Identifies No short-term Safety Concerns Re Util 890525 Response to Bulletin 88-011, Pressurizer Surge Line Thermal Stratification. Evaluation of Westinghouse Owners Group Bounding Analysis Encl
ML20059E931
Person / Time
Site: Prairie Island  Xcel Energy icon.png
Issue date: 08/30/1990
From: Diianni D
Office of Nuclear Reactor Regulation
To: Parker T
NORTHERN STATES POWER CO.
References
IEB-88-011, IEB-88-11, TAC-72157, TAC-72158, NUDOCS 9009110009
Download: ML20059E931 (3)


Text

-

-August'30,-1990

-Docket Nos. 50-282 DISTRIBUTION f and 50-306 DOCKll FRE'V TCHAN:

E HRC & LOCAL PDRs HSNIEN Mr. T. M. Parker, Manager PD31 R/F-ACRS(10).

Nuclear Support Service SMEADOR EJORDAN Northern States Power Company DDIIANNI' OGC 414 Nicollet Mali JZWOLINSKI Minneapolis, Minnesota 55401

Dear Mr. Parker:

SUBJECT:

HRC BULLETIN NO. E8-11. " PRESSURIZER SURGE LINE THERMAL STRATIFICATION" - EVALUATION OF WESTINGHOUSE OWNERS GROUP B0UNDING ANALYSIS (TAC NOS. 72157 AND 72158)

Ey letter dated May 25, 1989, Northern States Power Company responded to Item 1.b of NRC Bulletin No. 88-11. " Pressurizer Surge Line Thermal Stratification."

4 The letter stated that a bounding analysis performed by the Westinghouse Owners Group (WOG) for which Prairie Island Nuclear Generating Plant Units Nos. I and 2 is applicable, indicated that the pressurizer surge line (PSL) may not satisfy the ASME Section III Code criteria for the life of the plant, tcking into account the effects of thermal stratification. The analysis did, however, state that. the integrity of the PSL was adequate to justify continued operation of the facility for several years.

The staff has completed its review of the WOG boundi.ig analysis and concludes that there are no short-term safety concerns associated with the therral stratification effects for a duration of additional heatup/cooldown cycles of continued plant operation. A copy of the evaluation which was sent to the WOG is enclosed for your information.

The staff will essess the conformance of the PSL to applicable Codes and

)

ngulatory requirments for 40-year plant life when the WOG report'regarding.

Item I.d of the Bulletin is submitted.

i Sincarely, 44, 444e0 si W

)

Dominic C. Dilanni Project Manager Project Directorate 111-1

' Division of Reactor Projects - III,.

IV, V & Special Projects Office of Nuclear Reactor Regulation 4

Enclosure:

As stated cc w/ enclosure:

h See next page h0 l

LA/PD31:R PM/PD31:DRSP D/F

DRSP SMEADORf CIIANNI RPI ON h%[

8 Q/90 8/Q/90 8/g o

9009110009 900830 PRAIRIE ISLAND 88-11 72157/8 C

PDR ADOCK 05000282 O

PDC

(pmayh

' NUCLEAR REGULATORY COMMISSION' UNITED STATES q(/[g/

y g

e a

r, wassiworow. o. c. roess j

T g

August 30, 1990 I

j Docket Hos. 50-282 and 50-306 Mr. T. N. Parker, Manager Nuclear Support Service Northern States Power Company 414 Nicollet Mall Minneapolis, Minnesota 55401

Dear Mr. Parker:

SUP4LCT: NRC BULLETIN NO. 88-11. " PRESSURIZER SURGE LINE THERMAL STRAllFICATION" - EVALVATION OF WESTINGHOUSE OWNERS GROUP B0UNDING ANALYSIS (TACNOS.72157AND72158)

Cy letter dated May 25, 1989, Northern States Power Con.pany responded to item-i 1.b of NRC Bulletin No. 88-11. " Pressurizer Surge Line Thermal Stratification."

