APPENDIX AL NOTICE OF VIOLATION.

General Public Utilities Nuclear Corporation Docket No.

50-289 Three Mile Island,' Unit'1-License No. DPR-50 As a result of.the inspection conducted on May 7-11, 1990, and in accordance with thel" General Statement of Policy and Procedure for NRC Enforcement. Actions,

10 CFR Part 2,' Appendix C, the following violation was identified:

-10 CFR 50, Appendix 8, Criterion V requires that activities affecting quality-be accomplished iri accordance with procedures..."

Ocensee. Procedure No. SP-1101-41-003, Revision 2 for " Installation of Electrical Equipment," Section 4.4.3, Item C, states, in part that:

"Six (6) inch minimum free air space shall be maintained between redundant

- wiring... from the raceway entrance to. the termination points..."

Contrary to the.above, on May 11,1990, the 120 VAC - redundant power cables from containment high range radiation monitors RM-G22.and RM-G23 were found tied together within the PRF cabinet.

This violation is a Severity-Level IV, Supplement I.

t Pursuant to the provisicns of 10 CFR 2.201, General Public bi.ilities Corporation is:hereby-required to submit to this office within thirty days of the date of this letter which transmitted this Notice, a written statement or explanation in reply, including: (1) the corrective steps which have been taken and-the results achieved;-(2) corrective steps which will~ be taken to avoid-further violations; and (3) the date when~ full compliance will be achieved. Where good cause is shown, consideration will be given to extending this response time; k

i 1

90G7030189 900627 PDR ADOCK 05000289 Q

PDC b