October 5, 1993
. Docket Nos. 50-369 and 50-370 Mr. M. S. Tuckman Senior Vice President Nuclear Generation Department Duke Power Company P.O. Box 1006 Charlotte, North Carolina 28201-1006
Dear Mr. Tuckman:
SUBJECT:
RESPONSE TO GENERIC LETTER 91-11, " RESOLUTION OF GENERIC ISSUES 48,
'LCOs FOR CLASS lE VITAL INSTRUMENT BUSES,' AND 49, ' INTERLOCKS AND LCOs FOR CLASS lE TIE BREAKERS' PURSUANT TO 10 CFR 50.54(f)" FOR MCGUIRE UNITS 1 AND 2 (TAC N05. M82429 AND M82430)
On July 18, 1991, the NRC issued Generic Letter (GL) 91-11 that contained the staff resolution of Generic Issues 48 and 49. The GL required licensees to certify that procedures exist which contain time limitations and surveillance requirements for vital instrument buses (VIBs), inverters or other onsite power sources for VIBs, and tie breakers.
If procedures do not exist, a justification demonstrating the reasons why the controls are not needed is required by the GL.
By letter dated January 31, 1992, you responded to the GL explaining the appropriate administrative controls, procedures and/or mechanical devices that were in place to ensure conformance with the GL for the McGuire site.
The staff has reviewed your response and finds that it meets the reporting requirements set forth in GL 91-11. This completes the staff's activities on TAC Nos. M82429 and M82430.
Sincerely, VictorNers[s,!eniorProjectManager S
Project Directorate II-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc:
See next page ACRS (10), P-135 Dr." BUTION:
DMatthews JStarefos
- Dockb4 File
- >
VNerses Glainas NRC & Local PDRs LBerry EMerschoff, RII i
PDII-3 R/F OGC. 15B18 SVarga
,3 N HCE PDII-3/LA PDII-3/ PIE [
PDkIrE/PM D:PDIJ-3_ k L. BERRY h J.STAREk NERSES D.hHWS WE Dm
/6/S /93 10 /M /93
/g/ '[/93 lb / 993 i.
0FFICIAL RECORD COPY FILE NAME:
G:\\MCGUIRE\\M82429.30 I
9310080193 931005 l
.3
@Fo l PDR ADOCK 05000369 P
PDR 40
.#j
- a arc 4
1*
E UNITED STATES
%(
NUCLEAR REGULATORY COMMISSION k-
,/
WASHINGTON, D.C. 20555 0001 October 5, 1993 Docket Nos. 50-369 and 50-370 Mr. M. S. Tuckman i
Senior Vice President i
Nuclear Generation Department Duke Power Company P.O. Box 1006 Charlotte, North Carolina 28201-1006
Dear Mr. Tuckman:
SUBJECT:
RESPONSE TO GENERIC LETTER 91-11, " RESOLUTION OF GENERIC ISSUES 48,
'LCOs FOR CLASS lE VITAL INSTRUMENT BUSES,' AND 49, ' INTERLOCKS AND LCOs FOR CLASS lE TIE BREAKERS' PURSUANT T0 10 CFR 50.54(f)" FOR MCGUIRE UNITS 1 AND 2 (TAC NOS. M82429 AND M82430) l On July 18, 1991, the NRC issued Generic Letter (GL) 91-11 that contained the j
staff resolution of Generic Issues 48 and 49. The GL required licensees to j
certify that procedures exist which contain time limitations and surveillance i
requirements for vital instrument buses (VIBs), inverters or other onsite i
power sources for VIBs, and tie breakers.
If procedures do not exist, a justification demon'strating the reasons why the controls are not needed is required by the GL.
By letter dated January 31, 1992, you responded to the GL explaining the appropriate administrative controls, procedures and/or mechanical devices that were in place to ensure conformance with the GL for the McGuire site.
The staff has revi2wed your response and finds that it meets the reporting requirements set forth in GL 91-11. This completes the staff's activities on 1
TAC Nos. M82429 and M82430.
Sincer' :.
Victor Nerses, Senior Project Manager Project Directorate II-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc: See next page 1
i i
h:
~
Duke Power Company McGuire Nuclear Station cc:
Mr. A. V. Carr, Esquire Mr. Dayne H. Brown, Director Duke Power Company Department of Environmental, l
422 South Church Street Health and Natural Resources Charlotte, North Carolina 28242-Division of Radiation Protection 0001 P. O. Box 27687 i
I Raleigh, North Carolina 27611-7687 County Manager of Mecklenberg County 720 East Fourth Street Mr. Alan R. Herdt, Chief Charlotte, North Carolina 28202 Project Branch #3 U. S. Nuclear Regulatory Commission Mr. R. O. Sharpe 101 Marietta Street, NW. Suite 2900 Compliance Atlanta, Georgia 30323 Duke Power Company McGuire Nuclear Site Ms. Karen E. Long 12700 Hagers Ferry Road Assistant Attorney General Huntersville, NC 28078-8985 North Carolina Department of Justice J. Michael McGarry, III, Esquire P. O. Box 629 Winston and Strawn Raleigh, North Carolina 27602 1400 L Street, NW.
