ML20057E301

From kanterella
Jump to navigation Jump to search
Insp Repts 50-369/93-19 & 50-370/93-19 on 930830-31 & 0901- -03.No Violations Noted.Major Areas Inspected:Response to Unit 1 Shutdown on 930822 Due to Indicated Leak in SG a
ML20057E301
Person / Time
Site: McGuire, Mcguire  
Issue date: 09/27/1993
From: Blake J, Economos N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20057E296 List:
References
50-369-93-19, 50-370-93-19, NUDOCS 9310080300
Download: ML20057E301 (7)


See also: IR 05000369/1993019

Text

  1. n neg

UTUTED STATES

S

f*

4,

NUCLEAR REGULATORY COMMISSION

  • , *

4

' REGloN 11

[

S

101 MARIETTA STREET, N.W., SUITE 2900

ATLANTA, GEoRGtA 30323 0199

%....+/

Report Nos.: 50-369/93-19'and 50-370/93-19

Licensee: Duke Power Company

422 South Church Street

Charlotte, NC 28242

Docket Nos.: 50-369 and 50-370

License Nos.: NPF-9'and NPF-17-

Facility Name: -McGuire 1 and 2

.

Inspection Conducted: August 30 - 31, and September 1-3, 1993

N mmN

[M

3

i

InspectoI:

.

.

y

N. Economo~s

'W

pateSigned

i

Approved by:

'[

) 27 f3

-

J.

ake, Chief

D1te Signed

!

.

Ma r als and Processes Section

g eering Branch-

iv sion of Reactor Safety

l

SUMMARY

l

'

,

Scope:

.

This announced inspection was conducted in response to Unit I shutdown on

!

August 22, 1993, because of an indicated leak in "A" steam generator (S/G).

l

The leak rate prior to shutdown was approximately 185 gallons per day.

Results:

Following plant shutdown, the licensee determined that the primary source of

the leak was a sleeved tube, (R39-C72) in S/G "A".

The licensee's

investigation determined that the aforementioned tube exhibited a crack just

above the kinetic weld near the top of the sleeve. This crack provided the

leak path and was the primary source of the leak. Additional minor leaks

associated with sleeved tubes were identified in S/Gs "A", "B" and "D".

One

nonsleeved tube (R41-C43) was identified as a leaker in S/G "B".

The Eddy

Current (ET) indication in this tube was characterized as a single

circumferential crack that was located about 8.7-inches above the 8th tube

support plate (TSP) in the U-bend region. This indication had been miscalled

by the analysts, in the ET examination performed during the April 1993

refueling outage, as an indication with no dectable degradation.

The licensee is presently re-reviewing and re-examining tubes with suspect

indications.

$j

9310080300 930929

PDR

ADOCK 05000369

.t

Q

PDR

11

'

- .

.

.

.-- ..

. .

.

.

2

Two sleeved tubes (R39-C72 and R7-C78), are being removed for metallurgical

examination to determine the root cause and possible generic implication of

the failure. Through discussions with licensee technical and management

personnel, and a review of newly written analysis guidelines, the inspector

has determined that the licensee has dedicated adequate resources in this

effort. Procedure and guidelines have sufficient conservatism in terms of

acceptance criteria to provide a reasonable assurance that suspect indications

will be identified and properly dispositioned.

Within the areas inspected, no violations or deviations were identified.

,

1

I

.

.

'

!

l

-

.

~

REPORT DETAILS

l

1.

Persons Contacted

!

!

J. Baumann, Supervisor Eddy Current

K. Davis, Lead Analyst Level III Eddy Current

M. Geddie, Station Manager

  • R. Hall, Engineering Manager
  • L. Kunka, Regulatory Compliance Engineer
  • B. Lowery, Nuclear Service Engineer

j

D. Mayes, Nuclear Service Engineer

!

  • T. McMeekin, Vice President McGuire Nuclear Station

R. Sharpe, Regulatory Compliance Manager

M. Thompson, Component Engineer

Other licensee employees contacted during this inspection included

i

technical support, Quality Assurance, and administrative personnel.

i

!

'

NRC Resident Inspectors

  • G. Maxwell, Senior Resident Inspector

T. Cooper, Resident Inspector

j

4

  • Attended exit interview

2.

Plant Shutdown Due To Steam Generator Tube Leakage, Unit 1 (IP73753)

,

'

On August 22, 1993, Unit I was shutdown in response to an indicated tube

leak in S/G "A".

On August 30, 1993, the inspector arrived on site to

ascertain conditions relative to this leakage, to review previous

examination records of tubes found leaking at this time, to monitor the

l

licensee's inspection plans, and to evaluate activities and the

correctness of actions in the four S/Gs prior to plant startup.

l

l

Discussions with cognizant personnel disclosed that all but one of the

leaks were associated with sleeves in S/Gs '"A", "B" and "D".

