROSS AHHE-10A IS <0.063"H O AS SENSED BY AH-123-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-16A TRIPPED o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPERATION o START AHF-16B TO SUPPLY SWITCHGEAR ROOMS DISCUSSION:
THIS CONDITION AAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPER POSITION.
REFERENCES:
DRAWING 208-005 SHEET AH-058, DRAWING 308846 f}
SENSING ELEMENT: AH-123-DPS m
AR-401 Rev. 11 Page 17
',r^'
ENCLOSURE 1
( j)
(Page 17 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 l
CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0446 INDICATED CONDITION:
o AHF-168 CONTROL HANDLE IN NORMAL AFTER START, AND DIFFERENTIAL PRESSURE ACROSS AHHE-10B IS <0.050"H O AS SENSED BY AH-124-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
7,()
o AHF-16B TRIPPED o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR FIRE DAMPER OPEPATION o START AHF-16A TO SUPPLY SWITCHGEAR ROOMS DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE DAMPER ACTUATION, CHECK FIRE DAMPER POSITION.
REFERENCES:
DRAWI"S 208-005 SHEET AH-059, DRAWING 308846 SENSING ELEMENT:
d-124-DPS C
v' AR-401 Rev. 11 Page 18
ENCLOSURE I O
(Page 18 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 i
i CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0468 l
INDICATED CONDITION:
o AHF-17A, OR AHF-18A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <15"H O AS SENSED BY AH-34-DPS i
2 i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW FLOW INDICATION ON AH-32-FIR o POSSIBLE FAN TRIP ALARMS 1
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 i
i DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.
ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.
4 1,
REFERENCES:
DRAWING 208-005 SHEET AH-080, DRAWING 308847 SENSING ELEMENT: AH-34-DPS O
AR-401 Rev. 11 Page 19
- l ENCLOSURE 1 (Page 19 of 182)
~
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 i
1 CNTRL COMPLEX i
AIR FLOW 4
LOW l
l l
EVENT POINT 0480 INDICATED CONDITION:
i i
o AHF-19A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <10"H O AS SENSED BY AH-176-DPS 2
)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS l
o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
I o INVESTIGATE THE CAUSE OF ALARM i
o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM j
o REFER TO OP-409 i
DISCUSSION:
f THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A HAE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
l h
REFERENCES:
DRAWING 208-005 SHEET AH-086, DRAWING 308847 l
SENSING ELEMENT: AH-176-DPS r
O i
-i AR-401 Rev. 11 Page 20'-
l
~.. _..,..
l t
ENCLOSURE I O
(Page 20 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 0486 i
r INDICATED CONDITION:
i 4
o AHF-20A CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.08"H O AS SENSED BY AH-36-DPS l
2 t
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS 6
]
o FIRE DAMPER ALERTS j
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM j
o REFER TO OP-409 i
i i
j DISCUSSION:
?
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER?
j ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE l
CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
l
REFERENCES:
DRAWING 208-005 SHEET AH-088, DRAWING 308847 SENSING ELEMENT: AH-36-DPS l
O i
AR-401 Rev. 11 4
Page 21 1
1
ENCLOSURE 1
~
(Page 21 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX AIR FLOW LOW EVENT POINT 1545 INDICATED CONDITION:
o AHF-17B, OR AHF-18B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK 0F <15"H O AS SENSED BY AH-546-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
('
o LOW FLOW INDICATION ON AH-32-FIR o POSSIBLE FAN TRIP ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 f
DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FLOW BLOCKAGE.
ALTERNATING VENTILATION EQUIPMENT SHOULD CORRECT THE CONDITION.
REFERENCES:
DRAWING 208-005 SHEET AH-081, DRAWING 308847 SENSING ELEMENT: AH-546-DPS AR-401 Rev. 11 Page 22 D
l I
ENCLOSURE 1 O'
(Page 22 of 182) 4 PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 i
i I
l CNTRL COMPLEX AIR FLOW LOW j
EVENT POINT 1546 l
INDICATED CONDITION:
4 o AHF-19B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <10"H O AS SENSED BY AH-547-DPS 2
f REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALERTS i
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM i
o REFER TO OP-409 i
i DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-086, DRAWING 308847 SENSING ELEMENT: AH-547-DPS O
AR-401 Rev. 11 Page 23 i
ENCLOSURE I
(~'))
(Page 23 of 182)
(
PSA ANNUNCIATOR RESPONSE PSA-X-01-02 F-01-02 CNTRL COMPLEX l
AIR FLOW LOW j
EVENT POINT 1547 INDICATED CONDITION:
o AHF-20B CONTROL HANDLE IN NORMAL AFTER START AND A LOW FLOW CONDITION EXISTS IN DUCT WORK OF <0.08"H O AS SENSED BY AH-548-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALERTS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF ALARM o CHECK FOR TRIPPED FIRE DAMPERS o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-089, DRAWING 308847 SENSING ELEMENT: AH-548-DPS AR-401 Rev. 11 Page 24
ENCLOSURE 1 O
(Page 24 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-03 F-01-03 AH FLTR 4A/B PRESS HIGH I
EVENT POINT 0476 i
INDICATED CONDITION:
I o A HIGH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-4A 0F <5.20"H O AS 2
SENSED BY AH-205-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DIFFERENTIAL PRESSURE INDICATOR AH-205-DPI-1 ON REAR OF MCB o PJSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 l
l DISCUSSION:
l THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE l
CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
i i
REFERENCES:
DRAWING 208-005 SHEET AH-131, DRAWING 308847 SENSING ELEMENT: AH-205-DPS AR-401 Rev. 11 Page 25
. m
ENCLOSURE I (Page 25 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-03 F-01-03 AH FLTR 4A/B PRESS HIGH I
EVENT POINT 0477 INDICATED CONDITION:
o A HIGH DIFFERENTIAL PRESSURE EXISTS ACROSS AHFL-4B 0F <5.20"H O AS 2
SENSED BY AH-206-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DIFFERENTIAL PRESSURE INDICATOR AH-206-DPI-I ON REAR OF MCB o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o ALTERNATE VENTILATION EQUIPMENT TO CLEAR ALARM o REFER TO OP-409 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FAN TRIP, OR A FIRE DAMPER ACTUATION.
IF ALTERNATING VENTILATION EQUIPMENT DOES NOT CORRECT THE CONDITION THERE IS PROBABLY A FIRE DAMPER TRIPPED.
REFERENCES:
DRAWING 208-005 SHEET AH-131, DRAWING 308847 SENSING ELEMENT: AH-206-DPS O
AR-401 Rev. 11 Page 26
ENCLOSURE 1 (Page 26 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0469 INDICATED CONDITION:
o HIGH TEMPERATURE OF >135'F EXISTS IN THE CONTROL COMPLEX SUPPLY DUCT AS SENSED BY AH-207-TS, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM j
o REFER TO OP-409 e
o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.
IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-080, DRAWING 308847 SENSING ELEMENT: AH-207-TS O
1 AR-401 Rev. 11 Page 27
ENCLOSURE I (Page 27 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH EVENT POINT 0487 INDICATED CONDITION:
o HIGH TEMPERATURE OF >I35'F EXISTS IN THE DISCHARGE OF AHF-20A DUCT AS SENSED BY AH-258-TS, REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 O REFER TO AP-880 DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.
IF SO A FIRE 1
DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
i i
REFERENCES:
DRAWING 208-005 SHEET AH-088, DRAWING 308847 SENSING ELEMENT: AH-258-TS 1
AR-401 Rev. 11 Page 28 i
=. _.,
d ENCLOSURE I O
(Page 28 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 l
CNTRL COMPLEX DUCT TEMP i
HIGH j
EVENT POINT 0517 l
l l
l l
INDICATED CONDITION:
i l
o HIGH TEMPERATURE' EXISTS OF >135'F IN THE DISCHARGE OF AHF-20B DUCT AS SENSED BY AH-543-TS, t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
o POSSIBLE FAN TRIP ALARMS o FIRE DAMPER ALARMS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 DISCUSSION-THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.
IF SO A FIRE i
DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
i
REFERENCES:
DRAWING 208-005 SHEET AH-089, DRAWING 308847 SENSING ELEMENT: AH-543-TS AR-401 Rev. 11 Page 29
ENCLOSURE 1 O
(Page 29 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-04 F-01-04 CNTRL COMPLEX DUCT TEMP HIGH i
EVENT POINT 0493 INDICATED CONDITION:
o HIGH TEMPERATURE OF >135 F EXISTS IN THE CONTROL COMPLEX RETURN DUCT ON ELEVATION 124' AS SENSED BY AH-191-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o POSSIBLE LOW AIR FLOW ALARMS o FIRE DAMPERS FD-28, AND FD-29 ACTUATE OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE HIGH TEMPERATURE ALARM o REFER TO OP-409 o REFER TO AP-880 I
i DISCUSSION:
THIS CONDITION MAY BE THE RESULT OF A FIRE IN THE DUCT.
IF SO A FIRE DAMPER ACTUATION IS AN INDICATION OF A VALID ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-101, DRAWING 308847 SENSING ELEMENT: AH-191-TS AR-401 Rev. II Page 30
ENCLOSURE 1
/^(
(Page 30 of 182)
PSA ARNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 i
CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1690 INDICATED CONDITION:
o AIR PRESSURE IN THE RECEIVER OF AHP-1A/lB AS SENSED BY AH-507-PS IS
<55 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
0 LOCAL PRESSURE INDICATOR AH-896C-PI ON JOHNSON CONTROL PANEL 25A OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1A/1B ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR T0 "AB" SYSTEM COMP 0NENTS.
~
REFERENCES:
DRAWING 208-005 SHEET AH-148 SENSING ELEMENT: AH-507-PS r~
\\
AR-401 Rev. 11 Page 31
ENCLOSURE 1 (Page 31 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1691
)
INDICATED CONDITION:
o AIR PRESSURE IN THE RECEIVER OF AHP-IC/1D AS SENSED BY AH-509-PS IS <55 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL PRESSURE INDICATOR AH-894C-PI ON JOHNSON CONTROL PANEL 25B OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1C/1D ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) i o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE) l DISCUSSION:
1 THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMPONENTS AND A LOSS OF "B" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-149 SENSING ELEMENT: AH-509-PS O
AR-401 Rev. 11 Page 32
ENCLOSURE 1
(,)
(Page 32 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1692 INDICATED CONDITION:
o AIR PRESSURE IN THE RECEIVER OF AHP-1A/1B AS SENSED BY AH-512-PS IS <l7 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
,-~
o LOCAL PRESSURE INDICATOR AH-896B-PI ON JOHNSON CONTROL PANEL 25A OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-1A/lB ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "A" COMPONENTS AND A LOSS OF "A" SYSTEM AIR TO "AB" SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENT:
AH-512-PS O
AR-401 Rev. 11 Page 33
4
.]
ENCLOSURE 1 O
l (Page 33 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-05 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW EVENT POINT 1693 i
IHDICATED CONDITION:
o AIR PRESSURE FOR DAMPER CONTROL AS SENSED BY AH-513-PS IS <17 PSIG P
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL PRESSURE INDICATOR AH-895B-PI ON JOHNSON CONTROL PANEL 25AB OPERATOR ACTIONS FOR A VALID ALARM:
i o ENSURE THAT AHP-1A/1B ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM COMPONENTS l
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-513-PS O
AR-401 Rev. 11 Page 34
ENCLOSURE 1 (Page 34 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-09 F-01-05 CNTRL COMPLEX INST AIR PRESS LOW I
i EVENT POINT 1694 I
INDICATED CONDITION:
o AIR PRESSURE IN THE RECEIVER OF AHP-IC/lD AS SENSED BY AH-514-PS IS <17 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL PRESSURE INDICATOR AH-8948-PI ON JOHNSON CONTROL PANEL 25B f
OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE THAT AHP-IC/1D ARE RUNNING o VERIFY SAV-406 AND SAV-405 (CC STATION AIR SUPPLY VALVES) OPEN i
o DEENERGIZE AH-517-SV (CC CONTROL AIR SUPPLY VALVE) o ENERGIZE AH-518-SV (CC CONTROL AIR SUPPLY VALVE)
DISCUSSION:
THIS CONDITION MAY RESULT IN THE LOSS OF CONTROL AIR TO CONTROL COMPLEX VENTILATION SYSTEM "B" COMPONENTS AND A LOSS OF "B" SYSTEM AIR TO "AB" i
SYSTEM COMPONENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-514-PS O
AR-401 Rev. 11 Page 35
ENCLOSURE 1 (Page 35 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01-06 i
CNTRL COMPLEX AIR DRYER TEMP i
HIGH I
EVENT POINT 1695 l
INDICATED CONDITION:
o AIR TEMPERATURE ON THE OUTLET OF AHDR-1A IS >45*F AS SENSED BY AH-510-TS l
t REDUNDANT INDICATION WHICH'WILL VERIFY ALARM:
6 OPERATOR ACTIONS FOR A VALID ALARM:
l 0 NOTIFY HVAC PERSONNEL TO INSPECT AHDR-IA FOR PROPER OPERATION I
t l
l
)
DISCUSSION:
AHDR-1A IS REFRIGERATED AIR DRYER WHICH UTILIZES A REFRIGERANT CYCLE TO DRY CONTROL COMPLEX CONTROL AIR SUPPLY. HIGH AIR TEMPS CAN BE CAUSED BY LOW REFRIGERANT CHARGE OR A DIRTY CONDENSER C0ll.
REFERENCES:
ORAWING 208-005 SHEET AH-150 l
SENSING ELEMENT: AH-510-TS O
l AR-401 Rev. 11 Page 36 l
l
(
f l
ENCLOSURE I (Page 36 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-06 F-01-06
{
i CNTRL COMPLEX AIR DRYER TEMP i
HIGH j
EVENT POINT 1696 INDICATED CONDITION:
l o AIR TEMPERATURE ON THE OUTLET OF AHDR-1B IS >45'F AS SENSED BY AH-511-TS l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O I
t OPERATOR ACTIONS FOR A VALID ALARM:
j o NOTIFY HVAC TO INSPECT AHDR-1B FOR PROPER OPERATION DISCUSSION:
AHDR-1B IS REFRIGERATED AIR DRYER WHICH UTILIZES A REFRIGERANT CYCLE TO DRY CONTROL COMPLEX CONTROL AIR SUPPLY. HIGH AIR TC4PS CAN BE CAUSED BY j
LOW REFRIGERANT CHARGE OR A DIRTY CONDENSER COIL.
i
REFERENCES:
DRAWING 208-005 SHEET AH-150 SENSING ELEMENT: AH-511-TS AR-401 Rev. 11 Page 37
ENCLOSURE 1 s s q)
(Page 37 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 0518 INDICATED CONDITION:
o CHP-1A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o GREEN LIGHT ON WITH A RED FLAG ON THE CHP-1A CONTROL STATION o RUNNING CHILLER TRIPS ON LOW CHILLED WATER FLOW OPERATOR ACTIONS FOR A VALID ALARM:
o START CHP-1B AND CHHE-1B PER OP-409 DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET CH-03 SENSING ELEMENT: AH-511-TS AR-401 Rev. 11 Page 38
i ENCLOSURE 1
.)
(Page 38 of 182) l l
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 t
CHILLED WATER SYSTEM TROUBLE EVENT POINT 0519 t
INDICATED CONDITION:
o CHP-1B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN THE NORMAL f
AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON THE CHP-1B CONTROL STATION o RUNNING CHILLER TRIPPED ON LOW CHILLED WATER FLOW OPERATOR ACTIONS FOR A VALID ALARM:
+
o START CHP-1A AND CHHE-IA PER OP-409 i
I i
l DISCUSSION:
1 j
REFERENCES:
DRAWING 208-005 SHEET CH-04 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 11 Page 39
I ENCLOSURE 1
(
(Page 39 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
CHILLED WATER SYSTEM i
TROUBLE I
i EVENT POINT 0520 i
4 INDICATED CONDITION:
i o CHHE-1A BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION I
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CHHE-1A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o SWAP CHILLERS PER OP-409 l
l DISCUSSION:
l AN ES BUS UNDERVOLTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABLE TO BE RECLOSED UNTIL THE UNDERV0LTAGE LOCK OUT HAS BEEN RESET.
