FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS j
As Required by the Provisions of the ASME Code Section XI i, o n.,
Jersey Central Power & Light Co.
5/4/93 pe,e nome Madison Ave. & Punch Bowl Rd. Morristown, M 1
3
^o or" 08731 l
- 2. Plant Ovster Creek Nuclear Generating Station uni,, 0. / ster Creek Nuclear Generating
'3tation i
U.S. Route 9, Forked River, N.J. 08731 GPU Nuclear
{
Asoress moosir oreentzet6on P.O. No., Job No., etc.
}
- 3. Work Performed by CPU Nuclear Type Code Symbos stamp N/A
[
N/A l
Authoriretion No.
1 Uoner Pond Road. Parsippany.
N.T.
07054 Empiretion Date N/A Aooress
- 4. Identification of System See Attached.
- 5. tal Applicab6e Construction Code B31.1 is 55 geition, 55 N/A Addenda Code Case (b) Applicabie Edition of Section XI Utilized for Repairs or Replacements 19 86 l
L
- 6. Identificateon of Components Repaired or Replaced and Replacement Components A$ME Coes National
- Repaired, Stamped Name of Name of Manufacturer Board Other Year
- Replaced, (Yes Component Manu rer Serial No.
No.
Identification Built or Replacement or Nol
\\.
N i
\\
N N
e aded
- 7. Description of Work Hydrostetie 0 eneum tic 0 Nominal Operating Pressure O B. Tests Conducted:
Other Q Pressure psi Test Temp.
'F N/A NOTE: Supplemental eheets in form of lists, sketches, or drowings may be used provided (1) size is B4 in. x 11 in., (2) Informe.
tion in items 1 through 6 on this report is included on each shoot, and (3) each sheet is numbered and the number of sheets is recorded et the top of this form.
(12/82) l This Form (E00030) may be obtained from the Order Dept.. ASME,345 E. 47th St., New York, N.Y.10017 I
l i
9305190355 930511 PDR ADOCK 05000219 O
PDR e
_+.e%
i FORM NIS-2 (Back)
- 9. Remarks See remarks column on attached sheet Applicabte Manufacturer's Date Reports to De etteched l
l CERTIFICATE OF COMPLIANCE repair /
We certify that the statements made in the report are correct and this ren1accrentconforms to the rules of the ASME Code,Section XI.
l N/A Type Cooe Svmoot Stamp Certificate of Authorization No.
N/A Expiration Dete N/A t
93 Man b 19 Signed,
Mgr, NDE/ISI Servi ces Date l
Owner or Owners Desegw, Titie t
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiter and Pressure Vessel inspectors and the State bMMU DNM N0'W l OO of or Provinee of Neul A m eY and employed by M h T F~c r h 07-have inspected the components described in this Owner's Report during the period 3 - IS - 9J J
'#- 93
_ and state that tv to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures oescribed in this Owner's Report in accordance with the reouirements of the ASME Code,Section XI.
By signmg this certificate neither the inspector nor his employer makes any warranty, expressed or amplied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor has employer shall be liable in any manner for any personal injury or prtoerty damage or a loss of any kind arising from or connected with this inspection.
/]
LY NO S01f [I] N Nb UU2 Commissions insportorySignature Nationet Book, State, Provmce, and E ndorsements Date
/D d Y
/#
19 @ A
]
M2/821
..4
,, _ ~
'f MIS-2 OWNE2S DATA REPO2T FCR ICIERVICE ICSPZCTION 1.
OWNER:
Jersey Central Power & Light Company, Madison Avenue &
Punch Bowl Read, Morristown, New Jersey
}
'2.
PLANT:
Oyster Creek Nuclear Generating Station,
}
U.S. Route 9, Forked River, New Jersey i
3.
PLANT UNIT: NA I
4.
OWNER CERTIFICATION OF AUTHORIZATION (if required): NONE l
5.
COMMERCIAL SERVICE DATE:
12/23/69 6.
NATIONAL BOARD NUMBER FOR UNIT: Reactor vessel 14895 l
l t
SYSTEM ASME COMPONENT EXAKIMATION NO.
ITEM IDENTIFICATION NO.