The letter stated that a bounding analysis performed by the Westinghouse Owners-Group (UOG) for which Prairie Island Nuclear Generating Plant Units Nos. I and 2 isapplicable,indicatedthatthepressurizersurgeline(PSL)maynotsatisfy l

the ASI'E Section III Code criteria fcr the life of the plant, taking into account the effects of thermal stratification.' The analysis did, however, f the state that the integrity of the PSL was adequate to justify continued. operation o fecility for several years.

4 The staff has cortpleted its review of the WOG bounding analysis and concludes that there are no short-term safety concerns associated with the thermal stratification effects for a duration of additional heatup/cooldown cycles of continued plant operation. A copy of the evaluation which was sent to the WOG is enclosed for your inforniation.

The staff will assess the conformance of the PSL to aaplicable Codes and regulatory requirements for 40-year plant life when tie WOG report regarding Iten ).d cf the Bulletin is subniitted.

Sincerely.

T V

a c s. L Dominic C. Dilanni, Project Manager l

Project Directorate III-1 I

Division of Reactor Projects - III, IV, V & Special Projects Office of Nuclear Reactor Regulation j

Enclosure:

As stated

-j cc w/ enclosure:

-See r. ext page n

_)

Mr: T.'M..Pa'rker Prairie Island' Nuclear Generating Northern States Power Company Plant cc:-

i Gerald Charnoff Esq.

Shaw, Pittman, Potts and Trowbridge 2300 N Street, N.W.

Washington, DC 20037 Dr. J. W. Ferman Minnesota Pollution Control Agency 520 Lafayette Road St. Paul, MN 55155 l

Mr. E. L. Watz), Piant Manager Prairie Island Nuclear Generating Plant.

Northern States Power Company Route 2 Welch, Minnesota 55089 Joseph G. Maternowski Assistant Attorney General Environmental Protection Division Suite 200 520 Lafayette Road St. Paul, Minnesota 55155 U.S. Nuclear Regulatory Commission Resident Inspector's Office 1719 Wakonade Drive East Welch, Minnesota 55089 Regional Administrator, Region III U.S. Nuclear Regulatory Comission Office of Executive Director for

.i l

Operations l

799 Roosevelt Road Glen Ellyn, Illinois 60137 Mr. William Miller, Auditor Goodhue County Courthouse j

Red Wing, Minnesota 55066 l

L i

l e

n 9

l l

i.

l Page 1 of 8 THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO THE REVIEW OF i

WESTINGHOUSE OWNERS GROUP (WOG)

BOUNDING EVALUATION FOR PRESSURIZER SURGE LINE.

THERMAL STRATIFICATION WCAP-12277

_ INTR M CTION The' pressurizer surge line (PSL) in the pressurized water reactors (PWRs),

is a stainless steel pipe, connecting.the bottom of the pressurizer vessel to the hot leg of the coolant loop.

The out flow of the pressurizer water is generally warmer than the hot leg flow.

Such temperature differential-(AT) varies with plant' operation activities and can be as high.as 320'F

.(

during the initial plant heat up.

Thermal stratification is the separation of cold flow stream in the horizontal portion of the PSL resulting in temperature difference at the top and bottom of the pipe.

Since thermal stratification is the direct result of the differences in densities between the pressurizer water and the hot ~ leg water, the potential for stratification is increased as system AT increases and as the insurge or outsurge flow decreases.

Stratification in PSL was found recently and confirmed by data measured from several PWR plants.

Original design analyses did not include any stratified. flow loading conditions.

Instead it assumed complete sweep of fluid along the line during insurges or outsurges resulting in uniform thermal loading at any particular piping location. Such analyses did not reflect PSL actual thermal condition and potentially may overlook undesirable line deflection i

j and its actual high stresses may exceed design limits.

In addition, the striping phenomenon, which is the oscillation of the hot and cold i

stratified boundary, may induce high cycle fatigue to the inner pipe wall t

and needs also-to be analyzed. Thus assessment of stratification effects on PSL is necessary to ensure piping integrity and ASME Code Section III conformance.

l t

g pfh g1W

% (S' 1

i

. - ~

Yege 2 of 8 STAFF EVALUATION Since stratification in PSL is a generic concern to all PWRs an NRC Information Hotice No 88-80 was issued on October 7, 1988, and then an NRC

]

Bulletin 88-11 for the same concern was also issued on December 20, 1988.