REFERENCES:
DRAWING 208-076 SHEET CH-01 SENSING ELEMENT: CS/SC, CS/0, R/B CONTACT AR-401 Rev. 11 Page 40
ENCLOSURE 1 i
O (Page 40 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 0521 4
INDICATED CONDITION:
o CHHE-1B BREAKER IS OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
o GREEN LIGHT ON WITH A RED FLAG ON CHHE-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS o SWAP CHILLERS PER OP-409 l
l DISCUSSION:
l AN ES BUS UNDERVOLTAGE CONDITION WILL CAUSE THIS CONDITION, THE BREAKER WILL NOT BE ABLE TO BE RECLOSED UNTIL THE UNDERVOLTAGE LOCK OUT HAS BEEN RESET.
REFERENCES:
DRAWING 208-076 SHEET CH-02 SENSING ELEMENT:
CS/SC, CS/0, R/B CONTACT O
AR-401 Rev. 11 Page 41
ENCLOSURE 1 O
(Page 41 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 i
CHILLED WATER SYSTEM TROUBLE EVENT POINT 1526 INDICATED CONDITION:
o CHT-1 LEVEL IS < 180' 2",
OR < 12" BELOW CENTER LINE OF TANK l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
o LOCAL LEVEL INDICATOR ON CHT-1 i
OPERATOR ACTIONS FOR A VALID ALARM:
[
o CONTACT CHEMISTRY AND REFILL CHT-I REFER TO OP-409 i
DISCUSSION:
I
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT: CH-660-LSS P
i AR-401 Rev. 11 Page 42 l
1 j
ENCLOSURE 1 (Page 42 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
r CHILLED WATER SYSTEM t
TROUBLE EVENT POINT 1554 INDICATED CONDITION:
o CHHE-IA BREAKER HAS NO DC CONTROL POWER l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NO INDICATING LIGHTS ON CHHE-IA CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
l f
o VERIFY " PULL OUT" FUSE BLOCK FOR CHHE-IA BREAKER IS INSTALLED o VERIFY DPDP-5A BREAKER 9 CLOSED
)
DISCUSSION:
l THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.
~
REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.
l THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.
i f
REFERENCES:
DRAWING 208-076 SHEET CH-01 i
SENSING ELEMENT:
27C RELAY
!O t
AR-401 Rev. II Page 43 l
ENCLOSURE 1
()'
(Page 43 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1555 INDICATED CONDITION:
o CHHE-1B BREAKER HAS NO DC CONTROL POWER REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o NO INDICATING LIGHTS ON CHHE-1B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY PULL OUT FUSE BLOCK FOR CHHE-1B BREAKER IS INSTALLED o VERIFY DPDP-5B BREAKER 9 CLOSED DISCUSSION:
THIS CONDITION DISABLES REMOTE BREAKER OPERATION AND PROTECTIVE RELAYING.
)
REFER TO OP-703 FOR INSTRUCTIONS ON LOCAL BREAKER OPERATION.
i THIS IS AN EXPECTED ALARM FOR BREAKER TAGGING OPERATIONS.
REFERENCES:
DRAWING 208-076 SHEET CH-02 lSENSINGELEMENT: 27C RELAY I
s l
AR-401 Rev. 11 Page 44
./s ENCLOSURE 1 (j)
(Page 44 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1556 INDICATED CONDITION:
o CHHE-IA MOTOR WINDING TEMPERATURE IS >105 C, OR CHHE-1A OIL TEMPERATURE IS >170 F.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(_)
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0ll/ MOTOR TEMPERATURE" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT:
6R, 2/A
'<J AR-401 Rev. 11 Page 45
l t
ENCLOSURE I i
O (Page 45 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 I
CHILLED WATER SYSTEM i
TROUBLE i
EVENT POINT 1557 l
INDICATED CONDITION:
o CHHE-IA REFRIGERANT PRESSURE IS <I7.9"HGA l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" b
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 l
t DISCUSSION:
(
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT:
7R, 2/A O
AR-401 Rev. 11 Page 46
l I
ENCLOSURE I O
(Page 46 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 i
l l
l l
CHILLED WATER SYSTEM TROUBLE l
EVENT POINT 1558 INDICATED CONDITION:
l 0 CHHE-1A REFRIGERANT PRESSURE IS >9 PSIG l
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE" OPERATOR ACTIONS FOR A VALID ALARM:
i o SWAP CHILLERS PER OP-409 i
i l
DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED l
i t
-1
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT: BR. 2/A O
\\
AR-401 Rev. 11 Page 47
ENCLOSURE I i
O (Page 47 of 182)
I PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
CHILLED WATER SYSTEM TROUBLE EVENT POINT 1559 INDICATED CONDITION:
o CHHE-1A OIL PRESSURE IS < 27 PSIG REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT: 9R, 2/A AR-401 Rev. 11 Page 48
4 ENCLOSURE I O
(Page 48 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1560 i
INDICATED CONDITION:
l o CHHE-1A DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR.
MOTOR AS SENSED BY RELAY 14/R
{
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:
l I
o INVESTIGATE THE CAUSE OF POWER LOSS i
I DISCUSSION:
i t
i 9
s
REFERENCES:
DRAWING 208-076 SHEET CH-05 SENSING ELEMENT:
14R, 2/A O
i I
i i
AR-401 Rev. 11 Page 49 i
I
ENCLOSURE I (Page 49 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1561 INDICATED CONDITION:
o CHHE-1B MOTOR WINDING TEMPERATURE IS >105 C, OR CHHE-1B OIL TEMPERATURE IS >170*F.
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "0ll/ MOTOR TEMP" OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 i
DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT:
6R, 2/B O
AR-401 Rev. 11 Page 50
i ENCLOSURE 1 i
O-(Page 50 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 P
CHILLED WATER SYSTEM l
TROUBLE i
EVENT POINT 1562 t
INDICATED CONDITION:
o CHHE-IB REFRIGERANT PRESSURE IS <17.9"HGA REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW PRESSURE" i
t OPERATOR ACTIONS FOR A VALID ALARM:
i o SWAP CHILLERS PER OP-409 DISCUSSION:
j THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSE]
l
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT:
7R, 2/B O
AR-401 Rev. 11 Page 51 i
..I
i I
ENCLOSURE I f
O (Page 51 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 l
CHILLED WATER SYSTEM i
TROUBLE EVENT POINT 1563 i
INDICATED CONDITION:
o CHHE-IB REFRIGERANT PRESSURE IS >9 PSIG j
i i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM-O LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR "HIGH PRESSURE" l
1 OPERATOR ACTIONS FOR A VALID ALARM:
l 0 SWAP CHILLERS PER OP-409
[
i DISCUSSION:
l 1
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN 4
UNTIL THE RESET PUSHBUTTON IS DEPRESSED J
~
l
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT: BR, 2/B AR-401 Rev. II Page 52
. ~.
^
i i
ENCLOSURE 1 (Page 52 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1564 l
INDICATED CONDITION:
l o CHHE-1B OIL PRESSURE IS < 27 PSIG I
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL CONTROL PANEL - RED INDICATOR LIGHT IS ON FOR " LOW OIL PRESS" l
l l
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP CHILLERS PER OP-409 l
l DISCUSSION:
THIS CONDITION WILL CAUSE THE CHILLER TO TRIP, THE CONDITION SEALS IN UNTIL THE RESET PUSHBUTTON IS DEPRESSED 1
REFERENCES:
DRAWING 208-076 SHEET CH-06 SENSING ELEMENT:
9R, 2/B l
l l
AR-401 Rev. 11 Page 53
.. - ~, _ _. _ - -.
ENCLOSURE 1
(~'
(,)/
(Page 53 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-01-07 F-01-07 CHILLED WATER SYSTEM TROUBLE EVENT POINT 1565 INDICATED CONDITION:
o CHHE-1B DOES NOT HAVE ANY POWER TO THE CONTROL PANEL OR COMPRESSOR MOTOR AS SENSED BY RELAY 14/R REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o AMBER " POWER FAILURE" LIGHT ON LOCAL CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF POWER LOSS DISCUSSION:
1
REFERENCES:
DRAWING 208-076 SHEET CH-06 j
SENSING ELEMENT:
14R, 2/B i
AR-401 Rev. 11 Page 54
4 d
ENCLOSURE 1 (Page 54 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 l
T0XIC GAS MONITOR TROUBLE EVENT POINT 0314 I
INDICATED CONDITION:
o ONE OR MORE OF THE FOLLOWING MONITORS' LOCAL TROUBLE ALARMS HAS
(
ACTUATED:
AH-648-CE AH-652-CE AH-649-CE AH-653-CE l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM.
3 o LOCAL TROUBLE ALARMS ON AH-648-CE, AH-649-CE, AH-652-CE, OR AH-653-CE o COMPUTER POINTS S263, S297, 5298, S299 FOR T0XIC GAS CONCENTRATION
[
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF TROUBLE o NOTIFY I&C TO TROUBLE SHOOT MONITORS t
DISCUSSION:
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
4
REFERENCES:
DRAWING 208-005 SHEET AH-84 SENSING ELEMENT: AH-648-CE, AH-652-CE AH-649-CE, AH-653-CE O
t AR-401 Rev. 11 Page 55
ENCLOSURE 1 O
(Page 55 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 i
2 T0XIC GAS MONITOR TROUBLE EVENT POINT 0432 INDICATED CONDITION:
l o T0XIC GAS >5 PPM CL AS SENSED BY AH-648-CE AND/0R AH-649-CE OR,
>2 PPM S0 SENSED BY AH-652-CE AND/0R AH-653-CE z
REDUNDANT INDICATION WHICH WILL VERIFY ALAPJ4:
o COMPUTER POINTS S263, S297, S298, OR S299 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO AP-513 o REFER TO SP-300 DISCUSSION:
i REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-84 SENSING ELEMENT: AH-648-CE, AH-652-CE, AH-649-CE, AH-653-CE O
\\
AR-401 Rev. 11 Page 56 lj
ENCLOSURE 1 O
(Page 56 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-01 F-02-01 l
T0XIC GAS i
MONITOR TROUBLE l
EVENT POINT 0800 INDICATED CONDITION:
o T0XIC GAS >20 PPM S0 SENSED DETECTORS AT UNITS 1&2 i
2 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NOTIFICATION OF A SPILL FROM UNITS 1&2 OPERATOR ACTIONS FOR A VALID ALARM-I r
o REFER TO AP-513 t
?
i DISCUSSION:
l REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
j I
i
REFERENCES:
DRAWING 208-005 SHEET AH-84 SENSING ELEMENT:
O AR-401 Rev. 11 Page 57
t ENCLOSURE I i
O (Page 57 of 182) 1 PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 l
CI CIRC PUMP 2A/B 3A/B TRIP h
EVENT POINT 0524 INDICATED CONDITION:
o CIP-2A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION l
[
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CIP-2A CONTROL STATION I
OPERATOR ACTIONS FOR A VALID ALARM:
o START CIP-2B l
0 HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS i
i DISCUSSION:
i f
REFERENCES:
DRAWING 208-077 SHEET CI-03 SENSING ELEMENT: CS/SC, CS/0, R/B f
AR-401 Rev. 11 Page 58
ENCLOSURE I
/'~(j}
(Page 58 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 i
CI CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0526 INDICATED CONDITION:
o CIP-2B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
o GREEN LIGHT ON WITH A RED FLAG ON CIP-2B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o START CIP-2A o HAVE BREAKER CUBICLE CHECKED FOR DROPPED TARGETS DISCUSSION:
REFERENCES:
DRAWING 208-077 SHEET CI-04 SENSING ELEMENT:
CS/SC, CS/0, R/B AR-401 Rev. II Page 59
ENCLOSURE I
(T q_,)
(Page 59 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 CI CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0528 INDICATED CONDITION:
o CIP-3A CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(~
(_,/
o GREEN LIGHT ON WITH A RED FLAG ON CIP-3A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING TO "B" SIDE PER OP-409 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-077 SHEET CI-18 SENSING ELEMENT: CS/SC, CS/0, 42B Y.
AR-401 Rev. 11 Page 60
ENCLOSURE 1 O
(Page 60 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-06 F-02-06 CI CIRC PUMP 2A/B 3A/B TRIP EVENT POINT 0529 INDICATED CONDITION:
o CIP-3B CONTROL HANDLE IN NORMAL AFTER START POSITION WITH THE MOTOR NOT ENERGIZED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON CIP-3B CONTROL STATION P
OPERATOR ACTIONS FOR A VALID ALARM:
l 0 SWAP REACTOR CAVITY COOLING T0 "A" SIDE PER OP-409 i
o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409
\\
DISCUSSION:
l A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE l
EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-077 SHEET CI-19 SENSING ELEMENT:
CS/SC, CS/0, 42B O
AR-401 Rev. 11 Page 61
J ENCLOSURE 1 O,
(Page 61 of 182) i j
PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 i
a CI CIRC PUMP 2A/B OVERLOAD T
l EVENT POINT 0525 I
INDICATED CONDITION:
{
o CIP-2A MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH LOCAL TEMPERATURES ON PUMP AND OR MOTOR OPERATOR ACTIONS FOR A VALID ALARM:
o SHUTDOWN CIP-2A AND START CIP-2B o INVESTIGATE THE OPERATION OF THE PUMP MOTOR TO DETERMINE THE CAUSE OF THE ALARM I
)
DISCUSSION:
THIS ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED AND THAT THE MOTOR MAY TRIP AT ANY TIME.
j
~
REFERENCES:
DRAWING 208-077 SHEET CI-03 j
SENSING ELEMENT: CS/SC, CS/0, 42B O
t AR-401 Rev. 11 Page 62 I
ENCLOSURE 1 I
(Page 62 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-07 F-02-07 i
i CI CIRC PUMP 2A/B OVERLOAD l
l EVENT POINT 0527 f
INDICATED CONDITION:
o CIP-2B MOTOR AMPS >IIS% RATED LOAD 1
)
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH LOCAL TEMPERATURES ON PUMP AND OR MOTOR t
t OPERATOR ACTIONS FOR A VALID ALARM:
o SHUTDOWN CIP-2B AND START CIP-2A
{
o INVESTIGATE THE OPERATION OF THE PUMP MOTOR TO DETERMINE THE CAUSE OF THE ALARM j
DISCUSSION:
THIS ALARM INDICATES THAT THE INTERNAL OVERCURRENT DEVICE HAS ACTUATED i
AND THAT THE MOTOR MAY TRIP AT ANY TIME.
1 i
REFERENCES:
DRAWING 208-077 SHEET CI-04 i
SENSING ELEMENT:
CS/SC, CS/0, 428 O
AR-401 Rev. II Page 63
ENCLOSURE 1 1
r~(])
(Page 63 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 CI PUMP SUCT PRESS LOW EVENT POINT 1702 INDICATED CONDITION:
o CIP-2A BREAKER IS CLOSED AND SUCTION PRESSURE IS < 5 PSIG AS SENSED BY CI-728-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-99-PI OPERATOR ACTIONS FOR A VALID ALARM:
o CHECK CIT-I LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE PRESSURE DROP ACROSS THE TOWER OR THE LEAK RATE TEST COOLER. THE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.
