July 20, 1990 ViS. Nuclear Regul'atory Commission ATTN:. DOCUMENT CONTROL DESK-
. Washington,-D.C.
20555
Subject:
Zion Station Units 1 and 2 Status of NRC-Bulletin 88-10 tRC Docket Nos. 50-191L304
References:
(a) NRC Bulletin 88-10, dated, November-22, 1988.
!f.
(b) M. Richter (CECO) letter to U.S. NRC, dated April 4, 1989.
(c) M.- Richter (CECO) letter to U.S. NRC, dated July 7.-1989.
(d) NRC Bulletin 88-10 Supplement 1 dated August 3, 1989.
(e) M. Richter (CECO). letter to U.S. NRC, dated September 13, 1989.
(f) M. Richter (CECO) letter to U.S. NRC, dated November 9, 1989.
Dear Sir:
'NRC Bulletin 88-10 (Bulletin) requested that actions be taken to provide reasonable assurance that molded-case circuit breakers (MCCB)
. purchased for use-in safety related applications without verifiable
~
. traceability.to the circuit breaker manufacturer (CBM) perform their safety function.
In
Reference:
(e), Commonwealth Edison Company (CECO) reported
- that both units at Zion Station had non-traceable MCCBs installed'in safety-related applications, and that thesc breakers would be replaced (by.
f
-traceable breakers) to complete Bulletin Action 5.
For Zion Unit 1, an
+
alternative. schedule was presented for the replacement of the non-traceable MCCBs Ceco indicated that' breaker replacement would be completed by the
<end of the.second refueling outage beginning after March 1, 1989 (presently scheduled for September 1991).
For Zion Unit 2, Ceco indicated that breaker replacement would be completed by the end of the current Spring 1990
.-refueling outage.
This letter provides a status report on the breaker replacements for both units, and presents an updated schedule for completion
-of the Unit:2 bre r replacements.
$$p2ggggg[@$
o
- gg9, Ih
i?
$s.
.. l- ]
+
U.S. Nuclear Regulatory Commission July 20, 1990' For Zion Unit 1, there were eight (8) non-traceable MCCBs installed.
in safety-related applications (an increase of one breaker from the total previously reported in Reference (e)).
The location of these breakers, and their associated loads.:are identified in Attachment
'A'.
At this time, six-(6) of the non-traceable breakers have been replaced, as indicated in Attachment
'A'.
A replacement breaker is currently available for MCC 13818 (Compartment F-1) which feeds the Control Room HVAC System Air Handling: Unit
'0A'; however, breaker replacement cannot be performed at this time since the remaining: Control Room HVAC System Air Handling Unit ('0B') is out of service for'a modification (scheduled for completion by the end of August 1990).
Following~ completion of this modification, the replacement breaker for Air Handling Unit 'OA' will be scheduled for installation.
The replacement breaker for Instrument Inverter 113 (see Attachment 'A') is currently
. ordered, and delivery is expected in August 1990.
Following receipt of the replacement breaker, it will be installed at the first available opportunity which w1_Il not jeopardize or impact unit operation (not to exceed the next refueling outage which is presently scheduled for September 1991).
Therefore, replacement of the non-traceable breakers (for Bulletin Action 5) for Unit I will be completed within the schedule presented in Reference (e).
For Zion Unit 2, there were ten (10) non-traceable MCCBs installed in safety-related applications.
The location of these breakers, and their associated-loads, are identified in Attachment
'B'.
At this time, seven (7) of,the non-traceable breakers have been replaced, as indicated in Attachment
'B'.
The remaining replacement breakers (for Instrument Inverters 212 and 214) are currently ordered, however, they (replacement breakers) are not expected to be available prior to the completion of the current refueling outage (Spring 1990).. It is~ expected that these breakers will-be delivered
-in August and September 1990 (as indicated in Attachment
'B').
Following receipt, the replacement breakers will be installed at the first available opportunity which will not jeopardize or impact unit operation (not to exceed the next refueling outage which is presently scheduled for January 1992).
