Interim Deficiency Rept Re Potentially Loose Stud/Nut Combinations in Diesel Generators,Initially Reported on 820614.AE Developing Rework Plan for Inspecting & Retorquing Stud/Nut Combinations.Next Rept by 821027
ML20055B045
Person / Time
Site: Wolf Creek 
Issue date: 07/14/1982
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-82-221, NUDOCS 8207200294
Download: ML20055B045 (2)


Text

O w

KANSAS GAS AND ELECTRIC COMPANY T><E ELECTRC COMPANY GLENN L.

MOESTER W<E PertOct47 N uCL E a st July 14, 1982 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 KMLNRC 82-221 Re:

Docket No. STN 50-482 Subj: Potential 10CFR50.55(e) - Diesel Generator Bolt Torque

Dear Mr. Seidle :

The purpose of this letter is to provide a status report on the potentially loose stud / nut combinations in the diesel generators at Wolf Creek Generating Station. This potential problem was reported to Region IV of the Nuclear Regulatory Commission on June 14, 1982 by Kansas Gas and Electric Company.

The stud / nut combination in question holds the generator spider to the generator shaft. The potential problem was discovered when Colt Industries performed a recheck of rotor to spider fastener torque values on a Beloit Power Systems generator to verify op-eration of newly designed tooling for field use.

The check revealed one fastener was not loaded at all, and three others were only 13%

tight based on prescribed torque values. Since it is possible that other generators may have improperly torqued stud / nut combinations, Beloit submitted a 10CFR21 Report. Diesel generators at Wolf Creek Generating Station were listed as potentially affected.

The Architect / Engineer is developing a rework plan for inspecting and retorquing the stud / nut combinations in question. Upon completion of the rework, an evaluation will be made to determine the report-ability of this matter under the requirements of 10CFR50.55(e).

The status of the inspection and evaluation will be reported to you

\\

YQ l

h\\

8207200294 820714 PDR ADOCK 05000482

/

S PDR 201 N. Market - WicMa, Kansas - Mail Address: PO. Box 208 I Wichita, Kansas 67201 - Telephone: Area Code (316) 261-6451

  • o e

Mr. W.C. Seidle KMLNRC 82-221 July 14, 1982 on or before October 27, 1982. In the interim, please direct any questions concerning this matter to me or to Mr. Otto Maynard of my staff.

Yqurs very truly, l

inn 94' f,,

trZ Glenn L. Koester s

Vice President - Nuclear GLK:bb cc:

Mr. Thomas Vandel Resident NRC Inspector P.O. Box 311 Burlington, Kansas 66839 i