REFERENCES:
DRAWING 208-077 SHEET CI-03 SENSING ELEMENT-Cl-728-PS. R/A 1
AR-401 Rev. 11 Page 64 l
l ENCLOSURE 1 l
(Page 64 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 CI PUMP I
SUCT PRESS LOW EVENT POINT 1703 l
INDICATED CONDITION:
l 0 CIP-2B BREAKER IS CLOSED AND SUCTION PRESSURE IS < 5 PSIG AS SENSED BY CI-729-PS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-101-PI OPERATOR ACTIONS FOR A VALID ALARM:
o CHECK CIT-1 LEVEL l
o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE DISCUSSION:
THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OP, BY EXCESSIVE PRESSURE DROP ACROSS THE TOWER OR THE LEAK RATE TEST COOLER. THE LINE UP OF THE SYSTEM SHOULD BE VERIFIED.
l l
l
REFERENCES:
DRAWING 208-077 SHEET CI-04 SENSING ELEMENT:
CI-729-PS, R/A AR-401 Rev. 11 Page 65
l 4
I l
ENCLOSURE 1 i
O (Page 65 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 l
l l
l l
l CI PUMP
~
l i
SUCT PRESS 1
I LOW i
i I
i EVENT POINT 1704 i
INDICATED CONDITION:
o CIP-3A CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION PRESSURE IS 7
i
< 45 PSIG AS SENSED BY CI-730-PS
]
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-732-PI i
OPERATOR ACTIONS FOR A VALID ALARM:
I o CHECK CIT-I LEVEL o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409
[
l DISCUSSION:
i i
j THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR BY EXCESSIVE PRESSURE DROP ACROSS THE TOWER OR THE LEAK RATE TEST d
COOLER. THE LINE UP 0F THE SYSTEM SHOULD BE VERIFIED.
l l
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-077 SHEET CI-18 j
SENSING ELEMENT: CI-730-PS, CS/SC, CS/0 1
i AR-401 Rev. II Page 66
.-~J
k l
ENCLOSURE 1 l
(Page 66 of 182) l l
PSA ANNUNCIATOR RESPONSE PSA-X-02-08 F-02-08 I
I CI PUMP I
I I
l I
I SUCT PRESS I
I I
LOW t
i I
EVENT POINT 1705 0
INDICATED CONDITION:
l l
l
{
o CIP-3B CONTROL SWITCH IS IN NORMAL AFTER START, AND SUCTION PRESSURE IS
< 45 PSIG AS SENSED BY CI-731-PS i
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW LOCAL PRESSURES ON PUMP SUCTION GAUGE CI-733-PI OPERATOR ACTIONS FOR A VALID ALARM:
l o CHECK CIT-1 LEVEL I
o INVESTIGATE THE CAUSE OF LOW SUCTION PRESSURE o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 l
1 l
j DISCUSSION:
l l
3 THIS CONDITION COULD BE CAUSED BY A LOW LEVEL IN THE EXPANSION TANK, OR I
i BY EXCESSIVE PRESSURE DROP ACROSS THE TOWER OR THE LEAK RATE TEST i
COOLER. THE LINE UP 0F THE SYSTEM SHOULD BE VERIFIED.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE l
EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
l l
REFERENCES:
DRAWING 208-077 SHEET CI-19 SENSING ELEMENT: CI-731-PS, CS/SC, CS/0 l
.l AR-401 Rev. 11 Page 67 l
i
...n..
ENCLOSURE I
(
(Page 67 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT EVENT POINT 0427 INDICATED CONDITION:
o DUCT TEMPERATURE AT DISCHARGE OF AHF-46 IS > 125'F AS SENSED BY AH-667-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
ex()
o AHF-46 TRIPS DUE TO INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-46 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:
THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN Tl'E DUCT WORK.
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS.
AHF-46 IS THE RUSTY BUILDING RECIRC FAN.
REFERENCES:
DRAWING 208-005 SHEET AH-142 SENSING ELEMENT: AH-667-TS AR-401 Rev. 11 Page 68
l ENCLOSURE 1 O.
(Page 68 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-01 F-03-01 TURBINE BLDG FIRE ALERT i
i EVENT POINT 0512 INDICATED CONDITION:
o DUCT TEMPERATURE AT DISCHARGE OF AHU-7 IS > 125 F AS SENSED BY AH-670-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o AHU-7 TRIPS DUE TO INTERLOCK' t
O i
1 OPERATOR ACTIONS FOR A VALID ALARM:
1 o ENSURE AHU-7 IS SHUTDOWN o INVESTIGATE CAUSE OF ALARM i
DISCUSSION:
I THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE l
APPROPRIATE ACTIONS.
l AHU-7 IS THE RUSTY BUILDING AIR CONDITIONING UNIT.
i
REFERENCES:
DRAWING 208-005 SHEET AH-144 O
SENSING ELEMENT: AH-670-TS
%)
AR-401 Rev. 11 Page 69 i
~.
l O
ENCLOSURE 1 (Page 69 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0006 INDICATED CONDITION:
o PENETRATION COOLING DUCT TEMPERATURE UPSTREAM 0F FD-278 IS >165 F AS SENSED BY AH-1004-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o PENETRATION COOLING FANS AHF-9A/9B TRIP ON INTERLOCK OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-9A/9B ARE SHUTDOWN o INVESTIGATE CAUSE OF ALARM DISCUSSION:
THIS ALARM IS AN INDICATION OF A POSSIBLE FIRE IN THE DUCT WORK.
CONSIDERATION SHOULD BE GIVEN TO CONSULTING FIRE PLANS FOR THE APPROPRIATE ACTIONS. AH-1004-TS IS A MANUAL RESET TEMPERATURE SWITCH LOCATED AT INT. BLDG. 95' ELEV. NEXT TO THE LOCAL CONTROL STATION FOR AHF-9A AND 9B.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 SENSING ELEMENT: AH-1004-TS AR-401 Rev. 11 Page 70
l fNCLOSURE 1 (Page 70 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT i
i EVENT POINT 0380 l
i J
l INDICATED CONDITION:
i o RB PURGE SUPPLY DUCT TEMP IS >135'F AS SENSED Bf AH-23-TS, OR PRODUCTS l
0F COMBUSTION HAVE BEEN SENSED BY AH-23-CE AND/OR AH-24-CE, OR RELAY 3PSFP HAS ACTUATED l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o PURGE SUPPLY FANS AHF-6A/6B TRIP o PURGE SUPPLY DAMPER AHV-ID CLOSES ON LOW PURGE SUPPLY FLOW j
OPERATOR ACTIONS FOR A VALID ALARM:
l 0 INVESTIGATE THE CAUSE OF THE ALARM o SECURE RB PURGE PER OP-417 o REFER TO AP-880 l
DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE PURGE SUPPLY FAN DISCHARGE OUCT THE TEMPERATURE AND PRODUCT OF COMBUSTION DETECTORS SENSE THE DISCHARGE UPSTREAM 0F THE RECIRCULATION DAMPER.
REFERENCES:
DRAWING 208-005 SHEETS AH-020, AND AH-15, DRAWING 308849 SENSING ELEMENT: AH-23-TS, AH-23-CE, AH-24-CE, AND RELAY 3PSFP O
i AR-401 Rev. 11 Page 71 l
1 1
i J
ENCLOSURE 1 (Page 71 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 I
i AUX BLDG FIRE ALERT l
i I
EVENT POINT 0387 I
INDICATED CONDITION:
o RB PURGE EXHAUST DUCT TEMP IS >135*F AS SENSED BY AH-295-TS, OR PRODUCTS OF COMBUSTION HAVE BEEN SENSED BY AH-295-CE, OR RELAY 3PEFP HAS ACTUATED i
REDUNDANT INDICATION WHICH W TL VERIFY ALARM:
o PURGE EXHAUST FANS AHF-7A TB TRIP I
j f
OPERMOR ACTIONS FOR A VALID ALAkM:
l 0 INVESTIGATE THE CAUSE OF THE ALARM o SECURE THE RB PURGE REFER TO OP-417
[
o REFER TO AP-880 I
d DISCUSSION.
THIS IS INDICATIVE OF A FIRE IN THE PURGE EXHAUST DISCHARGE DUCT THE TEMPERATURE AND PRODUCT OF COMBUSTION DETECTORS SENSE THE DISCHARGE OF i
THE FANS i
(
REFERENCES:
DRAWING 208-005 SHEETS AH-020, AND AH-15, DRAWING 308849 SENSING ELEMENT: AH-295-CE, AH-295-TS, AND RELAY 3PEFP
- O
)
AR-401 Rev. Il Page 72
i ENCLOSURE I 4
l (Page 72 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG i
FIRE ALERT l
EVENT POINT 0391 INDICATED CONDITION:
o TEMPERATURE IS >I35'F IN SPENT FUEL AIR HANDLING FAN AHF-8A DISCHARGE 4
DUCT WORK AS SENSED BY AH-314-TS 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o AHF-8A TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM i
o REFER TO AP-880 l
1 l
i DISCUSSION:
l THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL COOLING UNIT DISCHARGE j
DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-026, DRAWING 308849 i
SENSING ELEMENT: AH-314-TS O
i AR-401 Rev. II Page 73
-.,c
_,,.,m_.,..
.,,...,,~~..-...,_.__,,__...m,7r.,,.
4 ENCLOSURE I i
O (Page 73 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG l
FIRE ALERT e
EVENT POINT 0394 INDICATED CONDITION:
1 I
o TEMPERATURE IS >135 F IN SPENT FUEL AIR HANDLING FAN AHF-8B DISCHARGE DUCT WORK AS SENSED BY AH-409-TS J
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
()
o AHF-8B TRIPS
[
l OPERATOR ACTIONS FOR A VALID ALARM:
i o INVESTiuAlt' THE CAUSE OF THE ALARM o REFER TO AP 880 i
DISCUSSION:
l THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL COOLING UNIT DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR l
ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION-i
REFERENCES:
DRAWING 208-005 SHEETS AH-027 DRAWING 308849 SENSING ELEMENT: AH-409-TS 4
a AR-401 Rev. 11 Page 74
.. ~.
l j
I ENCLOSURE I 4
(Page 74 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
l AUX BLDG j
1 FIRE ALERT i
(
l l
EVENT POINT 0403 INDICATED CONDITION:
a o TEMPERATURE IS >135 F IN SPENT FUEL AREA AIR HANDLING FAN AHF-10 l
DISCHARGE DUCT WORK AS SENSED BY AH-377-TS 1
4 REDUNDANT INDICATION WHICH WILL VERIFY ALARM-5 o AHF-10 TRIPS
.i i
OPERATOR ACTIONS FOR A VALID ALARM:
)
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 i
l l
DISCUSSION.
THIS IS INDICATIVE OF A FIRE IN THE SPENT FUEL FLOOR AIR HANDLING UNIT l
DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION l
REFERENCES:
DRAWING 208-005 SHEETS AH-044 DRAWING 308849 j
SENSING ELEMENT: AH-377-TS AR-401 Rev. 11 Page 75 l
. i
ENCLOSURE I (Page 75 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT l
l EVENT POINT 0410 INDICATED CONDITION:
o TEMPERATURE IS >135'F IN AUXILIARY BUILDING SUPPLY FAN DISCHARGE DUCT WORK AS SENSED BY AH-318-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-IIA / IIB FANS TRIP OPERATOR ACTIONS FOR A VALIO ALARM:
+
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880
)
DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING SUPPLY FANS DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION
REFERENCES:
DRAWING 208-005 SHEETS AH-045 DRAWING 308849 SENSING ELEMENT: AH-318-TS O
AR-401 Rev. 11 Page 76
I l
ENCLOSURE I l
(Page 76 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
i AUX BLDG FIRE ALERT i
i i
EVENT POINT 0416 i
i i
INDICATED CONDITION:
o TEMPERATURE IS >135'F IN AUXILIARY BUILDING RECIRC FAN SUCTION DUCT WORK AS SENSED BY AH-375-TS i
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f c AHF-13 TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
1 o INVESTIGATE THE CAUSE OF THE ALARM l
4 o REFER TO AP-880 i
I j
DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING RECIRC FAN DISCHARGE DUCT CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE
[
PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION i
REFERENCES:
DRAWING 208-005 SHEETS AH-048 DRAWING 308849 SENSING ELEMENT: AH-375-TS
- O AR-401 Rev. II Page 77 s
1 ENCLOSURE 1 O
(Page 77 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT J
l
]
EVENT POINT 0426 j
4 3
i INDICATED CONDITION:
l o TEMPERATURE IS >135*F IN AUXILIARY BUILDING EXHAUST DUCT WORK AS SENSED BY AH-354-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i AUXILIARY BUILDING EXHAUST FANS AHF-14A, AHF-14B, AHF-14C, & AHF-14'D f
o TRIP OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE THE CAUSE OF THE ALARM o REFER TO AP-880 l
l DISCUSSION:
THIS IS INDICATIVE OF A FIRE IN THE AUXILIARY BUILDING EXHAUST DISCHARGE DUCT, CONSIDERATION SHOULD BE GIVEN TO CONSULTING THE FIRE i
PLANS FOR ADDITIONAL HELP IN DETERMINING A COURSE OF ACTION l
i i
i
REFERENCES:
ORAWING 208-005 SHEETS AH-001, AND AH-005, DRAWING 308849 I
SENSING ELEMENT: AH-354-TS O
AR-401 Rev. 11 Page 78 l
DCLOSURE I
(~')T
(
(Page 78 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
AUX BLDG FIRE ALERT EVENT POINT 0431 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-156-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-156-CE o TEMPERATURE > 135'F AS SENSED BY AH-156-TS EXISTS AT THE 95' LEVEL INTERMEDIATE BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE TRIP 0F AHF-24A/B IF RUNNING o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42, AND FD-43 OPEPATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-51, AND AH-55. DRAWING 308846 SENSING ELEMENT: AH-156-CE, AH-156-TS, RELAY 3AH-156-TS/RRIA AR-401 Rev. 11 Page 79 1
I
\\
ENCLOSURE 1
()
V (Page 79 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG I
FIRE ALERT k
EVENT POINT 0433 INDICATED CONDITION:
o TEMPERATURE > 135 F AS SENSED BY AH-157-TS EXISTS AT THE 95' LEVEL INTERMEDIATE BUILDING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42, AND FD-43 OPEPATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THE IS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE 95' INTERMEDIATE BUILDING.
REFERENCES:
DRAWING 208-005 SHEETS AH-51, AND AH-55. DRAWING 308846 SENSING ELEMENT: AH-157-TS, U
AR-401 Rev. II Page 80
ENCLOSURE I (Q
3 (Page 80 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT EVENT POINT 0435 INDICATED CONDITION:
o PENETRATION COOLING SUPPLY AIR DUCT TEMPEPATURE UP3TREAM 0F FD-32 IS
>135'F AS SENSED BY AH-737-TS. OR AH-737-TS TROUBLE CIRCUIT HAS ACTUATED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o FD-32 FIRE DAMPER CLOSES o LOCAL TROUBLE ALARM ON AH-737-TS OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FD-32 CLOSED o REFER TO AP-880 DISCUSSION:
THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE TURBINE BUILDING ADJACENT TO THE FAN INTAKE, OR A PROBLEM WITH THE DETECTOR.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 p
SENSING ELEMENT: AH-737-CE, AH-737-CE TROUBLE CIRCUIT j
()
i AR-401 Rev. II Page 81
)
1 t
i ENCLOSURE 1 i
i (Page 81 of 182)
[
I PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT 4
i i
i EVENT POINT 0437
}
4 INDICATED CONDITION:
i o PENETRATION COOLING SUPPLY AIR DUCT TEMPERATURE UPSTREAM 0F FD-33 IS j
>135 F AS SENSED BY AH-738-TS. OR AH-738-TS TROUBLE CIRCUIT HAS ACTUATED REDUNDANT INDICATION WHICH.WILL VERIFY ALARM:
O i
i o FD-33 FIRE DAMPER CLOSES 1
o LOCAL TROUBLE ALARM ON AH-738-TS 1
l OPERATOR ACTIONS FOR A VALID ALARM:
o VERIFY FD-33 CLOSED i
i 1
4 I
f DISCUSSION-THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE OUTSIDE AIR INTAKE, OR OF A PROBLEM WITH THE DETECTOR
)
REFERENCES:
DRAWING 208-005 SHEET AH-057, DRAWING 308849 SENSING ELEMENT: AH-738-TS AND AH-38-TS TROUBLE AR-401 Rev. 11 Page 82
1 ENCLOSURE I (Page 82 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT i
EVENT POINT 0439 INDICATED CONDITION:
l c PENETRATION COOLING FAN DISCHARGE. DUCT TEMPERATURE IS >150*F AS SENSED BY AH-305-TS 1
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL TROUBLE ALARM ON AH-305-TS OPERATOR ACTIONS FOR A VALID ALARM:
l o ENSURE CHILL WATER IS SUPPLIED TO THE OPERATING PENETRATION COOLER o INVESTIGATE THE CAUSE OF THE HIGH TEMPERATURE ALARM o REFER TO AP-880 DISCUSSION:
THIS IS INDICATIVE OF A HIGH TEMPERATURE CONDITION IN THE DISCHARGE OF THE PENETRATION COOLING FANS, OR OF A PROBLEM WITH THE DETECTOR.
