' 3 / 4 '.~ 4 ; ' ELECTRICAL POWER SYSTEMS r ;-~.
3/4.4.1 A.C.
SOURCES LIMITING' CONDITION FOR FUEL HANDLING OPERATION 3.4.1.1.0ne circuit between the offsite transmission network and the onsitetdistribution system and one diesel generator shall be-I OPERABLE.
APPLICABILITY:
DEFUELED MODE-* f-l JACTION:
i
'With-one of the-above A.C.-sources not OPERABLE suspend-handling of
' irradiated fuel-in the secondary containment and crane operations over theispent-fuel storage pool:when fuel assemblies are stored therein..
j i
JSURVEILLANCE_REQUIREffNTS 1,
4i4.1.1 The aboveirequired independent circuit-between the offsite l
l transmission networf and the-onsite'AC distribution. system'shall be
" determined 10PERABLE-at11 east once per 7 days by-verifying. correct breaker: alignments and indicated power availability.
g
~K4.4;1.2 ?The above> required diesel generator shall be determined OPERABLE at least once per 7 days by verifying correct breaker
~
q F
alignments and-indicated. power availability.
1 1
n 4'.4.1.3 LThe above-required diesel generator shall be demonstrated 0PERABLE:
f La.-
At.leasttonce per 92 days by:
q 1.,
Verifying that the day fuel. tank contains a minimum of
'275 gallons of fuel.
e
- 2. :
' Verifying the fuel storage tank contains a minimum ofL 1
20,412, gallons, y
+
4
^E ;Ihi~spEcIfied diesel generator shall be OPERABLE only when
' handling fuel in the secondary,. containment.-
Li OPERABILITY of A.C. sources is unaffected by'the use.of commercial grade (non-Categor'y'I)' parts provided that the use of such Jgr1 i s
- administrative 1y documented ~and tracked.sr In e cc;;;;n, u;1;;A. L T 1 dCitt act ; p p ;;, tb :n; :;;f;ty el:t;d functient.f 3HOREHAM - UNIT 1 3/4 4-1 9011070116 901030 F
PDR ADOCK 05000322 P
PNV &
p.
g y-w e
n.
4 s.:
e Ue?j.]LECTRIC)L^POWERTSYSTEM[-
's-324'.42?-ONSITEPOWERfDISTRIBUTIONSYSTEMS TLIMIT-ING CONDITION FOR FUEL HA'NDLING-OPERATION-o
'I' i
. ~.
3.4'2.1
.As a minimum,<two' of the followin.g-A.C. system divisions,.and
?
~ one1D.C. power distribution' system divisioniwhich correspondsnto a j
L 0PERABLE^dieselfgenerator shall be OPERABLE and energized:-
-a.
A.C. powerLdistriDution-1.;
Division 1' consisting of:
a')
4160-volt A.C. bus 101.-
b) 480-volt A.C. bus 111 and MCCs 1110 through.1116, a
1118,1119,111Y and 1112.
c') '
120-volt:A.C. distribution. panels R1,-R2, and R3.
J 1
-2..
Division 2. consisting of:
a )l
~4160 volt A.C. bus 102
}
t.6
.b ) -
480-voltrA.C. bus 112 and.MCCs 1120fthrough 1126,
1128, 1129, and1112X.
~
c')
120-volt A.C.. distribution panels in B1, B2 and l
B 3 '.
i 3.
- Divis. ion 3 consisting of:
a )'
4160 voltLA.C.' bus 103 b))
'480-vo.it A.C. bus.113 and-MCCs-1133 and11134.
~
s t
c) 120-volt 1 A.C. distribution Lpanels 01 and 02.
1 l
bl. -
D.C.xpower distribution-m 1.-
l Division 1 consisting off125-volt D.C.. distribution busL A.-
- 12. ;
Division 2 consisting of.125-volt D.C. distr.ibution bus 1 B
t y:n L3..
~ Division;3 consisting-o'f-125-volt' D'.C. Edistr1bution' bus l
~
C.-
i lAPPL'ICABILITYi4DEFUELED MODE * #
,, ;- -~The D7Y.- power distribution system shall'be OPERABLE only.when
(
Lhandling fuel.in the' secondary containment, f
o
- g"ifi;0PERAB]LITYJ of-OnsiteL Power
- Distribution Systems is unaffected by sthe: uselof commercial gradeE(non-Category I) parts provided that thecuse: of 'suchi > arts ~is administrative 1y documented and tracked.
+
- f'.h:dditica,U"Eit,STt'Tider:
90: :pply t:
h: ::::ty-rt::t; p # -
r
- 4 n+s. _f 5
x
.SHOREHAM1-UNIT 1-3/4 4-3 I