The

~

leaking sleeves were associated with the following tubes:

Tube

Sleeve Installation Date/TYDe

Leakaae Rate

S/G "A"

l

R2-C114

4/90 (kinetic / roll)

1 drip /2 min.

I

l

R7-C77

4/90 (kinetic / roll)

1 drip /5 min.

!

R7-C111

4/90 (kinetic / roll)

1 drip /5 min.

R39-C72

9/91 (double kinetic)

Steady Stream

S/G "B"

l

R21-C61

4/90 (kinetic / roll)

1 drip /1.25 min.

R21-C62

4/90 (kinetic / roll)

1 drip /2.25 min.

  • R41-C43

not sleeved

I drip /10 sec.

,

-

_

I

.

m

2

'

S/G "D"

R6-C43

4/90 (kinetic / roll)

I drip / min.

  • The only leaker found on the cold leg side of the steam

generators that was not sleeved.

Background on Leaky Tubes:

Tube R39-C72 S/G "A":

Through discussions with cognizant licensee personnel and records

review, the inspector ascertained that the subject tube was

sleeved in April of 1991. The overall length of this sleeve is

approximately 17{ inches. Approximately five (5) inches of the

sleeve length is positioned in the tube sheet. The sleeve is

secured to the parent tube by energizing a prepositioned explosive

charge near each end of the sleeve. The explosive force of the

charge expands a narrow band of the sleeve fusing the sleeve to

l

,

the tube. A subsequent thermal treatment relieves the residual

stresses generated by the process. This fused area is tested

qualitatively with ET to determine joint integrity.

Prior to the

1991 outage, sleeves were secured using the hard roll expansion

technique on the lower end of the sleeve inside the tubesheet and

the kinetic weld / roll technique on the upper end of the tube

located in the free span tube region. The double kinetic weld

along with an improved joint cleaning technique was meant to

improve sleeve integrity. A review of the log book disclosed that

the sleeve in the subject tube had been returned to the vendor for

i

repairs prior to installation. The repair involved

'

relocation / realignment of the charge and replacement of a missing

wafer. The licensee stated that physical measurements taken

during the current outage places the location of the charge

slightly above optimum sleeve height but still within tolerance.

Sleeve Examination:

Through discussions with cognizant licensee personnel, the

inspector ascertained that the subject sleeve had been examined

during the April 1993 outage and there were no detectable

indications observed. During the present outage, examination with

a rotating pancake (RPC) probe disclosed a crack like indication

in the parent tube at the upper weld, just above the apex of the

i

expansion. This location coincides with the location where

remote visual examination, performed during this inspection,

showed a small amount of water cascading over the top of the

sleeve. Based on the above mentioned ET test results, it would

appear that a crack was probably present in the aforementioned

tube location, but its magnitude was below the threshold of ET

probe detectibility. From the time the plant returned to power

until the time the leak was detected, by plant monitors, it

appears that the crack grew at an accelerated rate until

propagating through the tube wall.

Following the close of this

l

l

._

._

_

_

-

i

1

3

.

inspection, the licensee pulled the subject sleeve, from the S/G,

,

and forwarded it to B&W in Lynchburg, VA. (BWNS) for a

'

metallurgical investigation to determine the root cause of the

crack and possible generic implications.

In addition to R39-C72,

the licensee identified a total of approximately 31 sleeved tubes,

,

located in all four S/Gs, which were labeled as suspect due to the

l

presence of indications which were not crack like, identified by

Bobbin and confirmed by RPC. Tube, R7-C78 located in S/G "A",

was .

'

also pulled and sent to BWNS for metallurgical investigation, as

it exhibited a ET signal interpreted as a geometry distortion

which was not fully understood.

Tube, R41-C43 S/G "B", Cold Leg:

As stated earlier in this report, by visual inspection, the

,

licensee determined the leak rate of this tube to be approximately

!

one drop per 10 seconds. The source of the leak was established

at a height of approximately 8.7 inches above the 8th tube support

plate, on the cold leg side of the S/G, at the transition U-bend.

Examination of the tube with bobbin coil and RPC probes, during

'

the present outage, confirmed the presence of a single

'

circumferential crack which had propagated through the tube wall.