Westinghouse, on behalf of the Westinghouse Owners Group (WOG), has performed a generic bounding evaluation report W' AP-12277 (Reference 1).

This report provides the technical basis for the generic justification for continued operation (JCO), for each of the WOG plants and constitutes compliance with the requested action 1.b of Sulletin 88-11.

Plants which have discovered any pross discernable distress during performance of the walkdown, as requested by Bulletin's action 1.a. should report findings and specify corrective actions in their JC0, in addition to that provided in this report.

house's efforts and information provided in the reportiThe following i Prior to the issuance of the Bulletin, WOG implemented a program to address the issue of the surge line therma! stratification. The program consisted of plant-specific analysis covering five plants and a review of thermal mLiitoring data from eight plants.

Westinghouse had instrumented PSLs and collected data for verifying stratification conditions.

The thermal monitoring data obtained considered outside wall temperatures at different location around the pipe and along the axis of the pipe vs.

time, vertical and lateral displacements at various locations along the pipe vs. time, and various plant parameters vs. time, from existing plant instrumentation and control sensors. ~In some cases the data were ba not on19 on plant heatup but also on operation and plant cooldown conditions.

The specific analyses included redefinition of revised thermal transients considering stratification effects and evaluation of pipe stress and fatigue usage factors.

The overall analytical approach used in all these cases have been consistent and has been reviewed in detail by the NRC staff.

The evaluation concluded that a single bounding analysis was not feasible.

Due to the variations in design, Westinghouse could not define a single envelope case to justify the 40 year life of the surge line, therefore a bounding evaluation was performed to justify continued operation for at least ten (10) additional heatup/cooldown cycles.

The bounding evaluation is essentially a demonstration of the applicability of the plant-specific and the monitoring results to the remaining WOG plants.

All plant-specific analyses completed to-date, have demonstrated 4

a 40 year life of the surge line Two sets of parameters were defined, a)

Parameters which affect severity of thermal stratifica-tion (i.e thermal hy@oulic and operational effects)

,s Page 3 of 8 i

.c b)

Parameters which affect PSL response to thermal strati-fication (i.e. structural effects).

The range of the parameters for the plants analyzed and/or monitored was used to establish the bounding criteria and to enable an individual plant i

by plant comparison.

To expand the data base for a wider range of PSL configurations, Westinghouse recommended additional plant monitoring based on plant similarities (grouping), and surge line phr** cal, design and operational parameters of all 55 domestic Westinghouse plants.

Plants with parameters not within the range of the current monitoring database were recommended for additional monitoring.

Ten (10) different groups were identified = for the 55 domestic Westinghouse plants for data collection, review and analysis of the pertinent thermal hydraulic, operational.and structural paramettrs.

Curreistly 22 separate monitoring programs are either completed, in process, or being planned.

About 40% of the plants falling in one group with the remaining 60% of the Westinghouse PWR's divided among the 1

nine groups.

When this program is completed, it will provide sufficient I

monitoring data with at least one plant monitored in each group.

Parameters which have a significant effect from a thermal hydraulic stand ~

I point are pipe inside diameter and slope. Plante falling outside the resulting bounding criteria of pi pipe average slope of O' to 1.44'pe inside diameter of 7" to IL4" and degrees, were recommended frr monitoring.

The range of the parameters was expanded by 2 20% in determir.ing a bounding criteria to which other plants were. compared.

It was conc 19ded that a bounding evaluation which is based on enveloping techni:p::4, will not have a significent effect on the thermohydraulic behavior due to a 2 20% change in pipe size and slope.

The staff. agrees with Westinghouse's efforts and methodology for monitoring, updating and assessing PSt. for the.

stratification condition.

Thermal hydraulic evaluations using higher slope and smaller diameter pipe i

are expected to reduce the stratification effects.

Eleven plants.have an average slope higher and one plant has a pipe size smaller than that allowed by the critraia.

