Ro:On 730405,during Routine Surveillance Testing,Lpci 11 Inboard Injection Valve MO-2014 Could Not Be Opened Using Control Room Handswitch.Caused by Dirty Contacts Preventing Energizing Coil Circuit.Contacts Cleaned
ML20058K617
Person / Time
Site: Monticello Xcel Energy icon.png
Issue date: 04/24/1973
From: Mayer L
NORTHERN STATES POWER CO.
To: Oleary J
US ATOMIC ENERGY COMMISSION (AEC)
References
NUDOCS 9102120668
Download: ML20058K617 (1)


Text

___ _ _ _ _ _ _ _

Fib Cy.

~B C",N:3cre*

NORTHERH STATES POWER COMPANY Minneapolis, Minnesota 55401 April 24, 1973

(\ .W.U-Mr. J. F. O' Leary, Director  ! j phId/.(<}.,

Directorate of Licensing United States Atomic Energy Comission , 'd ef ~ 1 Washington, D C 20545 33 -

~..

Dear Mr. O' Leary:

hDhTICEL11] NUCLEAR GENERATING PIANT ,

Docket No. 50-263 License No. DPR-22 Failure of LPCI Injection Valve to Open A condition occurred at the Monticello Nuclear Generating Plant which we are reporting to your office in accordance with Section 6.6.C. of the Technical Specifications, of Provisional Operating License DPR-22.

On April 5, 1973, during routine surveillance testing, the No. 11 LPCI inboard injection valve, FD-2014, could not be opened using the control room handswitch. Dirty auxiliary contacts were found to have prevented energizing the opening contactor coil circuit. The contacts were cleaned and the valve was demonstrated to operate properly.  !

Yours very truly, ,

/O .

1 l

L 0 Mayer, PE Director of Nuclear Support Services gy, ;-ag, Im/kik dd S Q tc:c 3 cc: B H Grier A ffy G Charnoff -

f@y g1b73 6 %

Minnesota Pollution Control Agency '

-5 ATFN: Ken Dzugan 0- ths Docm[g fo ( x8 a3 4 LSD1 D

..,x 9102120668 730424 CF ADOCK 05000263 CF