Interim Deficiency Rept Re Potentially Defective Diesel Generator Thermostatic Valves.Initially Reported on 820622. Results of Insp to Determine Status of Valves Expected by 820923.Part 21 Rept Filed by Colt
ML20058E149
Person / Time
Site: Wolf Creek 
Issue date: 07/19/1982
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-82-222, NUDOCS 8207280067
Download: ML20058E149 (1)


Text

KANSAS GAS AND ELECTRIC COMPANY THE ELECTAC COMPANY GLENN L MOESTER vice pagoogNT.NucLgan July 19, 1982 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 KMLNRC 82-222 Re:

Docket No. STN 50-482 Subj: Potential 10CFR50.55(e) Report - Possible Diesel Generator Thermostatic valve Malfunctions

Dear Mr. Seidle:

The purpose of this letter is to provide a status report on the investi-gation into a potential 10CFR50.55(e) matter concerning the diesel generator thermostatic valve. Kansas Gas and Electric Company reported this problem to Region IV of the Nuclear Regulatory Commission on June 22, 1982.

The potentially defective thermostatic valves are used to control the diesel cooling water temperature. The unit has a spring restrained between two end pieces whose length and " breakdown" is set by an axial bolt and nut.

If the nut backs off, then the length of the assembly results in a valve stroke not generated by the thermal assembly. This additional stroke makes the unit control at lower temperatures, thus overcooling the system.

Engine damage could occur with lcw raw water supply temperatures. The design was changed in 1977 to require the nut to be soldered to the bolt to prevent the nut from backing off.

However, it is possible thac some units supplied to nuclear plants were of the older design. Colt has filed a 10CFR21 Report on this matter.

The Architect / Engineer is developing a rework plan to inspect the thermostatic valve units that were furnished with the Wolf Creek diesel generators. The inspection will determine whether or not the units have the above-described de fect.

The status of the inspection and any necessary rework will be reported to you on or before September 23, 1982.

In the interim, please direct any questions on this matter to me or to Mr. Otto Maynard of my staff.