REFERENCES:
DRAWING 208-005 SHEET AH-056, DRAWING 308849 SENSING ELEMENT: AH-305-TS O
AR-401 Rev. 11 Page 83
{
i
l ENCLOSURE I (Page 83 of 182) i PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
AUX BLDG FIRE ALERT EVENT POINT 0449 INDICATED CONDITION-o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >I35'F AH-153-TS AH-523-TS AH-524-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O o FIRE DAMPERS FD-52, FD-53, AND FD-54 TRIP o AHF-25A, AHF-25B, AND AHF-25C TRIP IF OPERATING OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-25A/B/C HAVE ACTUATED. AHF-25A/B/C SHOULD SHUTDOWN AUTOMATICALLY.
REFERENCES:
DRAWING 208-005 SHEET AH-061, AH-70, DRAWING 308846 SENSING ELEMENT: AH-153-TS, AH-523-TS, AH-524-TS, AND RELAY 3HBTIA O
AR-401 Rev. II Page 84
i i
l l
ENCLOSURE 1 O
(Page 84 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 r
AUX BLDG FIRE ALERT EVENT POINT 0450 l
INDICATED CONDITION:
I o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135'F AH-155-TS AH-527-TS AH-528-TS l
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-26A, AHF-268, AND AHF-26C TRIP IF OPERATING t
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING SUPPLY FANS j
o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS FOR AHF-25A/B/C HAVE i
ACTUATED. AHF-26A/B/C SHOULD ALSO SHUTDOWN AUTOMATICALLY.
REFERENCES:
DRAWING 208-005 SHEET AH-064, AH-70, DRAWING 308846 SENSING ELEMENT: AH-155-TS, AH-527-TS, AH-528-TS, AND RELAY 3HBT2 AR-401 Rev. 11 Page 85
i ENCLOSURE I O
(Page 85 of 182) i PSA ANNUNCIA10R RESPONSE PSA-X-03-02 F-03-02 l
1 i
AUX BLDG FIRE ALERT l
J 3
)
EVENT POINT 0451 i
i INDICATED CONDITION:
i o ONE OF THE FOLLOWING TEMPERATURE SWITCHES HAS ACTUATED AT >135*F i
AH-155-TS AH-527-TS AH-528-TS j
j i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM-o AHF-26A, AHF-26B, AND AHF-26C TRIP IF OPERATING'
)
)
OPERATOR ACTIONS FOR A VALID ALARM:
\\
1 o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THESE TURBINE BUILDING l
SUPPLY FANS o REFER TO AP-880 DISCUSSION:
THIS ALARM INDICATES THAT THE FIRE DAMPERS BETWEEN THE AUXILIARY BUILDING AND THE TURBINE ROOM HAVE ACTUATED. AHF-26A/B/C SHOULD ALSO SHUTDOWN AUTOMATICALLY.
REFERENCES:
DRAWING 208-005 SHEET AH-067, AH-70, DRAWING 308846 SENSING ELEMENT: AH-154-TS, AH-525-TS, AH-526-TS, AND RELAY 3HBT2 AR-401 Rev. 11 Page 86 I
i ENCLOSURE 1 O
l (Page 86 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT f
EVENT POINT 0455 t
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-386-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-386-CE REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
(
l OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY TURBINE BUILDING OPERATOR TO INVESTIGATE THE FIRE PUMP HOUSE.
\\
DISCUSSION:
~
d
REFERENCES:
DRAWING 208-005 SHEET AH-072 SENSING ELEMENT:
AH-386-CE O
AP-401 Rev. 11 Page 87
}
]
l i
i i
ENCLOSURE 1 (Page 87 of 182) i O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 4
AUX BLDG FIRE ALERT I
EVENT POINT 0500 1
i INDICATED CONDITION:
o PRODUCTS Of COMBUSTION HAVE BEEN DETECTED BY AH-220-CE i
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-220-CE o TEMPERATURE > 135*F AS SENSED BY AH-220-TS EXISTS IN "A" BATTERY 3
CHARGER ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
f o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-42 AND FD-43 OPERATOR ACTIONS FOR A VALID ALARM:
i o REFER TO THE CR3 PRE FIRE PLAN 0 REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE, OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
DRAWING 208-005 SHEET AH-104 SENSING ELEMENT: AH-220-TS, AH-220-CE,
-401 AR Rev. 11 Page 88
i I
ENCLOSURE 1 (Page 88 of 182)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0501 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-217-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUlTS FOR AH-217-CE o TEMPERATURE > 135 F AS SENSED BY AH-217-TS EXISTS IN "B" BATTERY CHARGER ROOM l
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-19 1
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 l
l l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-109, AND DRAWING 308847 SENSING ELEMENT: AH-217-TS, AH-217-CE, AR-401 Rev. 11 Page 89 a
I ENCLOSURE 1 (Page 89 of 182)
,: O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 i
i l
AUX BLDG j
FIRE ALERT i
EVENT POINT 0502 INDICATED CONDITION:
I o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-219-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-219-CE l
o TEMPERATURE > 135*F AS SENSED BY AH-219-TS EXISTS IN "A" BATTERY ROOM
}
I i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-9 AND FD-21 i
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 l
DISCUSSION:
j
REFERENCES:
DRAWING 208-005 SHEETS AH-104, AH-108, DRAWING 308847 SENSING ELEMENT: AH-219-CE, AH-219-TS AR-401 Rev. 11 Page 90 j
.~.\\
i ENCLOSURE 1 (Page 90 of 182)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
r l
AUX BLDG FIRE ALERT i
EVENT POINT 0503 i
l INDICATED CONDITION:
i o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-218-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-218-CE o TEMPERATURE > 135 F AS SENSED BY AH-218-TS EXISTS IN THE "B" BATTERY ROOM l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-220 AND FO-222 OPERATOR ACTIONS FOR A VALID ALARM:
t o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
i THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-108 AND DRAWING 308847 SENSING ELEMENT: AH-218-CE, AH-218-TS AR-401 Rev. 11 Page 91
ENCLOSURE 1 (Page 91 of 182) m PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0504 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-222-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-222-CE o TEMPERATURE > 135'F AS SENSED BY AH-222-TS EXISTS IN THE "A" INVERTER ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-12 AND FD-24 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
~
REFERENCES:
DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847 SENSING ELEMENT: AH-222-CE, AH-222-TS
/m s
AR-401 Rev. Il Page 92
i ENCLOSURE I (Page 92 of 182)
O PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
AUX BLDG 1
FIRE ALERT l
i l
I EVENT POINT 0505 1
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-221-CE
~
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-221-CE i
o TEMPERATURE > 135'F AS SENSED BY AH-221-TS EXISTS IN THE "B" INVERTER ROOM
]
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-11 AND FD-23 1
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN I
]
o REFER TO AP-880 l
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION
~
CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEETS AH-104, AH-109 AND DRAWING 308847 SENSING ELEMENT: AH-221-CE, AH-221-TS AR-401 Rev. 11 Page 93
i i
{
1 ENCLOSURE 1
)
(Page 93 of 182)
I PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 l
~
-i AUX BLDG FIRE ALERT 4
i EVENT POINT 0506 l
1
{
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-235-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-235-CE o TEMPERATURE > 135 F AS SENSED BY AH-235-TS EXISTS IN THE CONTROL COMPLEX STAIR WELL REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-25 l
1 I
i j
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN 1
o REFER TO AP-880 l
i 1
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, A FIRE OR A HIGH TEMPERATURE IN THE ROOM.
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
1
REFERENCES:
DRAWING 208-005 SHEETS AH-105, AH-109 AND DRAWING 308847 i
SENSING ELEMENT: AH-235-CE, AH-235-TS i
AR-401 Rev. 11 Page 94
1 i
l i
ENCLOSURE 1 (Page 94 of 182)
)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 1
AUX BLDG FIRE ALERT J
i l
l EVENT POINT 0513 i
INDICATED CONDITION:
I o TEMPERATURE > 135 F AS SENSED BY AH-132-TS EXISTS IN CLEAN MACHINE SHOP lI AIR HANDLING UNIT AHU-2 DISCHARGE l
I 1
J l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
[
4 o HIGH TEMPERATURE WILL RESULT TRIP 0F AHU,-2 2
i f
4 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN l
0 REFER TO AP-880 5
i O
l DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE DISCHARGE DUCT OF AHU-2.
REFERENCES:
DRAWING 208-005 SHEETS AH-094, DRAWING 308846 SENSING ELEMENT: AH-132-TS 1
]
.I AR-401 Rev. II Page 95
l ENCLOSURE I (Page 95 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-02 F-03-02 AUX BLDG FIRE ALERT EVENT POINT 0514 i
i INDICATED CONDITION:
i o TEMPERATURE > 135'F AS SENSED BY AH-165-TS EXISTS IN HOT MACHINE SHOP AIR HANDLING UNIT AHU-3 DISCHARGE I
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 HIGH TEMPERATURE WILL RESULT TRIP OF AHU-3 i
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 t
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE l
DISCHARGE DUCT OF AHU-3.
^
REFERENCES:
DRAWING 208-005 SHEETS AH-095, DRAWING 308846 SENSING ELEMENT: AH-165-TS O
AR-401 Rev. II-Page 96
ENCLOSURE I (Page 96 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 i
i CNTRL COMPLEX i
g SWGR/DG RM FIRE ALERT l
i EVENT POINT 0443 INDICATED CONDITION:
o TEMPERATURE > 135'F AS SENSED BY AH-125-TS EXISTS IN THE INTAKE PLENUM FOR AHF-16A/16B l
REDUNDANT INDICATION WHICil WILL VERIFY ALARM:
o AHF-16A TRIPS O
o AHF-16B TRIPS OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE INTAKE DUCT OF AHF-16A/AHF-16B.
l
REFERENCES:
DRAWING 208-005 SHEETS AH-058, DRAWING 308846 SENSING ELEMENT: AH-125-TS O
AR-401 Rev. 11 Page 97
ENCLOSURE 1 (Page 97 of 182)
O.
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 0444 i
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-126-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-126-CE o TEMPERATURE > 135 F AS SENSED Bf AH-126-TS EXISTS IN THE RETURN AIR DUCT FROM 119' SWITCH GEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-38, FD-40, FD-48, FD-49, AND FD-50 OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE RETURN AIR DUCT FROM 119' SWITCH GEAR ROOM TO AHF-16A/AHF-16B.
j
REFERENCES:
DRAWING 208-005 SHEETS AH-058, AH-060, AND DRAWING 308846 SENSING ELEMENT: AH-126-TS, AH-126-CE, 3AH-126-TS/RR-HV-V AR-401 Rev. 11 Page 98
)
I
_ - -.. ~..
I ENCLOSURE _1 (Page 98 of 182) l O
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
CNTRL COMPLEX l
SWGR/DG RM FIRE ALERT l
EVENT-POINT 0448 INDICATED CONDITION:
t o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-127-CE l
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-127-CE l
0 TEMPERATURE > 135'F AS SENSED BY AH-127-TS EXISTS IN THF RElURN AIR f
DUCT FROM 95' SWITCH GEAR ROOM l
- )
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM-i O
O THIS ALARM WILL RESULT IN THE ACTUATION OF THE FOLLOWING FIRE DAMPERS FD-39 AND FD-41 l
c t
l OPERATOR ACTIONS FOR A VALID ALARM:
o ENSURE AHF-16A/AHF-16B ARE SHUT DOWN o REFER TO THE PRE FIRE PLAN i
o REFER TO AP-880 l
DISCUSSION:
l l
l THIS CONDITION IS INDICATIVE OF A FIRE OR A HIGH TEMPERATURE IN THE RETURN AIR DUCT FROM 95' SWITCH GEAR ROOM TO AHF-16A/AHF-16B.
i a
i
REFERENCES:
DRAWING 208-005 SHEETS AH-059, AH-060, AND DRAWING 308846 SENSING-ELEMENT: AH-127-TS, AH-127-CE, 3AH-127-TS/RR-HV-V j
1 AR Rev. 11 Page 99
-401
i ENCLOSURE 1 (Page 99 of 182)
I PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
i CNTRL COMPLEX j
---a SWGR/DG RM l
FIRE ALERT EVENT POINT 0460 i
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-364-CE 5
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-364-CE i
c i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AN ALARM ON AH-364-CE WILL ACTUATE FD-36 AND FD-37 OPERATOR ACTIONS FOR A VALID ALARM:
l 0 DEENERGIZE AHF-28A LOCALLY OR VIA ACDP-50 BREAKER 13 o REFER TO THE PRE FIRE PLAN o REFER TO AP-880 i
I l
i i
DISCUSSION:
t THIS CONDITION IS INDICATIVE OF EITHER A TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE EGDG-1A ROOM.
1 1
't
REFERENCES:
DRAWING 208-005 AH-073, AH-076. AND DRAWING 308849 SENSING ELEMENT: AH-364-CE, 3AH-364-CE/ RELAY 4
AR-401 Rev. 11 Page 100
~
ENCLOSURE I (Page 100 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 i
CNTRL COMPLEX i
SWGR/DG RM i
FIRE ALERT l
EVENT POINT 0465 I
INDICATED CONDITION:
l o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-374-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-374-CE i
1 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
e o AN ALARM ON AH-374-CE WILL ACTUATE FD-34 AND FD-35 l
1 OPERATOR ACTIONS FOR A VALID ALARM:
e o DEENERGIZE AHF-288 LOCALLY OR VIA ACDP-50 BREAKER 14 o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
i i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION i
CIRCUITS, OR A FIRE IN THE EGDG-IB ROOM.
a
REFERENCES:
DRAWING 208-005 SHEETS AH-073, AH-079, AND DRAWING 308849 SENSING ELEMENT: AH-374-CE 3AH-374-CE/ RELAY AR-401 Rev. II Page 101
.... ~..
