APPENDIX A l

j NOTICE OF VIOLATION

)

Carolina Power and Light Company Docket No. 50-400 Shearon Harris 1 License No..CPPR-158 As a result of the inspection conducted on May 10-13, 1982, and in accordance with the NRC Enforcement Policy, 47 FR 9987 (March 9, 1982), the following violation was identified.

10 CFR 50, Appendix B, Criterion V, as implemented by Carolina Power and Light PSAR Section 1.'8.5.5, requires in part that activities affecting l

quality shall be prescribed by documented instructions, procedures or drawings and shall be accomplished in accordance with these instructions, procedures or drawings.

Shearon Harris specification ' CAR-SH-CH-6 " Con-crete", requires that field cured test cylinders be controlled in accordance j

~

with ASTM C-31.

ASTM C-31 specifies that field med test cylinders are to be stored under conditions that maintain the Iture in a range of 60-80 degress Fahrenheit for the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

.nolding of the test j

cylinders.

Contrary to the above, test cylindets.fren concrete pour number ICBXW406002 L

were observed being stored at temperatures greater than 80 degrees Fahren-heit during the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after molding.

z_

t This is a Severity level V Violation (Supplement II.E).

l Pursuant t_o the provisions of 10 CFR 2.201, you are hereby required to submit to f

this of fice within thirty days of the date of this Notice, a written statement or explanation in reply, including: (1)~ admission or denial of the alleged viola-tion; (2) the reasons for the v,iolation if admitted; (3; the' corrective steps

.l which have been taken and the results achieved; (4) corrective steps which will l

be taken to avoid further violations; and (5) the date< when full compliance will be achieved. Considerat' ion may' be given to extending your response time for good cause shown'.

JUN 2 1982 I