i

  • ~

)

i

.i i

SPECIAL TEST EXCEPTIONS dROUPHEIGHT.INSERTIONANDPOWLRDISTRIBUTIONLIMITS LIMITI:

CONDITION FOR OPERATION 3.'10.2 The group height, insertion and power distribution limits of Specifications 3.1.1.4, 3.1.3.1, 3.3.3.5, 3.1.3.6, 3.1.3.7, 3.2.2, 3.2.3, 3.2.7 and the Minimum Channels OPERABLE requirement of Functional Unit 15 of Table 3.3-1 may be suspended during the performance of PHYSICS TESTS provided:

a.

The THERMAL POWER is restricted to the test power plateau which shall not exceed 85% of RATED THERMAL POWER, and b.

The linear heat rate limit shall be maintained by either:

1.

Maintaining COLSS calculated core power less than or equal to COLSS calculated core power operating limit based on linear heat rate (when COLSS is in service); or 2.

Operating within the region of acceptable operation as specified in the CORE OPERATING LIMITS REPORT using any operable CPC channel (when COLSS is out of service.)

APPLICABILITY: During startup and PHYSICS TESTS.

ACTION-With any of the above limits being exceeded while any of the above requirements are suspended, either:

a.

Reduce THERMAL POWER sufficiently to satisfy the requirements of the above Specification, or b.

Be in HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.10.2.1 The THERMAL POWER shall be determined at least once per hour i'

during PHYSICS TESTS in which any of the above requirements are suspended and shall be verified to be within the test power plateau.

4.10.2.2 The linear heat rate shall be determined to be within its limits during PHYSICS TESTS above 5% of RATED THERMAL POWER in which any of the above requirements are suspended.

ARKANSAS - UNIT 2 3/4 10-2 Amendment No. E7,JPE 9310260384 931020 R-PDR ADOCK 05000368 a

.P..

pog 31

,