Dear Mr. Lewis:
In your letter dated June 5,1993, to Dr. Murley, you expressed concern, in i
the context of NRC Bulletin 93-02, about thermo-lag and its impact on reactor syst i in the event that it fails. As you know, licensees use Thermo-Lag fire uarriers to satisfy NRC fire prctection requirements.
These licensees separate one train of cables and equipment needed to shutdown the plant in the event of a fire from its redundant train with Thermo-Lag fire barriers.
1 Thermo-Lag is mainly used to separate redundant raceways locathti 'outside of primary containments by surrounding one of the raceways within a Thermo-Lag enclosure.
Some licensees have also used Thermo-Lag to construct radiant energy shields inside containment. This is a limited application.
The bulletin was narrowly focused on temporary sources of fibrous material in the primary containments of boiling and pressurized water reactors (BWRs and PWRs). The purpose of the bulletin was to have such material removed promptly if it is not cbsigned to withstand a loss-of-coolant accident (LOCA).
Our concern, as expressed in the bulletin, is that debris generated from such sources during a LOCA might be transported to the suppression pool for a BWR or to the containment sump for a PWR, If this material is deposited on the surface of strainers for the emergency core cooling system and the containment spray system, tnen the pumps in those systems might not have adequate net positive suction head and may fail to perform as designed.
We are also pursuing a broader concern that relates to fibrous material that is permanently installed in drywells of some BWRs..That concern was previously addressed in our review of Unresolved Safety Issue A-43,
" Containment Emergency Sump Performance." As a result of recent operating experiences, we are reviewing how this material and other materials would 3
perform during a LOCA and the impact of these materials on the performance of safety-related systems. The scope af this review would include thermo-lag if it were present in significant quantities within the drywell.
However, very I
little thermo-lag is located there.
I would like to thank you for your interest in the safety and performance of licensed nuclear power plants.
"' Y* [Y) OL (f&
y 9309080087 930715 MF PDR DRG NRRB AshoK C. l'haoani, Director PDR v
Division of Systems Safety and Analysis Office of Nuclear Reactor Regulation DISTRIBUTION:
Central File PDR CSB R/F DSSA R/F T.Murley F.Miraglia W. Russell AThadani MVirgilio M
fGfg.ad(g b ~
R.Barrett RLobel RWoodruff CMcCracken PJones Mail Room-12G18-(YT0930121) 3 g g4.5.$_/d j
S 4
- See previous concurrence DD:DbA SPik:)SSA B:DSSA SCSB:DSSA SCSB:DSSA SCSB:DSSA RWoodruff:lbk*
RLobel*
RBarrett*
CMcCtacken Rdon s MVlygilio 7/12/93 7/12/93 7/12/93 7//f /93 7/l
/93 7//t /93 t
D:DSSN!'s AThadtni N 000-ni Di 7/%/93 DOCUMENT NAME: A:\\435A.LTR 1
O j
j