November 17, 1993
{
+
Docket No. 50-302 DISTRIBUTION See attached page Mr. Percy M. Beard, Jr.
Senior Vice President, Nuclear Operations Florida Power Corporation ATTN: Manager, Nuclear Licensing Crystal River Energy Complex 15760 W Power Line Street Crystal River, Florida 34428-6708
Dear Mr. Beard:
SUBJECT:
CRYS 1AL RIVER UNIT 3 - ELECTRICAL SEPARATION CRITERIA (TAC M82172)
On October 28, 1993, we met with members of your staff to discuss cable separation criteria at Crystal River Unit 3 (CR-3).
You had previously provided Revision 2 to your " Electrical Design Criteria, Electrical Circuit Physical Separation and Cable Tray Loading" document to us for information by letter dated May 6, 1993.
You stated that this document was revised in accordance with your design control program and your commitment to ANSI N.25.2.ll.
j As a result of our preliminary review of your submittas and our meetings on this subject, we have determined that a detailed review of your submittal is not required and will not be performed by the Office of Nuclear Reactor Regulation (NRR). This si.ould not be interpreted as approval of your submittal or program. The adequacy of your electrical separation may be evaluated during future inspectionr.
During the October 28, 1993 meeting, your staff stated that evaluation i
and neca, w eirrections of electrical separation deviations would be completen a end of the CR-3 1996 outage. We emphasize that the 4
evaluati p, d necessary corrections should be completed as soon as possible u atat we request notification of any deviations from your current Mal e.
This completes our action on TAC No. M82172.
Sincerely, (Original Signed By)
Harley Silver, Project Manager Project Directorate II-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc: See next page *See previous concurrence on LA:PD22:DRPE PM:FD22:DRPE D:PD22dlRPE EELB PE:PDII-2 WE ETanal HSilver$
HBbb 2 CBerlinger*
RCroteauY DME
/
/93
/
/93
////C/93 11/17/93
/
/93 Document Name: CR38h72.LTR h*N 93120301c, 931117 I ()
j,TJ PDR ADOL.4 05000302 P
PDR m
Docket No. 50-302 DISTRIBUTION See attached page Mr. Percy H. Beard, Jr.
Senior Vice President, Nuclear Operations Florida Power Corporation ATTN: Manager, Nuclear Licensing Crystal River Energy Complex 15760 W Powur Line Street Crystal River, Florida 34428-6708
Dear Mr. Beard:
SUBJECT:
CRYSTAL RIVER UNIT 3 - ELECTRICAL SEPARATION CRITERIA (TAC M82172; On October 28, 1993, we met with members of your staff to discuss cable separation cr;teria at Crystal River Unit 3 (CR-3).
You had previously provided Revision 2 to your " Electrical Design Criteria, Electri 71 Circuit Physical Separation and Cable Tray Loading" document to us for information by letter dated May 6, 1993.
You stated that this document was revised in accordance with your design control program and your commitment to ANSI N.25.2.ll.
As a result of our preliminary review of your submittal and our meetings on this subject, we nave determined that a detailed review of your submittal is not required and will not be performed by the Office of Nuclear Reactor Regulation (NRR). This should not be interpreted as approval of your program.
The adequacy of your electrical separation may be evaluated during future inspections.
During the October 28, 1993 meeting, yr staff stated that evaluation and necessary corrections of electric; iration deviations would be We emphasize that the completed by the end of the CR-31995 i evaluation and necessary corrections shouw se completed as soon as possible and that we request notification of any deviations from your current schedule.
This completes our action on TAC No. M82172.
Sincerely, Harley Silver, Project Manager Project Directorate II-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc: See next page k4 M#
orr LA:PD22:DRPE PM:PD2bORPE D:PD22:DRPE EEWI h b ETana CTI HSdbgh HBe m w Chrh,wc fI M SM
/'/ /f /93
/ k h 93
/
/93 sl/-(1/9%
O Dm Document Name: CR382172.LTR
/
p
Mr. Percy M. Beard Crystal River Unit No.3 Florida Power Corporation Generating Plant Cc' Mr. Gerald A. Williams Mr. Joe Myers, Director Corporate Counsel Div. of Emergency Preparedness Florida Power Corporation Department of Comunity Affairs KAC-ASA 2740 Centerview Drive P. O. Box 14042 Tallahassee, Florida 32399-2100 St. Petersburg, Florida 33733 Mr. Bruce J. Hickle, Director Chairman Nuclear Plant Operations Board of County Comissioners Florida Power Corporation Citrus County Crystal River Energy Complex 110 North Apopka Avenue 15760 W. Power Line Street Inverness, Florida 32650 Crystal River, Florida 34428-6708 Mr. Robert B. Borsum Mr. Rolf C. Widell, Director B&W Nuclear Technologies Nuclear Operations Site Support 1700 Rockville Pike, Suite 525 Florida Power Corporation Rockville, Maryland 20852 Crystal River Energy Complex 15760 W Power Line Street Crystal River, Florida 34428-6708 Regional Administrator, Region II U. S. Nuclear Regulatory Comission Senior Resident Inspector 101 Marietta Street N.W., Suite 2900 Crystal River Unit 3 Atlanta, Georgia 30323 U.S. Nuclear Regulatory Comission Mr. Bill Passetti 6745 N. Tallahassee Road Office of Radiation Control Crystal River, Florida 34428 Department of Health and 4
Rehabilitative Services Mr. Gary Boldt 1317 Winewood Blvd.
Vice President - Nuclear l
Tallahassee, Florida 32399-0700 Production florida Power Corporation Attorney General Crystal River Energy Complex Department of Legal Affairs 15760 W Power Line Street The Capitol Crystal River, Florida 34428-6708 Tallahaseee, Florida 32304 I
DISTRIBUTION
' Docket file NRC & Local PDRs PD# 23 Reading S. Varga G. Lainas H. Berkow H. Silver E. Tana OGC ACRS (10)
E. Herschoff, Region II i
P Y
t i
r
'O I)*
l
.