)

Some parameters judged to be relatively significant for the structural effects are:

Entra6ce angle to the hot leg nozzle Mid line riser LenDth of the longest t traight run of pipe i

Type of in-line compone*.t J

Presence of whip restraints Number of vertical rigid supports g

~i Page 4 of S l

c Two plants have longest straight run lengths which are _less than the -

minimum in the criteria, and four plants have welded lugs or trunnion attachments to PSL.

Since none of the analysis to date has included evaluation of welded attachments, which may increase thermal stresses due to structural discontinuities, this condition falls outside the criteria,

L and the following has been recommended.

a)

Inspection of'these welds during walkdown b)

Evaluation of these attachments on a plant-specific basis.

The five plant specific analysis consisted of three parts:- (1) global effects on. stresses, moments, displacements, and support reaction loads, based on both axial and radial variations in the pipe metal temperature, (2) 1ccal stresses due to thermal gradient, and (3) local stresses and effects to fatigue due to thermal striping.

The global and local stresses in items (1) and (2) above were superimposed to obtain total stresses.

i In addition to the detailed plant specific analysis for the five plants, 4

twelve (12) plants have completed interim evaluations of the surge line stratification which include Finite Element structural analysis of.each 4

specific configuration under stratified conditions.

The five plants for which detailed plant-specific analyses performed and evaluation reports submitted to NRC, are as follows:

(

Seabrook (see WCAP-12151 and Suppl. 1 and WCAP-12305) south Texas Units 1-2 and 2 (see WCAP-12067 Rev 1 and Suppl. 1) Vogle U.-ft 2 (see WCAP-12132 WCAP-12199 and WCAP-12218) Beaver Valley Unit P see WCAP-12093 and Supp1's 1 and 2) Comanche Peak Unit 1 (see WC/) 12248 and Suppl. 1) s l Based on these reviews Westinghouse concluded that a shorter horizontal -

length will result in lower loads since the surge line will experience less vertical deflection and it will tend to result in a more uniform distribution of the bending moment due to stratified loading.

In' addition middle line risers will also tend to reduce the stratification effects.

The stratification induced gicbal bending of the surge line was calculated using ANSYS computer code.

Although a 320*F step temperature change was assumed for stratification through out the surge line, the changes were-linearized in ANSYS using conventional pipe element model.

Finite Element.

i models were used to calculate local stresses due to top-tobottom non-linear thermal gradients in the PSL.

Five (5) hot-to-cold interface locations were analyzed using eleven (11) cases of ~ thermal stratification.- to.

calculate piping response under all required loading conditions, ' reflecting temperatures differences up to 320'F. Other cases were obtained by interpolation.

Westinghouse reported that their best estimate analytical results compared favorably with measured displacements data observed-during monitoring.

f-4 r.-+

o

.,..3.._

.,m.,,

..., ~ _. -

Page 5 of 8 t

In two of the analyses, a rigid vertical support was removed. In one case it was shown that the support was not required, and in the other case it was replaced with a snubber and a spring. The PSL was subsequently re qualified and found acceptable.

Stress summary results from the five plant specific analyses performed to

(

date indicates that the primary plus secondary stress intensity range ratio of equation 12 of ASME III section N8-3600, is less than 1.0.

The critical location for stress is usually the safe end weld of the nozzle connecting the surge line to the primary loop hot leg.

In one case only it was determined to be at the reducer. This seem to be a unique case l

since no other utility within the WDG has a mid line reducer in the PSL.

Stresses were intensified hy "K" factors, to secount for the worst case concentration for all piping elements ~1n the PSL.

The staff agrees with-the approaches used hy the licensee for performing PSL reanalysis.

To account for the thermal striping effects to PSL, flow model test results, performed for the Liquid Metal Fast Breeder Reactor primary loop and for the Mitsubishi Heavy Industries Feedwater Line cracking, were reviewed to establish the boundary condition.