)
ENCLOSURE 1 (Page 101 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 CNTRL COMPLEX SWGR/DG RM FIRE ALERT 1
EVENT POINT 0481 s
INDICATED CONDITION:
a i
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-33-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-33-CE l
4 a
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o AN ALARM ON AH-33-CE WILL ALLOW THE CONTROL COMPLEX VENTILATION SYSTEM l
TO BE PLACED IN A SM0KE REMOVAL MODE OF OPERATION l
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 FIRE PLAN i
o REFER TO AP-880 I
t DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION l
CIRCUITS, OR A FIRE IN THE COMMON RETURN DUCT DOWNSTREAM OF AHF-19A/B
REFERENCES:
DRAWING 208-005 SHEETS AH-090, AH-079, AND DRAWING 308847 SENSING ELEMENT: AH-33-CE, 3AH-33-CE/ RELAY 1
AR-401 Rev. 11 Page 102
i ENCLOSURE 1 (Page 102 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
CNTRL COMPLEX i
SWGR/DG RM FIRE ALERT l
3 EVENT POINT 0492 i
INDICATED CONDITION:
h o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-529-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-529-CE o TEMPERATURE > 135'F AS SENSED BY AH-529-TS EXISTS AT THE 124' LEVEL OF j
THE CONTROL COMPLEX j
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-13 AND FD-84 j
OPERATOR ACTIONS FOR A VALID ALARM:
)
i o REFER TO THE CR3 FIRE PLAN j
l 0 REFER TO AP-880 I
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROVELE IN THE FIRE DETECTION f
CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX t
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-529-TS AH-529-CE, 3AH-529-TS/ RELAY l
t AR-401 Rev. 11 Page 103
4 4
ENCLOSURE 1 (Page 103 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 CNTRL COMPLEX i
SWGR/DG RM FIRE ALERT EVENT POINT 0494 INDICATED CONDITION:
t t
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-214-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-214-CE o TEMPERATURE > 135 F AS SENSED BY AH-214-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "A" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-4 AND FD-16 I
I OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
4 DISCUSSION:
1 THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX j
REFERENCES:
DRAWING 208-005 SHEETS AH-102, AH-107, AND DRAWING 308847 i
SENSING ELEMENT: AH-214-TS AH-214-CE, 3AH-214-TS/ RELAY i
AR-401 Rev. 11 Page 104
ENCLOSURE 1 (Page 104 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 0495 INDICATED CONDITION:
s L
i o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-212-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-212-CE o TEMPERATURE > 135'F AS SENSED BY AH-212-TS EXISTS AT THE 124' LEVEL OF THE CONTROL COMPLEX. ES 480V "B" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l; 0 HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-2 AND FD-14 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
i DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 124' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-102, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-212-TS AH-212-CE, 3AH-212-TS/ RELAY l
AR-401 Rev. 11 Page 105
ENCLOSURE 1 r
(Page 105 of 182)
(3)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 0498 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-216-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-216-CE o TEMPERATURE > 135 F AS SENSED BY AH-216-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "A" SWITCHGEAR ROOM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-6 AND FD-18 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847 SENSING ELEMENT: AH-216-TS AH-216-CE, 3AH-216-TS/ RELAY AR-401 Rev. 11 Page 106
ENCLOSURE 1 g-n (Page 106 of 182)
(
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 i
CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 0499 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-215-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-215-CE o TEMPERATURE > 135*F AS SENSED BY AH-215-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX. ES 4160V "B" SWITCHGEAR ROOM I)
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESUL1 IN THE ACTUATION OF FD-5 AND FD-17 OPECOR ACTIONS FOR A VALID ALARM:
'ER TO THE CR3 PRE FIRE PLAN ncFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-103, AH-107, AND DRAWING 308847
)
SENSING ELEMENT: AH-215-TS AH-215-CE, 3AH-215-TS/ RELAY l
AR-401 Rev. 11 Page 107
ENCLOSURE 1 (Page 107 of 182)
PSA ANNUNCIATOR PESPONSE PSA-X-03-03 F-03-03 1
CNTRL COMPLEX SWGR/DG RM FIRE ALERT i
t EVENT POINT 0507 4
i 3
I
)
INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-236-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-236-CE o TEMPERATURE > 135 F AS SENSED BY AH-236-TS EXISTS AT THE 108' LEVEL OF THE CONTROL COMPLEX REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-26 AND FD-27 l
OPERATOR ACTIONS FOR A VALID ALARM:
l 0 REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 I
J DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 108' ELEVATION OF THE CONTROL COMPLEX l
i i
REFERENCES:
DRAWING 208-005 SHEETS AH-105, AH-109 AND DRAWING 308847 SENSING ELEMENT: AH-236-TS AH-236-CE, 3AH-236-TS/ RELAY 1
l AR-404 Rev. 11 Page 108
i i
i i
1 ENCLOSURE 1 (Page 108 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
2 l
CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 1118 1
l INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-723-CE i
o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-723-CE l
i i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o DETECTION OF PRODUCTS OF COMBUSTION WILL TRIP AHF-49 IF RUNNING 1
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 FRE FIRE PLAN o REFER TO AP-880 1
OISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE INSTRUMENT CAL LAB 145' TURBINE DECK.
l
REFERENCES:
DRAWING 208-005 SHEETS AH-151 AND AH-152 SENSING ELEMENT: AH-723-CE
)
i AR-401 Rev. 11 Page 109
]
1 1
ENCLOSURE 1 (Page 109 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 t
CNTRL COMPLEX SWGR/DG RM i
FIRE ALERT EVENT POINT 1532 l
INDICATED CONDITION:
o TEMPERATURE > 135'F AS SENSED BY AH-534-TS EXISTS IN THE CONTROL COMPLEX MAIN AIR HANDLING SUPPLY DUCT AT 145' ELEVATION t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-56 1
OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 9
DISCUSSION:
I THIS CONDITION IS INDICATIVE OF A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-534-TS, 3AH-534-TS/RR-HV-AU i
AR-401 Rev. 11 Page 110
I 1
~
FNCLOSURE 1 (Page 110 of 182) l 7
i PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 I
CNTRL COMPLEX SWGR/DG RM i
FIRE ALERT l
i EVENT POINT 1533 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-531-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-531-CE
'l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o PRODUCTS OF COMBUSTION DETECTION WILL RESULT IN THE ACTUATION OF FD-51 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE OUTSIDE AIR INTAKE OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-531-CE l
AR-401 Rev. 11 Page 111
ENCLOSURE 1 (Page 111 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 l
CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT POINT 1534 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-535-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-535-CE o TEMPERATURE > 135'F AS SENSED BY AH-535-TS EXISTS IN THE CONTROL l
COMPLEX MAIN SUPPLY DUCT 95' ELEVATION t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-55 OPERATOR ACTIONS FOR A VALID ALARM:
l 0 REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 l
l DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE MAIN SUPPLY DUCT OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847 SENSING ELEMENT: AH-535-TS AH-535-CE, 3AH-535-TS/ RELAY AR-401 Rev. 11 Page 112
ENCLOSURE 1 (Page 112 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 CNTRL COMPLEX SWGR/DG RM FIRE ALERT EVENT P0 INT 1535 INDICATED CONDITION:
o TEMPERATURE > 135 F AS SENSED BY AH-533-TS EXISTS IN THE CONTROL COMPLEX MAIN RETURN AIR DUCT AT 145' ELEVATION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF FD-57 OPERATOR ACTIONS FOR A VALID ALARM:
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 DISCUSSION:
THIS CONDITION IS INDICATIVE OF A FIRE IN THE RETURN AIR DUCT OF THE CONTROL COMPLEX.
REFERENCES:
DRAWING 208-005 SHEETS AH-101, AH-106, AND DRAWING 308847
(_J SENSING ELEMENT: AH-533-TS, 3AH-533-TS/RR-HV-AT AR-401 Rev. 11 Page 113
s ENCLOSURE 1 (Page 113 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-03 F-03-03 i
CNTRL COMPLEX l
SWGR/DG RM FIRE ALERT EVENT POINT 1536 INDICATED CONDITION:
o PRODUCTS OF COMBUSTION HAVE BEEN DETECTED BY AH-211-CE o TROUBLE HAS BEEN DETECTED IN THE CIRCUITS FOR AH-211-CE o TEMPERATURE > 135*F AS SENSED BY AH-211-TS EXISTS AT THE 134' LEVEL 0F THE CONTROL COMPLEX REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH TEMPERATURE WILL RESULT IN THE ACTUATION OF THE FOLLOWING:
FD-45, FD-46, FD-47, FD-81, FD-82, AND FD-83 OPERATOR ACTIONS FOR A VALID ALARM:
i 4
o REFER TO THE CR3 PRE FIRE PLAN o REFER TO AP-880 i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF EITHER TROUBLE IN THE FIRE DETECTION CIRCUITS, OR A FIRE IN THE 134' ELEVATION OF THE CONTROL COMPLEX IN THE CABLE SPREADING ROOM.
REFERENCES:
DRAWING 208-005 SHEETS AH-105, AH-107, AND DRAWING 308847 SENSING ELEMENT: AH-211-TS AH-211-CE, 3AH-211-TS/ RELAY AR-401 Rev. 11 Page 114
i ENCLOSURE I i
(Page 114 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-03-04 F-03-04 FIRE 1
SYSTEM TROUBLE i
EVENT POINT 0197 i
- l INDICATED CONDITION:
j o FIRE SERVICE PANEL IN THE CONTROL ROOM HAS AN UNACKNOWLEDGED OR UNRESET ALARM REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o ALARM ON THE FIRE SERVICE PANEL OR ONE OF THE PYROTRONICS PANELS O
OPERATOR ACTIONS FOR A VALID ALARM:
o IMMEDIATE INVESTIGATION OF ALARM CAUSE SHOULD BE INITIATED l
?
i DISCUSSION:
REFER TO THE CR3 FIRE PROTECTION PLAN FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-031 SHEET FS-21 SENSING ELEMENT:
- !O AR-401 Rev. 11 Page 115
. ~.
\\
)
ENCLOSURE 1 (Page 115 of 182)
O 1
PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 REACTOR BLDG PURGE FAN i
TRIP i
EVENT POINT 0384 INDICATED CONDITION:
o AHF-7A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-7A CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE RB PURGE o REFER TO OP-417 DISCUSSION:
THIS CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT INDICATED BY EVENT POINT 0387, OR AN FSV-Il4 DELUGE VALVE ACTUATION t
REFERENCES:
DRAWING 208-005 SHEETS AH-022, AH-015 SENSING ELEMENT: CS/SC, CS/0, 42/49B RELAY i
l AR-401 Rev. 11 Page 116
ENCLOSURE 1 (Page 116 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-01 F-04-01 REACTOR BLDG PURGE FAN TRIP EVENT POINT 0385 INDICATED CONDITION:
o AHF-78 MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-7B CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE RB PURGE o REFER TO OP-417 DISCUSSION:
THIS CONDITION MAY BE CAUSED BY ACTUATION OF A FIRE ALERT IN THE DUCT INDICATED BY EVENT POINT 0387, OR AN FSV-114 DELUGE VALVE ACTUATION
REFERENCES:
DRAWING 208-005 SHEETS AH-023, AH-015 SENSING ELEMENT:
CS/SC, CS/0, 42/49B RELAY O
AR-401 Rev. 11 Page 117
J i
ENCLOSURE I (Page 117 of 182)
)
l PSA ANNUNCIATOR RESPONSE PSA-X-04-02 F-04-02 l
AH FLTR 1 DIFF PRESS l
HIGH EVENT POINT 0497 INDICATED CONDITION:
i o DIFFERENTIAL PRESS ACROSS AHFL-1 IS > 5.2 "H O AS' SENSED BY 2
AH-586A-PS, OR AH-586B-PS l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH FLOW INDICATED ON AH-32-FIR f
O
- 'oca' oirreat" 1^' eaessuae 1"oica11ous ou ^a-s88-oei OPERATOR ACTIONS FOR A VALID ALARM:
l 0 REDUCE RB PURGE FLOW RATE o REFER TO OP-417 i
I DISCUSSION:
THIS CONDITION IS INDICATIVE OF EXCESSIVE FLOW THROUGH THE PURGE EXHAUST FILTERS.
REFERENCES:
DRAWING 308848 SENSING ELEMENT: AH-586A-DPS, AH-586B-PS o
AR-401 Rev. 11 Page 118 J
'T ENCLOSURE I (Page 118 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 l
REACTOR BLDG I
MISC CLG FANS TRIP i
EVENT POINT 0360 INDICATED CONDITION:
1 I
o AHF-2A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION l
l I
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
j o GREEN LIGHT ON WITH A RED FLAG ON AHF-2A CONTROL STATION r
OPERATOR ACTIONS FOR A VALID ALARM:
[
o SWAP REACTOR CAVITY COOLING TO "B" SIDE PER OP-409 o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409 t
i J
DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
i I
f
REFERENCES:
DRAWINGS 208-005-AH-031, 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY i
AR-401 Rev. 11 Page 119 i
i 1
4 i
4' ENCLOSURE 1 (Page 119 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 i
l 1
i REACTOR BLDG l
MISC CLG FANS TRIP l
EVENT POINT 0362 i
INDICATED CONDITION:
i o AHF-2B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
j t
o -GREEN LIGHT ON WITH A RED FLAG ON'AHF-2B CONTROL STATION i
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING TO "A" SIDE PER OP-409 f
o MONITOR REACTOR CAVITY TEMPS ON AH-1003-TIR PER OP-409
\\
DISCUSSION:
i A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWINGS 208-005-AH-033, 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 11 Page 120
J 4
ENCLOSURE 1 (Page 120 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG t
MISC CLG FANS l
TRIP EVENT POINT 0365 INDICATED CONDITION:
i o AHF-3A MOTOR NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION l
l i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
^
o GREEN LIGHT ON WITH A RED FLAG ON AHF-3A CONTROL STATION i
OPERATOR ACTIONS FOR A VALID ALARM:
}
o ENSURE AHF-3B IS OPERATING o REFER TO OP-409 i
DISCUSSION:
i
REFERENCES:
DRAWINGS 208-005-AH-036, 308848 SENSING ELEMENT:
CS/SC, CS/0, 42B RELAY i
(
AR-401 Rev. 11 Page 121 L
1 ENCLOSURE 1 1
(Page 121 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03
)
i 1
i REACTOR BLDG
)j g
MISC CLG FANS i
l TRIP 1
EVENT POINT 0368 1
l INDICATED CONDITION:
4 o AHF-3B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER l
START POSITION l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
j o GREEN LIGHT ON WITH A RED FLAG ON AHF-3B CONTROL STATION i
f OPERATOR ACTIONS FOR A VALID ALARM:
t l
o START AHF-3A o TRANSFER PyA-6 SUCTION TO AHF-3A REFER TO OP-417 1
I i
DISCUSSION:
4 i
RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF AHF-3B OR THE DUCT OF AHF-3A DEPENDING ON WHICH IS IN OPERATION THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPERATION. REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
l l
1
REFERENCES:
DRAWINGS 208-005-AH-036, 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY i
O i
i AR-401 Rev. 11 Page 122 j
ENCLOSURE 1 (Page 122 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 I
i REACTOR BLDG MISC CLG FANS TRIP f
EVENT POINT 0371 INDICATED CONDITION:
o AHF-4A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-4A CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
I o START AHF-4B o REFER TO OP-409 1
DISCUSSION:
REFERENCES:
DRAWINGS 208-005-AH-038, 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 11 Page 123 i
-. ~
. J
Ef.! CLOSURE 1 (Page 123 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0373 INDICATED CONDITION:
i o AHF-4B MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o GREEN LIGHT ON WITH A RED FLAG ON AHF-4B CONTROL STATION O
i OPERATOR ACTIONS FOR A VALID ALARM:
[
o R
bP 409 f
i r
i i
DISCUSSION:
i
REFERENCES:
DRAWINGS 208-005-AH-040, 308848
)
SENSING ELEMENT: CS/SC, CS/0, 42B RELAY i
O i
AR-401 Rev. 11 Page 124
ENCLOSURE I (Page 124 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG
~
MISC CLG FANS TRIP
[
]
EVENT POINT 0378 INDICATED CONDITION:
o AHF-6A MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER f
START POSITION f-REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-6A CONTROL STATION O
o LOSS OF RB PURGE FLOW AS READ ON AH-32-FIR OPERATOR ACTIONS FOR A VALID ALARM:
f o START AHF-6B o REESTABLISH RB PURGE IF REQUIRED o REFER TO OP-409 i
F DISCUSSION:
ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB PURGE, SOME OF THE THINGS THAT WILL CAUSE THE PURGE SUPPLY FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-7B, ACTUATION OF FIRE ALERT EVENT POINT 0380
REFERENCES:
DRAWINGS 208-005 SHEETS AH-015, AH-20, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY l
i AR-401 Rev. 11 Page 125 f
,~.-g-
-, - ~.,.,...,,
ENCLOSURE 1 (Page 125 of 182)
O PSA ANNUNCIATOR RESPONSE PSA-X-04-03 F-04-03 REACTOR BLDG MISC CLG FANS TRIP EVENT POINT 0379 INDICATED CONDITION:
o AHF-GB MOTOR IS NOT ENERGIZED WITH THE CONTROL HANDLE IN NORMAL AFTER START POSITION i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-6B CONTROL STATION O
o LOSS OF RB PURGE FLOW AS READ ON AH-32-FIR OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-6A o REESTABLISH RB PURGE IF REQUIRED o REFER TO OP-409 DISCUSSION:
ONLY ONE PURGE SUPPLY FAN IS REQUIRED FOR ESTABLISHING AN RB ? URGE, SOME OF THE THINGS THAT WILL CAUSE THE PURGE SUPPLY ~ FAN TO TRIP ARE A LOSS OF EITHER OF THE PURGE EXHAUST FANS AHF-7A/AHF-7B, ACTUATION OF FIRE ALERT EVENT POINT 0380
REFERENCES:
DRAWINGS 208-005 SHEETS AH-015, AH-21, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY O
AR-401 Rev. 11 Page 126 1.