The traceable replacement breakers for Units 1 and 2 are being procured safety-related, and meet the criteria of Bulletin Action 7.
CECO will notify the NRC following completion of the breaker replacements for each unit. This will document the completion of Bulletin
- Action 5.
l
[g, }.
.'3
-.i' i
l'
,tm bl h, t v
, yy 9
'-v (U.S. Nuclear kegulatory-Commission- -
' July;20, 1990
(
Please direct any_ questions that you may have concerning this-
+
response to this office..
Respectful _ly, n
'l'
-l H.H. Richter f-Generic Issues Administrator j
y i
j
,i i
- Attachments:.A - Status of MCCB Replacement for Zion Unit 1.
.i B - Status of MCCB Replacement for Zion Unit 2.
1 o
cc:
A.B.: Davis - Regional Administrator, Region III l
Senior. Resident Inspector - Zion Station C. Patel - NRR' Project Manager q
'j i
Subscribed and-Sworn to
- r
- ::::::::...:.__.______
me-this d day l l
- OFFICIAL SEAL"3
,be[f^r
, PATRICIA LYNN M ARLOW h-m Jgig, W &
RlM E M a' d t %
- tu N0189 di #
19 0 NOTARY PUBLIC-
____- _::~ n ~-:::::-m, l ['* b,,F I.
~~
4E AL " ! ',
F c t.
', ', PATRICIA L,yNN MARLOW g l
- 'R0ta Pup a s e ll.UN018 lg miss os > 4ts 11/5/91]q
-c::......
s
$i d5 0:
ATTACHMENT A-
?..
1 Status of MCCB' Replacement for Zion Unit 1
'{
t Location Acolication Status
'l MCC 137.1 In-Core Flux Happing System
. replaced-(Compt. F-3)
Detector 'B' feed MCC 1371-
'O' Diesel Generator Lube replaced sCompt,-D-5)
Oil Heater MCC 1381'.
Main Steam Line Isolation Valve replaced'
-(Compt.-G-6)
Reset and Test Loop 'A' DC Bus 112 DC Control Power to 480V replaced
-(Circuit 24)
Bus'133 DC Bus 111
-Main Feed to NSSS Annunciator replaced i
(Circuit 27).
Cabinet ICB74 HCC 1393B Spare replaced (Compt.-M-2)
-Instrument-AC Input to Instrument delivery date Inverter 113.
Inverter 113 of August 1990
.H'CC 1381B Control Room HVAC System Air replacement breaker-
- (Comp t,.. F-1 )
Handling Unit '0A' available, cdatting completion Air Handling.
Unit '0B' modification l
4 ll' l-I t
1 l;
Imw/ID43
]
l
hil jyf f
o; g,---
l ATTACHMENT B y
Status of HCCB Replacement For Zion Unit 2 Lonilon 6polication Status MCC'2372~
Charging Pump '2B' Unit Cooler replaced (Compt. A-5)'
HCC 2372 SI Pump '2A' Discharge to Loops replaced
'(Compt. H-1)
'A' and 'D'-Hot leg Injection Valve MCC 2381 Diesel Generator '2A' Lube replaced (Compt. A-1) 011 Heater l
I MCC 2383B Steam Generator '2C' Res. Aux.
replaced (Compt. J-3)
.Feedwater Stop-Valve 1
(2H0V-FH0053) a HCC 2391 Diesel Generator '2B' Lube replaced (Compt. C-2)
Oil Heater HCC 2391 Feedwater '2A' Steam Supply from replaced
-(Compt. C-6)
Steam Generator '20' Stop Valve R
HCC 2393A Charging Pump '2A' Unit Cooler replaced
]
-(Compt. F-1)
Instrument AC Input to Instrument delivery date Inverter 212 Inverter 212 of August 1990 J
Instrument DC Input =to Instrument delivery date t
Inverter 212 Inverter 212 of September 1990 Instrument AC Input to Instrument delivery date Inverter 214 Inverter 214 of August 1990
'i t