These test results were i

used to define striping oscillation data, amplitude and frequencies, for evaluating high cycle fatigue.

i Portions of PSL which experience stratification and striping were defined based on measured results; Westinghouse reported that considering AT attenuation with time, and a-frequency of.30 H2, a usage factor of less than.20 was determined as the worst case due to striping alone, even when the stresses were intensified by "K" factors.

The worst case eler..ent was determined to be the butt weld.

A surface film coef ficient of 500 BTU /hr-sq. ft

'F was used and it was based on a flow rate of 90 gpm which was assumed to_be constant throughout all striping analysis.

Although the data used in the assess-ment were obtained from scale test model which showed that the frequency can range from.10-10 HZ. the staff agreed that the stresses will be higher with the lower frequency and the.30 HZ. average frequency is justified.

However the thermal striping potential due to a film coef ficient of 500 BTU /hr-sq. ft.

  • F and attenuation of AT is questionable, but at this time no other better number exists and therefore this represents the best judgement.

If other information will be available, based on the ongoing efforts by EPRI or possible future NRC research work,-

it will be utilized and further assessments will be made for assessing the striping effects to PSL.

With the thermal transients redefined, new fatigue ussge factors were calculated.

To determine the new fatigue usage factors, the more detail techniques of ASME III NB-3200 were employed.

Due to the non-axisymmetric i

nature of stratification loading, stresses due to all loadings were obtained from Finite Element analysis and then combined on a stresa compo-nent basis.

Five (5) levels of thermal stratification at five worst case i

1

~

a 1

Page 6 of 8-y points were calculated using the WECEVAL program.

Stresses were intensified by "K" factors to account for worst case concentration = in the piping elements.

- Westin-'ouse reported that a cumulative usage factor (COF)'of 0.73 was t-deterstrad to be the worst case at the-hot leg nozzle safe end location for all but one case.. For that case a 14x16 reducer existed in the surge line and the CUF at that location was determined to 0.94.The CUF included contributions from both global bending and local effects of stratifi-cation considering the nonlinear step change top to bottom temperature distribution and striping.

' Stresses resulting from primary loading such as pressure, dead weight, and seismic are not affected hy thermal stratification loading and typically have a minor effect on the calculation of the fatigue usage factor.

The contribution of seismic loadings to the cumulative usage factor from the plant specific analyses was reported to be 185.

All of the detailed plant specific analyses assumed the. occurrence of twenty operational earthquakes.

The staff agrees with the approaches used hy Westinghouse for calculating the usage. factor.-

Westinchouse reported that the PSL fatigue life is primarily depended upon the n m r of heatup and cooldown cycles rather than the years of operation.

The ww

ase years of operation at any WOG plant is 28.5 years.. The worst con number of heatup cooldown cycles is 75 and occurs _ at'a different-plant.

Based on the combination of these two worst case values an l

" Operating Life Factor" (0LF) of 0.44 is obtained which indicat 1

es that no more than 50% of the operating life has been used at any Westinghouse plant to date.

For the generic case of's CUF = 1.0 a 17% value wa?

attributed to age and an 83% was attributed to fatigue with a 20% of the 83% value attributed to striping.

a i

l

^

4 4

n-

,,....m

,.,.,.,-c_m-.,._.n..n,..,-,

,,,c.-,-

,e q

Page 7 of a C0h0LUSIONS Based on our review, we conclude +, hat the information provided by Westinghouse in references 1 and 2, is comprehensive and acceptable..

Westinghouse on behalf of the Owners Group had mada acceptable efforts to provide technical basis for the licensee's JC0 as indicated in the

{

requested actions of tie NRC Bulletin 88-11, item 1.b.

The staff believes thct there is,1o immediate or short term safety concerne associated witi. the stratification effects for 10 additional hec +-;/

cooldown cycles of sentinued plant operation.

However, each of the WDG l

plants should submit a.'100 using this report as the basis.

We will assess if the surge line in eech plant meet the code acceptance criteria for the 40 year plant life whe.1 additional generic analyses based on plant grouping is performed by Westinghouse for the Owners group.

Principal Contributor:

Shou-Dien Hou i

i

-e

.,,.n

j d

Page 8 of 8