9 ENCLOSURE 1
,r (Page 126 of 182)
C PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0364 INDICATED CCNCITION:
o AHF-2A AND/OR AHF-2B CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFF. PRESS. <0.25" ilz0 EXISTS AS SENSED BY AH-10-DPS AND/0R AH-532-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o CLOSED INDICATION OF AHD-1A
((
o CLOSED INDICATION ON AHD-1B OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP REACTOR CAVITY COOLING PER OP-409 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 i
DISCUSSION:
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY COULD HAVE ADVERSE I
EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
IF FLOW CANNOT BE RESTORED THEN CONSIDERATION SHOULD BE GIVEN TO SHUTTING DOWN THE PLANT.
j
REFERENCES:
DRAWINGS 208-005 SHEET AH-032, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 423 RELAY, AH-10-DPS, AH-532-DPS AR-401 Rev. 11 Page 127
ENCLOSURE 1 (Page 127 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 REACTOR BLDG MISC AIR FLOW LOW EVENT POINT 0366 i
INDICATED CONDITION:
f o AHF-3A CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H,0 EXISTS AS SENSED BY AH-13-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
d o INCREASING RB TEMPERATURES i
i l
OPERATOR ACTIONS FOR A VALID ALARM:
l i
o START AHF-3B o REFER TO OP-409 o MONITOR RB TEMPS I
DISCUSSION:
LOSS OF THIS AIR SUPPLY FAN WILL CAUSE RB TEMPERATURES TO INCREASE IN PLACES DUE TO A LACK OF MIXING FLOW.
l
REFERENCES:
DRAWINGS 208-005 SHEET AH-037, DRAWING 308848 l
SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-13-DPS O
I W
AR-401 Rev. 11 Page 128
f I
ENCLOSURE I (Page 128 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 l
REACTOR BLDG i
MISC AIR FLOW LOW s
EVENT POINT 0369 INDICATED CONDITION:
h o AHF-38 CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <0.25" H 02 EXISTS AS SENSED BY AH-15-DPS l
z REDUNDANT INDICATION WHICH UILL VERIFY ALARM:
o INCREASING RB TEMPERA 7URES O
OPERATOR ACTIONS FOR A VALID ALARM:
j o START AHF-3A o TRANSFER RMA-6 SUCTION TO AHF-3A REFER TO OP-417 i
DISCUSSION RM-A6 MONITORS THE REACTOR BUILDING ATMOSPHERE VIA EITHER THE DUCT OF i
AHF-3B OR THE DUCT OF AHF-3A DEPENDING ON WHICH IS IN OPERATION THE TRANSFER OF THE SAMPLE POINT PER OP-417 IS A MANUAL OPERATION. REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
l
REFERENCES:
DRAWINGS 208-005 SHEET AH-037, DRAWING 308848 SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-13-DPS l
)
l AR-401 Rev. 11 Page 129
i ENCLOSURE 1 (Page 129 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-04 F-04-04 i
l REACTOR BLDG i
MISC AIR FLOW t
LOW EVENT POINT 0375 INDICATED CONDITION:
o AHF-4A OR AHF-4B CONTROL HANDLE IN NORMAL AFTER START AND A LOW DIFFERENTIAL PRESSURE <.234" H O EXISTS AS SENSED BY AH-7-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o INCREASING RB TEMPERATURES i
j OPERATOR ACTIONS FOR A VALID ALARM:
f o START AHF-4A OR 4B AS REQUIRED o REFER TO OP-409 O MONITOR RB TEMPS DISCUSSION:
1 j
LOSS OF THE SG COOLING FANS WILL CAUSE SOME AREAS OF THE RB TO INCREASE l
DUE TO LACK OF MIXING FLOW.
4 REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWINGS 208-005 SHEET AH-038, DRAWING 308848 l
SENSING ELEMENT: CS/SC, CS/0, 42B RELAY, AH-7-DPS
- O i
4 AR-401 Rev. 11 Page 130
ENCLOSURE 1 (Page 130 of 182)
'v PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VIBRATION HIGH EVENT POINT 0361 INDICATED CONDITION:
o AH-ll-ME HAS ACTUATED DUE TO AHF-2A VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTIONS FOR A VALID AI. ARM:
o SECURE AHF-2A o SWAP REACTOR CAVITY CDCLING TO "B" SIDE PER OP-409 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-005 SHEET AH-133 SENSING ELEMENT: AH-ll-ME AR-401 Rev. Il Page 131
ENCLOSURJ_1 r~'
(Page 131 of 182)
(
PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VIBRATION HIGH EVENT POINT 0363 INDICATED CONDITION:
o AH-12-ME HAS ACTUATED DUE TO AHF-2B VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o NONE OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-2B o SWAP REACTOR CAVITY COOLING T0 "A" SIDE PER OP-409 o MONITOR REACTOR CAVITY TEMPERATURES ON AH-1003-TIR PER OP-409 DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
A SUSTAINED LOSS OF COOLING TO THE REACTOR CAVITY WILL HAVE ADVERSE EFFECTS ON THE RELIABILITY OF THE NUCLEAR INSTRUMENTATION.
REFERENCES:
DRAWING 208-005 SHEET AH-133 SENSING ELEMENT: AH-12-ME i
AR-401 Rev. 11 Page 132
l a
l i
ENCLOSURE 1 i
(Page 132 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 i
i REACTOR BLDG l
FAN VIBRATION HIGH EVENT POINT 0367 i
INDICATED CONDITION:
o AH-14-ME HAS ACTUATED DUE TO AHF-3A VIBRATION IN EXCESS OF SETPOINT AS 4
l DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o i
i OPERATOR ACTIONS FOR A VALID ALARM:
t l
0 SECURE AHF-3A j
0 ENSURE AHF-3B IS IN OPERATION j
i f
I DISCUSSION:
j THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN i
DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE l
REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO l
INVESTIGATE / REPAIR THE PROBLEM.
t
REFERENCES:
DRAWING 208-005 SHEET AH-133 SENSING ELEMENT: AH-14-ME l
O AR-401 Rev. 11 Page 133
ENCLOSURE 1 (Page 133 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VIBRATION HIGH EVENT POINT 0370 INDICATED CONDITION:
o AH-16-ME HAS ACTUATED DUE TO AHF-38 VIBRATION IN EXCESS OF SETPOINT AS DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-38 o START AHF-3A o TRANSFER RMA-6 SUCTION TO AHF-3A REFER TO OP-417 DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
REFERENCES:
DRAWING 208-005 SHEET AH-134 SENSING ELEMENT: AH-16-ME O
AR-401 Rev. Il Page.134
I I
i ENCLOSURE 1 i
(Page 134 of 182)
)
i PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 I
REACTOR BLDG FAN VIBRATION ZZZ ZZ HIGH EVENT POINT 0372 INDICATED CONDITION:
i o AH-8-ME HAS ACTUATED DUE TO AHF-4A VIBRATION IN EXCESS OF SETPOINT AS l
DETERMINED BY PM-294 i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
O OPEPX OR ACTIONS FOR A VALID ALARM:
o SECURE AHF-4A o START AHF-4B I
I I
i DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1 0 G HAS BEEN t
DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO l
INVESTIGATE / REPAIR THE PROBLEM.
i i
REFERENCES:
DRAWING 208-005 SHEET AH-134 j
l SENSING ELEMENT: AH-8-ME O
l 4
i i
AR-401 Rev. 11 Page 135
ENCLOSURE I (Page 135 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-05 F-04-05 REACTOR BLDG FAN VIBRATION HIGH EVENT POINT 0374 INDICATED CONDITION:
o AH-9-ME HAS ACTUATED DUE TO AHF-4B VIBRATION IN EXCESS OF SETPOINT AS i
DETERMINED BY PM-294 REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o OPERATOR ACTIONS FOR A VALID ALARM:
i i
o SECURE AHF-4B o START AHF-4A j
DISCUSSION:
THIS CONDITION INDICATES THAT A VIBRATION IN EXCESS OF 1.0 G HAS BEEN DETECTED. THERE IS NO WAY TO MONITOR THE VIBRATION FROM OUTSIDE THE i
REACTOR BUILDING, THEREFORE IT WILL REQUIRE A REACTOR BUILDING ENTRY TO INVESTIGATE / REPAIR THE PROBLEM.
l
~
REFERENCES:
DRAWING 208-005 SHEET AH-134 SENSING ELEMENT: AH-9-ME i O AR 401 Rev. 11 Page 136 l
i ENCLOSURE 1 I
(Page 136 of 182)
O H
PSA ANNUNCIATOR RESPONSE PSA-X-04-07 F-04-07 REACTOR BLDG PURGE AIR FLOW LOW i
EVENT POINT 0381 I
INDICATED CONDITION:
o DIFFERENTIAL PRESSURE ACROSS AH-1-DPS IS < 0.048" H 0 WITH AHF-6A AND/0R AHF-6BCONTROLHANDLEINNORMALAFTERSTARTPOSIT10fi REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHV-ID CLOSES O
OPERATOR ACTIONS FOR A VALID ALARM:
o DETERMINE THE CAUSE FOR THE LOW PURGE SUPPLY FLOW, AND ADJUST THE RECIRC FLOW DAMPER CONTROL TO REESTABLISH FLOW THROUGH THE OUCT DISCUSSION:
i l
~
[
REFERENCES:
DRAWING 208-005 SHEET 20, AND DRAWING 308848 SENSING ELEMENT: AHF-6A CS/SC, CS/0, AHF-6B CS/SC, CS/0, AH-I-DPS O
l 2
l AR-401 Rev. 11 Page 137
ENCLOSURE I (Page 137 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-07 F-04-07 REACTOR BLDG PURGE AIR FLOW LOW t
I EVENT POINT 0386 l
INDICATED CONDITION:
~
o DIFFERENTIAL PRESSURE ACROSS AH-296-DPS IS < 0.29" H 0 WITH AHF-7A AND/ORAHF-7BCONTROLHANDLEINNORMALAFTERSTARTPbSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l 0 LOW FLOW INDICATION ON AH-32-FIR POINT NUMBER 4 O
i l
OPERATOR ACTIONS FOR A VALID ALARM.
o DETERMINE THE CAUSE FOR THE LOW PURGE EXHAUST FLOW, AND CORRECT IF POSSIBLE i
DISCUSSION:
THIS CONDITION IS INDICATIVE OF A LOSS OF INTEGRITY IN THE DUCT WORK-AND SHOULD BE INVESTIGATED AS S00N AS POSSIBLE.
REFERENCES:
DRAWING 208-005 SHEET 22, AND DRAWING 308848 SENSING ELEMENT: AHF-7A CS/SC, CS/0, AHF-7B CS/SC, CS/0, AH-296-DPS I
AR-401 Rev. II Page 138
ENCLOSURE 1 (Page 138 of 182) l PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 l
I l
l l
CRDM SHROUD 1
l COOLING FANS I
I TRIP I
I 22 2
EVENT POINT 1224 1
INDICATED CONDITION:
o BREAKER IN UNIT 30 0F VENT MCC 3B IS OPEN
{
o 42/12CR RELAY FOR THIS CIRCUIT IS DEENERGIZED l
o AHF-51B, AHF-51F, AND AHF-5IJ ARE NOT RUNNING l
'l J
j REDUNDANT INDICATION WHICH WILL VERIFY. ALARM:
o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 3D 3
o LOCAL BREAKER POSITION I
OPERATOR ACTIONS FOR A VALID ALARM:
i o MONITOR CRDM STATOR TEMPS 4
o NOTIFY ELECTRICAL MAINTENANCE I
i 1
l 1
DISCUSSION:
i i
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE l
SHROUD FANS POWERED FROM THIS BREAKER.
ELECTRICAL-MAINTENANCE WILL i
DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINING FANS TO BE i
RUN.
1
REFERENCES:
DRAWING 208-005 SHEET AH-159 SENSING ELEMENT: 42/12CR RELAY O
1 9
AR-401 Rev. 11 Page 139
ENCLOSURE 1 (Page 139 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 l
l l
l CRDM SHROUD j
i l
COOLING FANS I
I TRIP l
l l
22 EVENT POINT 1225 I
INDICATED CONDITION:
o BREAKER IN UNIT 8A 0F VENT MCC 3B IS OPEN o 42/34CR RELAY FOR THIS CIRCUIT IS DEENERGIZED o AHF-51C, AHF-51G, AND AHF-51K ARE NOT RUNNING 4
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 8A o LOCAL BREAKER POSITION t
I OPERATOR ACTIONS FOR A VALID ALARM:
o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE i
DISCUSSION:
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER.
ELECTRICAL MAINTENANCE WILL I
DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINING FANS TO BE RUN.
REFERENCES:
ORAWING 208-005 SHEET AH-160 j
SENSING ELEMENT:
42/34CR RELAY I
t AR-401 Rev. 11 Page 140
ENCLOSURE 1 (Page 140 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04-08 i
l I
4 I
i CRDM SHROUD l
I I
I l
COOLING FANS i
I I
TRIP i
1 2
2 EVENT POINT 1226 l
I INDICATED CONDITION:
o BREAKER IN UNIT 10D OF VENT MCC 3B IS OPEN o 42/42CR RELAY FOR THIS CIRCUIT IS DEENERGIZED o AHF-51D, AHF-51H, AND AHF-51L ARE NOT RUNNING l
l REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o GREEN INDICATOR LIGHT ON VENT MCC 3B CUBICLE 10D o LOCAL BREAKER POSITION l
OPERATOR ACTIONS FOR A VALID ALARM:
t o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE i
DISCUSSION:
THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE SHROUD FANS POWERED FROM THIS BREAKER.
ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINDER TO BE RUN.
REFERENCES:
DRAWING 208-035 SHEET AH-161 SENSING ELEMENT: 42/42CR RELAY O
AR Rev. 11 Page 141
-401..
ENCLOSURE 1 (Page 141 of 182)
PSA ANNUNCIATOR RESPONSE PSA-X-04-08 F-04 ;
I I
l l
CRDM SHROUD l
l COOLING FANS I
I TRIP l
I 2
EVENT POINT 1229 INDICATED CONDITION:
o BREAKER IN UNIT 8A 0F VENT MCC 3A IS OPEN o 42/32CR RELAY FOR THIS CIRCUIT IS DEENERGIZED o AHF-51A, AHF-51E, AND AHF-51I ARE NOT RUNNING
~
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN INDICATOR LIGHT ON VENT MCC 3A CUBICLE SA o LOCAL BREAKER POSITION f
OPERATOR ACTIONS FOR A VALID ALARM:
o MONITOR CRDM STATOR TEMPS o NOTIFY ELECTRICAL MAINTENANCE f
DISCUSSION:
f THIS ALARM IS INDICATIVE OF AN OVERLOAD CONDITION ON ONE OR MORE OF THE l
SHROUD FANS POWERED FROM THIS BREAKER. ELECTRICAL MAINTENANCE WILL DETERM THE FAN (S) THAT ARE SHORTED TO ENABLE THE REMAINDER TO BE RUN.