METHOD REMARES 212 B9.11 NZ-3-0044B WELD SUR POST hTLD CROWN REDUCTION B9.11 NZ-3-0096 WELD SUR POST WELD CROWN REDUCTION i
B9.11 NZ-3-0096A WELD SUR POST WELD CROWN REDUCTION l
B7.70 V-1-0173 BOLT VT-1 NEW STUDS AND NUTS l
B7.70 V-1-0174 BOLT VT-1 NEW BOLTS AND NUTS j
I B7 70 V-1-0177 BOLT VT-1 NEW STUDS AND NUTS F1.20 212-MP-NZ SUPPORT VT-3 79-14-UPGRADE R13A-0035 214 BIO.10 214-BP-557-SUPPORT SUR 79-14 UPGRADE R11-0035 215 F1.10 215-BP-X SUPPORT VT-3 79-14 UPGRADE i
SS-1-0014 B l
216 B9.40 RHC-2-0033 WELD SUR INDICATION FOUND ON SUCH SUCH ISI EXAM AND REPAIR i
B7.50 216-BG-002 BOLT VT-1 (1) NEW REPLACEMENT STUD I
221 B5.10 NR02 1-567A WELD SUR POST WELD CROWN REDUCTION l
l l
B5.10 NR02 1-567B WELD SUR POST WELD CROWN REDUCTION l
B5.10 NR02 2-565A WELD SUR POST WELD CROWN REDUCTION B5.10 NR02 2-565D WELD SUR POST WELD CROWN REDUCTION B5.10 NR02 2-265E WELD SUR POST WELD CROWN REDUCTION B7.50 221-BG-002 BOLT VT-1 (8) NEW BOLTS, (8) NEW NUTS 223 B9.11 NG-A-0025A WELD SUR POST WELD CROWN REDUCTION B9.11 NG-B-0024A WELD SUR POST WELD CROWN REDUCTION B9.11 NG-D-0022A WELD SUR POST KTLD CROWN REDUCTION-B9.12 NG-D-0022B WELD SUR POST WELD CROWN REDUCTION i
B9.12 NG-E-002.5A WELD SUR POST WELD CROWN REDUCTION B6.180 P-37-005 BJ2-3 BOLT UT (16) NEW STUDS B6.190 P-37-005 BJ2-3 BOLT VT-1 (16) NEW STUDS B7.70 V-37-005 BOLT VT-1 NEW BOLTS AND NUTS Page 2 NI51.14R i
~
DIS-2 OWNERS DATA REPORT FOR IC ERVICE INSPECTION l
1.
OWNER:
Jersey Central Power & Light Coatpany, Madison Avenue &
Punch Bowl Read, Morristown, New Jersey 2.
PLANT:
Oyster Creek Nuclear Generating Station, U.S.
Route 9, Forked River, New Jersey 3.
PLANT UNIT: NA 4.
OWNER CERTIFICATION OF AUTHORIZATION (if required): NONE 5.
COMMERCIAL SERVICE DATE:
12/23/69 l
6.
NATIONAL BOARD NUMBER FOR UNIT: Reactor vessel 14895 l
SYSTEM ASME COMPONENT EXAMINATION NO.
ITEM IDENTIFICATION NO.
METHOD REMARKS I
241 C5.51 NO-2-0035 WELD SUR INDICATIONS FOUND ON SCH.ISI EXAMINATION REPAIR WAS PERFORMED C5.51 NO-2-0088 WELD SUR INDICATIONS FOUND ON SCH.ISI EXAMINATION REPAIR WAS PERFORMED C5.51 UQ-2-0094 WELD SUR INDICATIONS FOUND ON SCH.ISI EXAMINATION REPAIR WAS PERFORMED l
F1.20 241-BP-NO SUPPORT VT-3 79-14 UPGRADE H16-0016 A F1.20 241-BP-NO-2 SUPPORT VT-3 79-14 UPGRADE H48-0089 F1.20 241-BP-NQ-2 SUPPORT VT-3 79-14 UPGRADE H55-0038 F1.20 241-BP-NO SUPPORT VT-3 76-14 UPGRADE H8-0008 A C3.20 241-BP-433-R2-0057 SUPPORT SUR THIS IS A
PSI EXAMINATION-THIS EXAMINATION ACCEPTS LUG $025H AFTER INDICATION REMOVAL F1.20 241-BP-433-RS-0076 SUPPORT VT-3 79-14 UPGRADE 411 B7.70 V-1-0010 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0160 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0161 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0162 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0163 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0164 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0165 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0166 BOLT VT-1 NEW BOLTS AND NUTS B7.70 V-1-0167 BOLT VT-1 NEW BOLTS AND NUTS 532 F1.30 532-BP-SW-2-H1-0002 SUPPORT VT-3 79-14 UPGRADE F1.30 532-BP-SW-2-H9(B)-
SUPPORT VT-3 79-14 UPGRADE 0015 F1.30 532-GU-ISH-2-0074 SUPPORT VT-3 79-14 UPGRADE 0015
-Page 3-NINt.14R
ATTACHMENT l
TO TABLE 2 1
DISPOSITION CODE DESCRIPTION AEVAL ACCEPTED BY EVALUATION 1
l AEXAM ACCEPTED BY EKAMINATION j
AREPR ACCEPTED BY REPAIR INDICATION CODES DESCRIPTION 200 PT-SUFACE PLANAR FLAWS 210 MT-SUFACE PLANAR FLAW
(
(SEC XI) 213 MT-SUFACE MULTIPLE PLANAR FLAW (SEC XI) 250 LOOSE BOLTING ON SUPPORT (SEC XI) 251 SUPPORT WITH IMPROPER SETTING (SEC XI) 255 SUPPORT WITH RESTRICTED MOVEMENT (SEC XI) 256 SUPPORT WITH DEBRIS (SEC XI) 258 SUPPORT WITH CONCRETE SPALLING (SEC XI) l l
259 INTEGRAL ATTACHMENT WELD l
DIFFIDENCE (SEC XI) 261 SUPPORT MISSING PARTS (SEC XI) 262 VT-3 LINEAR INDICATION IN j
RX VESSEL (SEC XI) 263 VT-1 WASTAGE AT BOLTED CONNECTION (SEC XI) 265 SUPPORT MISALIGNED (SEC XI) 266 SUPPORT SPHERICAL BREARING DIFICIENCY (SEC XI) 268 SUPPORT DOES NOT CONFORM TO AS-BUILT DWG (SEC XI) 270 COMP. ON SUPPORT IS DESTORTED (SEC XI) i l
NIM 1.14k Page 3 l
l