ML20055B892

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Failure of Rockbestos Cable in Reactor Protection Sys,Initially Reported on 820126. Four Penetrations for Unit 4 Will Be Installed After Present Cables Are Replaced by IE-qualified Cables
ML20055B892
Person / Time
Site: Washington Public Power Supply System
Issue date: 07/02/1982
From: Mazur D
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To: Faulkenberry R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
10CFR-050.55E, 10CFR-50.55E, G1-82-413, GO1-82-0413, GO1-82-413, NUDOCS 8207230495
Download: ML20055B892 (4)


Text

-

Docket Nos. 50-460/513 50.55(e) Report l%

Washington Public Power Supply System.

P.O. Box 968 3000 GeorgeWashingtonWay R ichland, Washington 99352 "'k50S) 372-5000

! 'f p~J/

July 2, 1982 gy G01-82-0413 i,

Nuclear Regulatory Commission Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596 Attention:

R. H. Faulkenberry

Subject:

NUCLEAR PROJECTS 1 AND 4 DOCKET N05. 50-460 AND 50-513 REPORTABLE 10CFR50.55(e)

ROCKBESTOS CABLE

Reference:

1)

Telecon ME Rodin, Supply System to PP Narbut, Region V, Nuclear Regulatory Commission, dated January 26, 1982 2)

G0-1-82-0060, dated February 26, 1982, DW Mazur to RH Faulkenberry 3)

G0-1-82-0152, dated April 21, 1982, RW Root to RH Faulkenberry Reference 3) informed your office of a reportable deficiency under 10CFR50.55(e) and transmitted an interim status report on the subject condition.

Attachment A, to this letter, provides the Supply Systems final report on the above caption condition. The attachment includes a restatement of the problem and description of the safety implications associated with failure of the Rockbestos cable in the Reactor Protection System.

The only cable involved is that used in the Unit 4 penetrations. A review was performed of the Raychem cable used in the Unit 1 penetra-tions and it was found that there is not a similar problem with the cable. To date, we have been unable to establish a completion schedule for the replacement of the cables for the Unit 4 penetrations. Due to the construction delay, we will defer our quarterly updates to a yearly basis or more frequently when new information becomes available.

8207230495 820702 PDR ADOCK 05000460 S

PDR 62-Go

R. H. Faulkenberry July 2, 1982 Rockbestos Cable G01-82-0413 Page Two If you have any-q estions or desire further information, please advise.

?W//

l

^

T (tb 7

' /

D. W. Mazu Acting Program Director DWM:JMS:lm Attachment cc: CR Biyant, BPA (399)

JP Ladpa, Bechtel (860)

V. Mani, UE&C (897)

A Toth, NRC V. Stello, Director of Inspection, NRC FDCC (899) 1 i

i l

i l

I l

E

ATTACHENT A WNP-1/4 DOCKET NOS. 50-460 AND 50-513 REPORTABLE CONDITION PER 10CFR50.55(e)

ROCKBESTOS CABLE FINAL REPORT BACKGROUND The Supply System received a letter from Westinghouse Electric Corporation stating that they have been informed by the Rockbestos Company that their solid dielectric coaxial cable exhibited failures under certain conditions as described below. Westinghouse identified four penetrations (HE2, HH3, H15 and HK3) designated for Unit 4, in which the above type of Rockbestos cable was used.

Westinghouse however, did not know if the above penetrations carried any safety related circuit.

The Supply System requested the Architect Engineer of the Project, United Engineers & Constructors, to review the application of the four penetrations in question and determine if they are used for safety related circuits at temperatures where failures are likely to occur.

DESCRIPTION OF DEFICIENCY In a letter to Westinghouse, Rockbestos stated that testing confirmed that cable types RSS-6-100 through RSS-6-ll2 may be subject to failures at temperatures above 230 F.

Expansion of the die!ectric causes foreshortening of the braided shield which, in turn causes longitudinal compression and kinking of the center conouctor, resulting in cracking of the dielectric permitting shorting of the center-conductor to the shield.

Westinghouse listed cabin ty7e RSS-6-ll2 as used in Unit 4 penetrations numbered as HE2, HH3, h!5 and HK3.

SAFETY IMPLICATIONS Rockbestos recommends that the RSS-6-112 type cable not be instalfed or, if installed, should not be exposed to environments above 230 F.

The above type of Rockbestos cable is used for Unit 4 penetrations to connect the Ion chambers to the Reactor Protection System Cabinets (RPS).

The RPS initiates a reactor-trip when a sensed parameter (or group of parameters) exceeds a set point value indicating the approach of an unsafe condition.

In this manner, the reactor and the reactor coolant system is protected from over pressurization and fuel cladding damage.

The scope of the RPS includes all electronics, signal processing equipment and cabling from the system sensors to the input terminals of the Control Rod Drive Control System (CRDCS).

The potential to isolate the Reactor Protection System then represents a significant safety problem.

t

y CORRECTIVE ACTION PLANNED The Architect Engineer, United Engineers & Constructors, had notified Westinghouse,. the supplier of the penetration, that the four penetrations with Rockbestos RSS-6-ll2 cable are used for class fE circuits in an environment exceeding the recommended limit of 230 F and that these cables are to be replaced by a lE qualified cables.

As an added precaution, the Construction Manager, Bechtel Power Corporation, has been notified to write a nonconformance report and red tag the affected penetrations.

In addition to the above identified problem with Rockbestos Cable, Westinghouse was also requested to determine if the Raychem Cable, Raychem being the only other supplier of coaxial cable for penetrations, supplied for Unit 1 penetrations HE2, HH3, H15 and HK3, has a similar failure mode as the Rockbestos RSS-6-ll2. The Raychem Corporation informed the Supply System that the cables supplied by Raychem has different construction and does not have similar failure mode as the Rockbestos Cable.

CURRENT STATUS The four penetrations designated for Unit 4 have not been installed and are currently on hold. The installation will only be carried out after the present cables are replaced by 1E qualified cables.

i

.. _ _.,_ _,.. -..