REFERENCES:
DRAWING 208-005 SHEET AH-158 l
SENSING ELEMENT: 42/32 CR RELAY O
i l
AR-401 Rev. 11 Page 142
1 ENCLOSURE 1 (Page 142 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 l
W
\\
i l
AUX BLDG l
EXHAUST FAN I
TRIP i
l l
t I
EVENT POINT 0417 i
l INDICATED CONDITION:
I o AHF-14A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START l
POSITION i
~
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-14A CONTROL STATION l
O o AHF-10, AHF-11A, AHF-11B TRIP, IF RUNNING f
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14C, START AHF-14B AND AHF-140 PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP
~
DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-112 WILL TRIP THIS i
FAN. THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
l WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN l
THIS FAN TRIPS.
l REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-01 i
SENSING ELEMENT:
CONTROL STATION AND BREAKER CONTACTS O
I AR-401 Rev. 11 Page 143
ENCLOSURE 1 (Page 143 of 182) q)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 i
AUX BLDG EXHAUST FAN TRIP EVENT POINT 0419 INDICATED CONDITION:
o AHF-14B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-14B CONTROL STATION
(,^)
AHF-10, AHF-11A, AHF-llB TRIP, IF RUNNING o
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14D, START AHF-14A AND AHF-14C PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-110 WILL TRIP THIS FAN. WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH 02 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS e
AR-401 Rev. 11 Page 144 i
ENCLOSURE 1 (Page 144 of 182) p C/
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG EXHAUST FAN TRIP EVENT POINT 0421 INDICATED CONDITION:
o AHF-14C BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
gm o GREEN LIGHT WITH A RED FLAG ON AHF-14C CONTROL STATION d
o AHF-IIA, AHF-llB, AHF-10 TRIP, IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14A, START AHF-148 AND AHF-14D o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-116 WILL TRIP THIS FAN THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
i WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
j i
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
j i
REFERENCES:
DRAWING 208-005 SHEET AH-03 SENSING ELEMENT:
CONTROL STATION AND BREAKER CONTACTS O
AR 401 Rev. Il Page 145
ENCLOSURE 1 (Page 145 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-01 F-05-01 AUX BLDG EXHAUST FAN TRIP EVENT POINT 0423 INDICATED CONDITION:
o AHF-14D BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-14D CONTROL STATION o AHF-10, AHF-11A, AHF-llB TRIP, IF RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14B, START AHF-14A AND AHF-14C o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
AUX BLDG EXHAUST FILTER DELUGE VALVE ACTUATION, FSV-118 WILL TRIP THIS FAN THE SUCTION AND DISCHARGE DAMPER POSITION CONTACTS THAT FEED THE FAN RUN INTERLOCK STRING ARE DIFFERENT FROM THE CONTACTS THAT SUPPLY INDICATION ON THE HVAC PANEL.
WASTE GAS DECAY TANK OUTLET VALVES, WDV-436, 437, 438 WILL CLOSE WHEN THIS FAN TRIPS.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-04 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS LJ AR-401 Rev. 11 Page 146
ENCLOSURE 1 i
(Page 146 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 AUX BLDG EXHAUST FAN OVERLOAD P
EVENT POINT 0418 i
INDICATED CONDITION:
o AHF-14A MOTOR AMPS >115Y. RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
{
l o AHF-14A TRIPS O
o AHF-14A HIGH MOTOR AMPS INDICATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14A AND AHF-14C, START AHF-14B AND AHF-14D AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP l
DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS,
REFERENCES:
DRAWING 208-005 SHEET AH-01 SENSING ELEMENT: 74-AHF-14A O
AR-401 Rev. 11 Page 147
. J
I l
t ENCLOSURE 1 (Page 147 of 182) l O
I PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-OS-02 i
j AUX BLDG l
EXHAUST FAN OVERLOAD EVENT POINT 0420 1
INDICATED CONDITION:
l o AHF-14B MOTOR AMPS >115% RATED LOAD i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
}
i o AHF-14B TRIPS I
o AHF-14B HIGH MOTOR AMPS INDICATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14B AND AHF-140, START AHF-14A AND AHF-14C AND RESTORE AUX l
i BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP f
f f
DISCUSSION:
l I
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS j
OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANE0US OVERCURRENT l
PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
l REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
l
REFERENCES:
DRAWINS 208-005 SHEET AH-02 t
SENSING ELEMENT: 74-AHF-14B
~
i O l
-l AR-401 Rev. 11 Page.148,
-.,. - l
ENCLOSURE 1 (Page 148 of 182) 7(
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 AUX BLDG EXHAUST FAN OVERLOAD EVENT POINT 0422 INDICATED CONDITION:
o AHF-14C MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
s o AHF-14C TRIPS o AHF-14C HIGH MOTOR AMPS INDICATED ON HVAC PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14A AND AHF-14C, START AHF-14B AND AHF-14D AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANEOUS OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED.
INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-03 SENSING ELEMENT:
74-AHF-14C l
O AR-401 Rev. Il Page 149
ENCLOSURE 1 (Page 149 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-02 F-05-02 AUX BLDG EXHAUST FAN OVERLOAD EVENT POINT 0424 INDICATED CONDITION:
o AHF-14D MOTOR AMPS >115% RATED LOAD REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHF-14D TRIPS
(-]
o AHF-14D HIGH MOTOR AMPS INDICATED ON HVAC PANEL v
OPERATOR ACTIONS FOR A VALID ALARM:
o SECURE AHF-14B AND AHF-14D, START AHF-14A AND AHF-14C AND RESTORE AUX BUILDING VENTILATION AS REQUIRED PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP l
i DISCUSSION:
THIS ALARM INDICATES THAT EITHER THE TIMED OVERCURRENT OR INSTANTANE0US OVERCURRENT PROTECTIVE DEVICES HAVE ACTUATED. INSTANTANEOUS OVERCURRENT PROTECTIVE RELAY ACTUATION WILL TRIP THE BREAKER.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-04 SENSING ELEMENT: 74-AHF-14D AR-401 Rev. 11 Page 150
ENCLOSURE 1 (Page 150 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 I
AB FLTR 2A/B/C/D AP HIGH EVENT POINT 1552 INDICATED CONDITION:
o AUX BUILDING EXHAUST FILTER, AHFL-2A, FLOW IS >5.2" H O AS SENSED BY 2
AH-601-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHFL-2A LOCAL DIFFERENTIAL PRESSURE INDICATOR
,e
'w)
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-601-DPS LJ AR-401 Rev. 11 Page 151
1 1
ENCLOSURE 1 (Page 151 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 i
AB FLTR 2A/B/C/D AP HIGH EVENT POINT 1553 l
INDICATED CONDITION:
AUX BUILDING EXHAUST FILTER, AHFL-2B, FLOW IS >5.2" H,0 AS SENSED BY o
AH-602-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHFL-2B LOCAL DIFFERENTIAL PRESSURE INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER l
i DISCUSSION:
GPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
)
REFERENCES:
DPAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-602-DPS O
AR-401 Rev. 11 Page 152-
l ENCLOSURE 1 t'
(Page 152 of 182)
'x ]/
m PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 AB FLTR 2A/B/C/D AP HIGH EVENT POINT 1688 INDICATED CONDITION:
o AUX BUILDING EXHAUST FILTER, AHFL-2C, FLOW IS >5.2" H 0 AS SENSED BY g
AH-603-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
/~
o AHFL-2C LOCAL DIFFERENTIAL PRESSURE INDICATOR
(>]
OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER.
DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING EXHAUST FILTERS IS PERMITTED.
REFERENCES:
DRAWING 208-005 SHEET AH-131 SENSING ELEMENT:
AH-603-DPS AR-401 Rev. Il Page 153
ENCLOSURE 1 (Page 153 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-03 F-05-03 l
AB FLTR 2A/B/C/D AP HIGH EVENT POINT 1689 I
INDICATED CONDITION:
o AUX BUILDING EXHAUST FILTER, AHFL-2D, FLOW IS >5.2" H O AS SENSED BY 2
AH-604-DPS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o AHFL-2D LOCAL DIFFERENTIAL PRESSURE INDICATOR OPERATOR ACTIONS FOR A VALID ALARM:
o NOTIFY HVAC TO INSPECT FILTER l
i DISCUSSION:
OPERATION OF AUXILIARY BUILDING EXHAUST FANS WITH ONLY THREE AUX BUILDING l
EXHAUST FILTERS IS PERMITTED.
1 l
l
REFERENCES:
DRAWING 208-005 SHEET AH-131 SENSING ELEMENT: AH-604-DPS 1
AR-401 Rev. 11 Page 154
ENCLOSURE 1 (Page 154 of 182) l O
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-04 F-05-04 l
PENETRATION AIR FLOW TRCUBLE l
l i
EVENT POINT 0438 i
INDICATED CONDITION:
J i
l PENETRATION COOLING AIR FLOW IS <0.018" H 0 AS SENSED BY AH-30-DPS o
WITHEITHERAHF-9AORAHF-98CONTROLSTATiONINNORMALAFTERSTART l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
[
0 LOCAL DIFFERENTIAL FLOW INDICATION l
l 1
i OPERATOR ACTIONS FOR A VALID ALARM:
o START BACKUP PENETRATION COOLING FAN o REFER TO OP-409
[
DISCUSSION:
i L
f
REFERENCES:
DRAWING 208-005 SHEET AH-56 i
SENSING ELEMENT: AH-30-DPS i
O l
i i
l AR-401 Rev. 11 Page 155
i l
}
ENCLOSURE 1 (Page 155 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 l
i
?
FIRE PP HOUSE FAN ZZZZ Z
TROUBLE EVENT POINT 0454 i
i INDICATED CONDITION:
i FIRE PUMP HOUSE VENTILATION AIR FLOW IS <0.25" H 0 AS SENSED BY EITHER o
AH-168-DPSANDAHF-33AISRUNNINGORBYAH-173-Dh5ANDAHF-33BRUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL DIFFERENTIAL FLOW INDICATION OPERATOR ACTIONS FOR A VALID ALARM:
s o START BACKUP FIRE PUMP HOUSE FAN o CHECK FIRE PUMP HOUSE INLET FILTERS AND OUTLET REGISTERS FOR PROPER I
OPERATION j
i t
DISCUSSION.
FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS.
REFERENCES:
DRAWING 208-005 SHEET AH-71 SENSING ELEMENT: AH-173-DPS AH-168-DPS AND CONTROL STATION CONTACTS I
i O
i
{
-401 AR Rev. 11 Page 156
I ENCLOSURE I (Page 156 of 182)
"~iA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 l
t i
FIRE PP HOUSE l
FAN ZZZZ Z
TROUBLE r
EVENT POINT 1537 INDICATED CONDITION:
o AHF-33A BREAKER CLOSED AND CONTROL HANDLE IN THE NORMAL AFTER STOP 7
POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i L'
o RED LIGHT ON WITH A GREEN FLAG ON AHF-33A CONTROL STATION O
o TEMPERATURE IN FIRE PUMP HOUSE >85* F.
o ANY FIRE PUMP RUNNING i
OPERATOR ACTIONS FOR A VALID ALARM:
l o INVESTIGATE CAUSE OF AUTO START DISCUSSION:
i FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR i
FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME I
A FIRE PUMP IS IN OPERATION.
^
REFERENCES:
DRAWING 208-005 SHEET AH-71 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS 0
t l
AR-401 Rev. 11 Page 157 J
ENCLOSURE I (Page 157 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-05-05 F-05-05 a
FIRE PP HOUSE FAN TROUBLE EVENT POINT 1538 INDICATED CONDITION:
o AHF-33B BREAKER CLOSED AND CONTROL HANDLE IN THE NORMAL AFTER STOP POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG ON AHF-33B CONTROL STATION f s) t o TEMPERATURE IN FIRE PUMP HOUSE >85* F.
s, o ANY FIRE PUMP RUNNING OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF AUTO START DISCUSSION:
FIRE PUMP HOUSE FANS ARE USED FOR FIRE PUMP COOLING AND COMBUSTION AIR FOR DIESEL FIRE PUMPS. AT LEAST ONE FAN MUST BE IN OPERATION ANY TIME A FIRE PUMP IS IN OPERATION.
REFERENCES:
DRAWING 208-005 SHEET AH-72 SENSING ELEMENT: CONTROL STATION AND BREAKER CONTACTS O
J AR-401 Rev. II Page 158
l i
ENCLOSURE I i
(Page 158 of 182)
O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN j
TROUBLE EVENT POINT 0456 I
INDICATED CONDITION:
o AHF-22A BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START l
r REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22A CONTROL STATION f
OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IA IS RUNNING ENSURE AHF-22B IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP l
l DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-19-SS.
I SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
l 1
REFERENCES:
DRAWING 208-005 SHEET AH-75 SENSING ELEMENT: CONTROL SWITCH CONTACTS j
i I
AR-401 Rev. 11 Page 159
ENCLOSURE 1 (Page 159 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 0457 INDICATED CONDITION:
o AliF-22B BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IA IS RUNNING ENSURE AHF-22A IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP 6
i DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED i
BY EG-19-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
i j
REFERENCES:
DRAWING 208-005 SHEET AH-74 SENSING ELEMENT: CONTROL SWITCH CONTACTS O
AR-401 Rev. II Page 160
.- ~.
.--.\\
ENCLOSURE I q
(Page 160 of 182)
O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 0458 INDICATED CONDITION:
o DIESEL GENERATOR "A" ROOM DUCT AIR FLOW <0.25" H 0 AS SENSED BY E
AH-359B-DPS WITH AHF-22B OR AH-359A-DPS WITH AHF 22A ON REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-IA IS RUNNING SWAP OPERATING AHF-22 FANS o NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS AND OBSTRUCTIONS TO AIR FLOW DISCUSSION:
REFERENCES:
DRAWING 208-005 SHEET AH-74 SENSING ELEMENT: AH-359B-DPS, AH-359A-DPS w./
AR-401 Rev. II Page 161 i
u.
ENCLOSURE 1 (Page 161 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE j
f EVENT POINT 0459 INDICATED CONDITION:
i o DIESEL GENERATOR "A" CONTROL ROOM TEMPERATURE IS >118* F AS SENSED BY r
AH-540-TS l
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE "A" DIESEL GENERATOR CONTROL l
O ROOM L
OPERATOR ACTIONS FOR A VALID ALARM:
o INSPECT "A" DIESEL GENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE 1
o LOWER TEMPERATURE BY STARTING AHF-22A OR 22B i
o ENSURE AHF-28A IS RUNNING i
DISCUSSION:
o HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE OPERABILITY OF THE EMERGENCY DIESEL GENERATORS
REFERENCES:
DRAWING 208-005 SHEET AH-76 SENSING ELEMENT: AH-540-TS O
t AR-401 Rev. 11 Page 162
i ENCLOSURE I (Page 162 of 182) l PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 I
DIESEL GEN RM FAN i
TROUBLE EVENT POINT 0461 i
b INDICATED CONDITION:
o AHF-22C BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22C CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o IF EGDG-1B IS RUNNING ENSURE AHF-22D IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-20-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-77 SENSING ELEMENT: CONTROL SWITCH CONTACTS O
AR-401 Rev. 11 Page 163
ENCLOSURE I (Page 163 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 0462 INDICATED CONDITION:
o AHF-22D BREAKER OPEN WITH THE CONTROL HANDLE IN NORMAL AFTER START REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-22D CONTROL STATION OPERATOR ACTIONS FOR A VALID ALAPJi:
o IF EGDG-IB IS RUNNING ENSURE AHF-22C IS RUNNING o INVESTIGATE CAUSE OF FAN TRIP DISCUSSION:
DIESEL GENERATOR FANS WILL TRIP IF DIESEL SPEED IS <600 RPM AS SENSED BY EG-20-SS.