The bobbin coil signal was analyzed as a complex dent signal with

-

a voltage of approximately 5.7 volts. During the April 1993

outage, this tube had been examined with a similar bobbin coil

probe. The indication was analyzed by the primary and secondary

i

analysts and classified as an indication which had no detectable

degradation (NDD), even though the voltage of the signal was in

the range of 6-7 volts. Cognizant licensee personnel stated that

the high noise level associated with the U-bend region of the tube

bundle was in part responsible for the miscall i.e., NDD vs Dent

i

signal. However, this inspector's position on the high noise

phenomenon in the U-bend region, is that the analysts should have

been cautioned to be extremely sensitive to indications in this

area which could be masked by the high noise level.

The smaller leaks in the other tubes were believed to be related

to one or several steps in the process used to secure the sleeves

to the parent tubes. One of the most likely causes was thought to

be inadequate cleaning of the joining surfaces. Because of

concerns raised over the adequacy of the ET examinations, the

sleeving process, as well as the potential for generic

implications on the other unit and the Catawba Station, the

licensee implemented the following tube inspections / examinations.

(1)

Rewrote specific analysis guidelines, dated 9/1/93, to

review bobbin coil ET data, acquired during the April 1993

outage, for all dent-like indications with 2: 2.0 volts. The

objective was to detect any degradation with dent-like

indications throughout the entire length of the tube above

the Tubesheet.

Initial screening of data for this review

was done by computer. The 2.0 volt threshold was raised

I

.

.

,-

. - - ,

, . - - -

-.

. . .

.- -

.

l

l

4

l

-

l

later to 2.5 volts because it was determined that signals at

l

the lower level, were insignificant and beyond the scope of

the review.

(2)

RPC examine all indications with bobbin coil ET signals a

5.00 volts.

(3)

RPC examine the following sleeves in each of the four S/G/s.

S/G "A"

S/G/"B"

S/G "C"

S/G "D"

294

171

94

263

(4)

Ultrasonic examination of certain special interest sleeved

)

tubes including leakers.

S/G "A"

S/G "B"

S/G "C"

S/G "D"

!

46

0

0

10

'

(5)

RPC examine two rows of tubes around leakers.

t'

Since the close of this -inspection on September 3,1993, the

inspector has been following the progress of this work

through telephonic discussions with the licensee. Through

these discussions, the inspector ascertained that the

i

sleeved segments of tubes R39-C72 and R7-C78 were pulled and

forwarded to BWNS, for failure analysis.

Preliminary

-!

results indicated that tube R39-C72 exhibited a

~

circumferential crack which covered approximately 270

degrees of the tube's periphery. On September 14, 1993

1

during a telephone conference the licensee /BWNS reported

i

that preliminary results from the metallurgical

.

I

investigation indicated that this tube exhibited an

unusually fine, ASTM grain size (a 11), a relatively high

hardness and relativity high mechanical properties

suggesting the tube was susceptible to primary water stress

corrosion cracking.

Also the inspector ascertained that the review of indications

selected through computer data screening had been completed - this

review identified no obvious miscalls.

Following is a tabulation of tubes in the U-Bend region exhibiting

indications and therefore designated for RPC examination.

S/G "A"

S/G "B"

S/G "C"

S/G "D"

,

'

Indications / Tubes

221/147

510/205

133/96

785/363

3.

Mockup Training of Welders (55050)

Towards the end of this inspection welders were undergoing mockup

training in preparation for welding plugs in the Tubesheet where tubes

were removed from service.

In addition to verbal instruction, the

i

. . - , _ .

.

.

-

-

-

.

. - . - -

-

-

-

-..

.

. . . -

-

l

'

l

.

!

.

.'

5

l

candidates demonstrated their ability to fabricate an acceptable weld in

the overhead position inside a mockup of a steam generator bowl with a

tubesheet.

The men were dressed with protective. clothing and

respiratory protection equipment. The test plug, was welded (fillet

'

weld), using the gas tungsten arc welding (GTAW), process. Both the

!

plug and filler metal were made of inconel material. The inspector

observed three welders take the subject test successfully. Welder

performance qualification records and the associated weld data sheet for

the applicable weld procedure were reviewed and found to be in order.

,

Within the areas inspected no violations or deviations were identified.

>

4.

Exit Interview

The inspection scope and results were summarized on September 3, 1993,

i

with those persons indicated in paragraph 1.

The inspector described

j

the areas inspected and discussed in detail the inspection results. The

i

licensee did not identify as proprietary any of the material provided to

,

!

or reviewed by the inspector during this inspection. Dissenting

comments were not received from the licensee.

-

i

,

!

!

i

i

f

.

I

!

'

i

i

i

!

!

,

!

!

!

,

!

!

!

!

i

!

. . .

.

-

. _ .

- .

. .

. _ _ . _ . . , .

.

. . .

. -

. . _ _ . ..,___ __ ..,......._._ .. . ...,,_.