ML20057A615
| ML20057A615 | |
| Person / Time | |
|---|---|
| Site: | Fort Saint Vrain |
| Issue date: | 08/30/1993 |
| From: | Russell D PUBLIC SERVICE CO. OF COLORADO |
| To: | |
| References | |
| FPOR-23-I02, FPOR-23-I2, NUDOCS 9309150041 | |
| Download: ML20057A615 (3) | |
Text
..--
)
FORT ST. VRAIN NUCLEAR GENERATING STATION Public
) SerVICO+
PUBLIC SERVICE COMPANY OF COLORADO
~
]
DOCUMENT TRANSMITTAL TO sflMOd Afd bOfPs t
DATE
)
31 L 1 LOO 6l FROM (MLd \\ IMPh
&T 0 5 W O?_ l 9'h PLdhodir, f D TCL-5 )
THE FOLLOWING MATERIAL IS TRANSMITTED HEREWITH:
DFPP Undut tG&& A r Pw A "h3 F PO R 2 3 '00L4 ?
O I
l 1
\\
1 l
-151b'01 dh 9309150041 930830 (oI (T
PDR ADOCK 05000267 g)
F PDR PLEASE RETURN YOUR SIGNED ACKNOWLEDGEMENT INDICATING RECEIPT OF THE ABOVE MATERIAL
< siam o, so m >
l ro,m <Ci3n a aan wmaroa. rwwe.o wn,m Copy io neapient, Rmin Yernow Con RECIPIENT - Retorr. Acknow%dged White Copy to initiator
DFPP 8-30-93 j
Iccuo 20 l
l i
O I
SECTION DFP.5.1 i
FIRE PROTECTION OPERABILITY REQUIREMENTS TABLE OF CONTENTS l
NUMBER TITLF ISSUE EFFECTIVE
.l DATE
[
FPOR-0 Fire Protection Operability 4
12-7-92
)
FPOR-1 Emergency Diesel Generator Carbon 4
12-7-92 l
Dioxide System I
FPOR-2 Carbon Dioxide Hose Reels -
4 12-7-92 DELETED FPOR-3 Ha7 ori tystems 5
12-7-92
')
1 FPOR-4 Delhi ( 3 pray Systems 3
12-7-92 j
l FPOR-5 Fixed Water Spray Systems 4
12-7-92 1
FPOR-6 Plant Yard Hydrants 3
12-7-92 FPOR-7 Fire Extinguishers 4
12-7-92 FPOR-8 Breathing Air System - DELETED 3
12-7-92 t
FPOR-9 Fire Hose Stations 4.
12-7-92 FPOR-10 Fire Water Pumps 4
12-7-92 FPOR-11 Fire Water Headers and Mains 3
12-7-92 FPOR-12 Fire Detectors 6
12-7-92 FPOR-13 Fire Barriers 7
12-7-92 FPOR-14 Fire. Doors 8
12-7-92~
j FPOR-15 Fire Dampers 5
12-7 FPOR-16 Fire Protection Cooldown Trains -
5 12-7 DELETED l
FPOR-17 Alternate Cooling Method (ACM) 5 12-7-92 DELETED FPOR-18 Ladders - DELETED 4
12-7-92 i
FPOR-19 Cable Wraps - DELETED 3
12-7-92 FPOR-20 Emergency Lighting - DELETED 4
12-7 FPOR-21 Site Fire Brigade - DELETED 2
12-7-92 FPOR-22 Storage of Activated Graphite 1
12-7-92 FPOR-23 Fire Water Makeup System 2
8-30-93 O
.~
f FPOR-23 Iggua 2-y Page 1 of 2 FIIRE PROTECTION OPERABILITY REOUIREMENTS Fire Water Makeup System i
FPOR-23 The Fire Water Makeup System shall be operable with:.
a)
A minimum of five (5) million gallons of water in j
l the storage pond (s).
b)
At least two (2) operable circulating water makeup pumps.
t
'i c)
An operable flow path capable of taking suction
'l from the storage pond (s) and delivering the water l
to the fire water pump pits.
l APPLICABILITY: At all times ACTIONS:
I With less than 5 million gallons of water in the storage a.
pond (s), establish a backup water source of water within 72
~
l hours.
)
b.
With one of the circulating water makeup pumps inoperable, perform an operability check on the remaining pump..
1 With both the circulating water makeup pumps inoperable, c.
within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> return at least one pump to service or-establish a source of backup fire suppression.
d.
With no operable flow path available, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> restore an operable flow path or provide. an - alternate source of makeup water to the fire water pump pits.
SURVEILLANCE REOUIREMENTS:
The fire water makeup system shall be demonstrated operable:
At least once per seven (7)-days by verifying the storage a.
pond inventory.
b.
At least once per 31 days by running the required circulating water makeup pump.
O l
1 FPOR-23 Iccuo 2
[
Paga 2 of 2 c.
At least once per 18 months by:
1)
Cycling each testable valve in the makeup water flow path (s) through at least one complete cycle of full travel.
2)
Verifying the performance capability and mechanical l
condition of the required circulating water makeup l
l Pump.
l l
j i
BASIS FOR FPOR-23:
The operability of the Fire Water Makeup System, in conjunction with the fire water pumps (FPOR-10),
ensures adequate fire l
l suppression capability for any postulated fire (except in congested cable areas) involving water used as the primary suppression fluid.
The makeup system and the fire water pumps supply Deluge Systems, Fixed Spray Systems, Fire Hose Stations, and Plant Yard Hydrants.
There is a small possibility that a fire in one of the congested l
cable areas could disable the Fire Water Makeup Systam..In this l
- scenario, the Platteville Volunteer Fire Department would be summoned for assistance in extinguishing the fire using their pumpers.
In the unlikely event all makeup pumps, storage ponds and flow paths are inoperable simultaneously, off-site fire department response is available for supplemental or backup capability. 24 I
hours is sufficient time to return one makeup pump to service or establish a backup fire water source.
h As detailed 11. the DFPp and the DFPp Safety Evaluation, one million l
gallons of water is adequate for fire suppression purposes. Hence, I
5 million gallons of water in the storage pond (s) is very conservative and 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is adequate time to restore the storage pond (s) to the level in the event the inventory is less than 5 million gallons of water.
The Surveillance Requirements of the. Fire Water Makeup System are adequate to ensure a pump will be available in the event of a fire, and an adequate water supply and operable flow path exist.
k l