SECURING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-78 SENSING ELEMENT:
CONTROL SWITCH CONTACTS O
AR-401 Rev. II Page 164 t
j i
i ENCLOSURE 1 (Page 164 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 l
DIESEL GEN RM i
j FAN TROUBLE l
l l
EVENT POINT 0463
~
INDICATED CONDITION:
}
DIESEL GENERATOR "B" ROOM DUCT AIR FLOW <0.25" H,0 AS SENSED BY o
AH-369B-DPS WITH AHF-22D OR AH-369A-DPS WITH AHF-22C ON REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL FLOW INDICATION ON JOHNSON CONTROL PANEL OPERATOR ACTIONS FOR A VALID ALARM:
l o IF EGDG-IB IS RUNNING SWAP OPERATING AHF-22 FANS i
o NOTIFY AUX BLDG OPERATOR TO ENSURE INLET FILTERS ARE CLEAR OF DEBRIS AND OBSTRUCTIONS TO AIR FLOW l
DISCUSSION:
i I
i i
l
REFERENCES:
DRAWING 208-005 SHEET AH-77 t
SENSING ELEMENT: AH-369B-DPS, AH-369A-DPS O
I AR-401 Rev. II Page 165
l l
ENCLOSURE I (Page 165 of 182) j O
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 l
DIESEL GEN RM FAN l
TROUBLE t
EVENT POINT 0464 i
i INDICATED CONDITION:
o DIESEL GENERATOR "B" CONTROL ROOM TEMPERATURE IS >118' F AS SENSED BY AH-541-TS REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o HIGH AMBIENT TEMPERATURE CONDITIONS IN THE DIESEL GENERATOR CONTROL O
ROOM OPERATOR ACTIONS FOR A VALID ALARM:
o INSPECT "B" DIESEL GENERATOR CONTROL ROOM FOR ANY SIGNS OF A FIRE l
o LOWER TEMPERATURE BY STARTING AHF-22C OR 22D l
o ENSURE AHF-28B IS RUNNING
)
i i
DISCUSSION:
o HIGH AMBIENT TEMPERATURES IN THE CONTROL ROOM CAN ADVERSELY IMPACT THE OPERABILITY OF THE EMERGENCY DIESEL GENERATORS f
REFERENCES:
DRAWING 208-005 SHEET AH-79 SENSING ELEMENT: AH-541-TS O
AR-401 Rev. Il Page 166
l 1
ENCLOSURE 1 (Page 166 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 i
DIESEL GEN RM FAN TROUBLE l
EVENT POINT 1539
+
INDICATED CONDITION:
l o AHF-22A BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP
(
i REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
I o RED LIGHT ON WITH A GREEN FLAG ON AHF-22A CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START
)
l DISCUSSION:
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-19-SS.
STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-74 SENSING ELEMENT: CONTROL SWITCH CONTACTS O
AR-401 Rev. 11 Page 167
i
)
ENCLOSURE 1 (Page 167 of_182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 1540 INDICATED CONDITION:
[
o EGDG-1A SPEED IS >600 RPM AS SENSED BY EG-19-SS AND AHF-22A AND AHF-22B ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o EGDG-1A READY OR RUN LIGHT ON AND AHF-22A AND AHF-22B GREEN INDICATORS O
ON t
OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-22A AND/0R AHF-22B DISCUSSION:
1 DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.
OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING MUST BE CLOSELY MONITORED SO AS TO NOT EXCEED 105* ROOM TEMPERATURE.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS
REFERENCES:
DRAWING 208-005 SHEET AH-74 SENSING ELEMENT: 3 ERA AND BREAKER CONTACTS AR-401 Rev. 11 Page 168 e
ENCLOSURE 1-(Page 168 of 182) 0 PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE j
EVENT POINT 1541 l
INDICATED CONDITION:
i o AHF-22B BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP i
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
l o RED LIGHT ON WITH A GREEN FLAG ON AHF-22B CONTROL STATION f
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START 1,
l DISCUSSION:
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-19-SS.
STARTING THE FAN LOCALLY WILL. ACTUATE THIS ALARM.
I i
REFERENCES:
DRAWING 208-005 SHEET AH-75 SENSING ELEMENT: CONTROL SWITCH CONTACTS o
I AR-401 Rev. 11 Page 169 I
ENCLOSURE 1 (Page 169 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RH FAN TROUBLE I
EVENT POINT 1542 INDICATED CONDITION:
o AHF-22C BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
e o RED LIGHT ON WITH A GREEN FLAG ON AHF-22C CONTROL STATION (q)
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START DISCUSSION:
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-20-SS.
STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM,
REFERENCES:
DRAWING 208-005 SHEET AH-77 l
SENSING ELEMENT: CONTROL SWITCH CONTACTS
,O L) i l
AR-401 Rev. Il Page 170
I l
ENCLOSURE 1
(
(Page 170 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 DIESEL GEN RM FAN TROUBLE EVENT POINT 1543 INDICATED CONDITION:
l o EGDG-IB SPEED IS >600 RPM AS SENSED BY EG-20-SS AND AHF-22C AND AHF-22D ARE NOT RUNNING REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o EGDG-1B READY OR RUN LIGhi ON AND AHF-22C AND AHF-22D GREEN INDICATORS ON OPERATOR ACTIONS FOR A VALID ALARM:
o START AHF-22C AND/0R AHF-22D DISCUSSION:
DIESEL GENERATOR FANS PROVIDE COOLING FOR THE DIESEL GENERATOR ROOM.
OPERATION OF THE EMERGENCY DIESEL GENERATOR WITH NO COOLING FANS RUNNING MUST BE CLOSELY MONITORED 50 AS NOT TO EXCEED 105* ROOM TEMPERATURE.
REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-005 SHEET AH-77 SENSING ELEMENT:
3 ERB AND BREAKER CONTACTS O
AR-401 Rev. 11 Page 171
l l
1 i
ENCLOSURE 1 (Page 171 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-03 F-06-03 b
DIESEL GEN RM FAN TROUBLE EVENT POINT 1544 1
1 INDICATED CONDITION:
o AHF-220 BREAKER CLOSED WITH THE CONTROL HANDLE IN NORMAL AFTER STOP REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RED LIGHT ON WITH A GREEN FLAG ON AHF-22D CONTROL STATION i
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN AUTO START DISCUSSION:
DIESEL GENERATOR FANS WILL AUTO START IF DIESEL SPEED IS >600 RPM AS SENSED BY EG-20-SS.
STARTING THE FAN LOCALLY WILL ACTUATE THIS ALARM.
REFERENCES:
DRAWING 208-005 SHEET AH-78 SENSING ELEMENT: CONTROL SWITCH CONTACTS I
AR-401 Rev. 11 Page 172
ENCLOSURE I (Page 172 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM FAN I
TROUBLE EVENT POINT 0508 INDICATED CONDITION:
o AHF-44A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-44A CONTROL STATION O
I OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN TRIP o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION I
DISCUSSION:
l DUCTWORK TEMPERATURE >135' AS SENSED BY AH-402-TS WILL TRIP THIS FAN.
i AHF-20A MUST BE RUNNING IN EITHER FAST OR SLOW FOR THIS FAN TO RUN.
4 i
REFERENCES:
DRAWING 208-005 SHEET AH-98 SENSING ELEMENT: CONTROL STATION CONTACTS O
4 AR-401 Rev. II Page 173 l
(
ENCLOSURE I (Page 173 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 j
SAMPLING ROOM l
FAN TROUBLE i
i EVENT POINT 0509 i
4 INDICATED CONDITION:
i o AHF-44B BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START i
POSITION r
I REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-44B CONTROL STATION O
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF FAN TRIP o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION l
l DISCUSSION:
i DUCTWORK TEMPERATURE >135' AS SENSED BY AH-545-TS WILL TRIP THIS FAN.
AHF-20B MUST BE RUNNING IN EITHER FAST OR SLOW FOR THIS FAN TO RUN.
i
REFERENCES:
DRAWING 208-005 SHEET AF 4 SENSING ELEMENT: CONTROL STATION CONTACTS O
i i
AR-401 Rev. 11 Page 174
i ENCLOSURE I i
(Page 174 of 182) i PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 SAMPLING ROOM f
FAN TROUBLE j
r EVENT POINT 0510 i
INDICATED CONDITION:
o AHF-44A DUCTWORK TEMPERATURE >135'F AS SENSED BY AH-402-TS t
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
i o AHF-44A TRIPS O,
o WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-44A CONTROL STATION l
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF HIGH TEMP o IF FIRE CONDITIONS EXIST REFER TO AP-880 o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION f
DISCUSSION:
t
REFERENCES:
DRAWING 208-005 SHEET AH-98 SENSING ELEMENT: AH-402-TS O
AR Rev. 11 Page 175
-401
ENCLOSURE 1 (S
(Page 175 of 182)
V PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 i
SAMPLING ROOM FAN TROUBLE EVENT POINT 0511 INDICATED CONDITION:
o AHF-44A EXHAUST FLOW <0.10" H O AS SENSED BY AH-403-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW FLOW ON LOCAL INDICATION FOR AHF-44A G
OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE CAUSE OF LOW FLOW o CONSIDERATION SHOULD BE GIVEN TO SWAPPING TO "B" SIDE CONTROL COMPLEX VENTILATION o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION DISCUSSION:
AHF-20A MUST BE RUNNING PRIOR TO STARTING AHF-44A
REFERENCES:
DRAWING 208-005 SHEET AH-98 SENSING ELEMENT: AH-403-DPS O
l AR-401 Rev. 11 Page 176
i ENCLOSURE 1 (Page 176 of 182)
O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 i
SAMPLING ROOM i
FAN TROUBLE I
i EVENT POINT 1530 i
I INDICATED CONDITION:
o AHF-44B EXHAUST FLOW <0.10" H O AS SENSED BY AH-544-DPS 2
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOW FLOW ON LOCAL INDICATION FOR AHF-44B OPERATOR ACTIONS FOR A VALID ALARM:
l o INVESTIGATE CAUSE OF LOW FLOW o CONSIDERATION SHOULD BE GIVEN TO SWAPPING TO "A" SIDE CONTROL COMPLEX VENTILATION l
o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION j
i DISCUSSION:
AHF-20B MUST BE RUNNING PRIOR TO STARTING AHF-44B
REFERENCES:
DRAWING 208-005 SHEET AH-99 SENSING ELEMENT: AH-544-DPS l0 AR-401 Rev. Il Page 177
--l
1 ENCLOSURE 1 (Page 177 of 182)_
O PSA-F ANNUNCIATOR RESPONSE PSA-X-06-04 F-06-04 l
l SAMPLING ROOM FAN i
TROUBLE l
EVENT POINT 1531 i
l INDICATED CONDITION:
l o AHF-44B DUCTWORK TEMPERATURE >135'F AS SENSED BY AH-545-TS r
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
e o AHF-44B TRIPS o WHITE " TEMP NORM" LIGHT IS OUT FOR AHF-44B CONTROL STATION l
OPERATOR ACTIONS FOR A VALID ALARM:
f o INVESTIGATE CAUSE OF HIGH TEMP o IF FIRE CONDITIONS EXIST REFER TO AP-880
)
o NOTIFY CHEMISTRY OF LOSS OF SAMPLE HOOD VENTILATION i
l DISCUSSION:
t l
REFERENCES:
DRAWING 208-005 SHEET AH-99 l
SENSING ELEMENT: AH-545-TS I
O AR-401 Rev. Il Page 178
ENCLOSURE 1 (Page 178 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 i
INTERMEDIATE BLDG FAN TROUBLE I
EVENT POINT 0376 t
INDICATED CONDITION:
o AHF-24A BREAKER CLOSED AND DISCHARGE DAMPER AHD-67, CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o LOCAL DAMPER INDICATION OPERATOR ACTIONS FOR A VALID ALARM:
o SHUTDOWN AHF-24A o SWAP TO "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409 DISCUSSION:
i OPERATION OF AHF-24A WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.
h
REFERENCES:
DRAWING 208-005 SHEET AH-51 SENSING ELEMENT: 2-AHF-24A, AHF-24A-KS O
AR-401 Rev. 11 Page 179
ENCLOSURE 1 i
(Page 179 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 0377 INDICATED CONDITION:
o AHF-24B BREAKER CLOSED AND ITS DISCHARGE DAMPER AHD-68, CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
7 1
o LOCAL DAMPER INDICATION l
OPERATOR ACTIONS FOR A VALID ALARM:
[
o SHUTDOWN AHF-248 o SWAP TO "A" SIEE INTERMEDIATE BUILDING FANS PER OP-409 DISCUSSION:
OPERATION OF AHF-24B WITH THE DISCHARGE DAMPER CLOSED MAY CAUSE FAN DAMAGE.
REFERENCES:
DRAWING 208-005 SHEET AH-52 SENSING ELEMENT:
2-AHF-24B, AHF-248-KS O
AR-401 Rev. 11 Page 180
{
ENCLOSURE I i
(Page 180 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 i
INTERMEDIATE BLDG FAN i
TROUBLE EVENT POINT 1548 i
INDICATED CONDITION:
o AHF-29A BREAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION e
REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o GREEN LIGHT ON WITH A RED FLAG ON AHF-29A CONTROL STATION l
OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP TO "B" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP I
DISCUSSION:
i l
l i
REFERENCES:
DRAWING 208-005 SHEET AH-53 I
SENSING ELEMENT: CONTROL STATION CONTACTS O
AR-401 Rev. 11 Page 181
ENCLOSURE 1 (Page 181 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-05 F-06-05 INTERMEDIATE BLDG FAN TROUBLE EVENT POINT 1549 INDICATED CONDITION:
o AHF-29B BPEAKER OPEN WITH CONTROL HANDLE IN THE NORMAL AFTER START POSITION REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
{
o GREEN LIGHT ON WITH A RED FLAG ON AHF-29B CONTROL STATION OPERATOR ACTIONS FOR A VALID ALARM:
o SWAP T0 "A" SIDE INTERMEDIATE BUILDING FANS PER OP-409 o INVESTIGATE CAUSE OF FAN TRIP t
DISCUSSION:
i l
I
REFERENCES:
DRAWING 208-005 SHEET AH-54 SENSING ELEMENT: CONTROL STATION CONTACTS O
AR-401 Rev. 11 Page 182 i
ENCLOSURE 1 (Page 182 of 182)
PSA-F ANNUNCIATOR RESPONSE PSA-X-06-08 F-06-08 I
I l
l REACTOR BLDG I
I PERSONNEL DOOR I
I OPEN I
I EEE EVENT POINT 1212 INDICATED CONDITION:
o REACTOR BUILDING PERSONNEL OR EQUIPMENT HATCH INNER OR OUTER DOOR NOT CLOSED REDUNDANT INDICATION WHICH WILL VERIFY ALARM:
o RB D0OR INDICATION PANEL MCB PSA SECTION OPERATOR ACTIONS FOR A VALID ALARM:
o INVESTIGATE OPEN HATCH o REFER TO OP-417 i
j DISCUSSION:
1 REFER TO STS FOR ADMINISTRATIVE REQUIREMENTS.
REFERENCES:
DRAWING 208-064 SHEET ME-04 SENSING ELEMENT: ME-1,3,5&7-KS i O l
i l
AR-401 Rev. 11 Page 183 (LAST PAGE)
- -