Washington, DC 20005 Mr. G. A. Copp Licensing - EC050 Senior Resident Inspector Duke Power Company c/o U. 5. Nuclear Regulatory P. O. Box 1006 Commission Charlotte, North Carolina 28201-12700 Hagers Ferry Road 1006 Huntersville, North Carolina 28078 Regional Administrator, Region II Mr. T. Richard Puryear U.S. Nuclear Regulatory Commission Nuclear Technical Services Manager 101 Marietta Street, NW. Suite 2900 Westinghouse Electric Corporation Atlanta, Georgia 30323 Power Systems Field Sales
~
2709 Water Ridge Parkway, Suite 430 Mr. T. C. McMeekin Charlotte, North Carolina 28217 Vice President, McGuire Site Duke Power Company Dr. John M. Barry 12700 Hagers Ferry Road Mecklenberg County Huntersville, North Carolina 28078-8985 Department of Environmental Protection 700 N. Tryon Street Charlotte, North Carolina 28202 l
e pH#fCp h
IE UNITED STATES
)*
l' ii NUCLEAR REGULATORY COMMISSION j#
t W ASHINGTON. D.C. 20555-4001 g
October 5, 1993 Docket Nos. 50-369 and 50-370 Mr. M. S. Tuckman Senior Vice President Nuclear Generation Department Duke Power Company P.O. Box 1006 Charlotte, North Carolina 28201-1006
Dear Mr. Tuckman:
SUBJECT:
RESPONSE TO GENERIC LETTER 91-11
" RESOLUTION OF GENERIC ISSUES 48,
'LCOs FOR CLASS lE VITAL INSTRUMENT BUSES,' AND 49, ' INTERLOCKS AND LCOs FOR CLASS lE TIE BREAKERS' PURSUANT TO 10 CFR 50.54(f)" FOR MCGUIRE UNITS 1 AND 2 (TAC NOS. M82429 AND M82430)
On July 18, 1991, the NRC issued Generic Letter (GL) 91-11 that contained the staff resolution of Generic Issues 48 and 49. The GL required licensees to certify that prc:M6res exist which contain time limitations and surveillance requirements for vital instrument buses (VIBs), inverters or other onsite power sources for VIBs, and tie breakers.
If procedures do not exist, a justification demonstrating the reasons why the controls are not needed is required by the GL.
By letter dated January 31, 1992, you responded to the GL explaining the appropriate administrative controls, procedures and/or mechanical devices that were in place to ensure conformance with the GL for the McGuire site.
The staff has reviewed your response and finds that it meets the reporting requirements set forth in GL 91-11. This completes the staff's activities on TAC Nos. M82429 and M82430.
Sincerely, 4
Victor Nerses, Senior Project Manager Project Directorate 11-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation cc: See next page 4
x Duke Power Company McGuire Nuclear Station cc:
Mr. A. V. Carr, Esquire Mr. Dayne H. Brown, Director Duke Power Company Department of Environmental, 422 South Church Street Health and Natural Resources Charlotte, North Carolina 28242-Division of Radiation Protection 0001 P. O. Box 27687 Raleigh, North Carolina 27611-7687 County Manager of Mecklenberg County 720 East Fourth Street Mr. Alan R. Herdt, Chief Charlotte, North Carolina 28202 Project Branch #3 U. S. Nuclear Regulatory Commission Mr. R. O. Sharpe 101 Marietta Street, NW. Suite 2900 Compliance Atlanta, Georgia 30323 Duke Power Company McGuire Nuclear Site Ms. Karen E. Long i
12700 Hagers Ferry Road Assistant Attorney General Huntersville, NC 28078-8985 North Carolina Department of Justice J. Michael McGarry, III, Esquire P. O. Box 629 Winston and Strawn Raleigh, North Carolina 27602 1400 L Street, NW.
Washington, DC 20005 Mr. G. A. Copp Licensing - EC050 Senior Resident Inspector Duke Power Company c/o U. S. Nuclear Regulatory P. O. Box 1006 Commission Charlotte, North Carolina 28201-12700 Hagers Ferry Road 1006 Huntersville, North Carolina 28078 Regional Administrator, Region II Hr. T. Richard Puryear U.S. Nuclear Regulatory Commission Nuclear Technical Services Manager 101 Marietta Street, NW. Suite 2900 Westinghouse Electric Corporation Atlanta, Georgia 30323 Power Systems Field Sales 2709 Water Ridge Parkway, Suite 430 Mr. T. C. McMeekin Charlotte, North Carolina 28217 Vice President, McGuire Site Duke Power Company Dr. John M. Barry 12700 Hagers Ferry Road Mecklenberg County Huntersville, North Carolina 28078-8985 Department of Environmental i
Protection l
700 N. Tryon Street Charlotte, North Carolina 28202 i
J