ML20054L629
| ML20054L629 | |
| Person / Time | |
|---|---|
| Site: | Catawba |
| Issue date: | 06/28/1982 |
| From: | Parker W DUKE POWER CO. |
| To: | Adensam E, Harold Denton Office of Nuclear Reactor Regulation |
| References | |
| NUDOCS 8207080311 | |
| Download: ML20054L629 (3) | |
Text
_ _ _ _. _.... _ _ _ _ __
l t
DUKE POWEH COMI%NY PowEu llulLDING 4ee Sourn Cnuncu STHEET, CHAHLOTTE, N. C. 2es242 WILLIAM O. PA R M E R. J R.
MF Pa t Si c t M Y Tt.tPHONE:AstA 7C4 S T E A me P AOOuCYtOM 373-4303 Mr. Ilarold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention:
Ms. E. G. Adensam, Chief Licensing Branch No. 4 Re: Catawba Nuclear Station Docket Nos. 50-413 and 50-414
Dear Mr. Denton:
My letter of June 3, 1982 transmitted information in regards to containment boundary f racture toughness as requested by Elinor G. Adensam's letter of May 24, 1982.
The specification for the Lowest Service Metal Temperature of the containment plates should have been given as 10 F.
A corrected copy of the containment fracture toughness data is attached.
Very truly yours, ?
w a. /, 4 William O. Parker, J.
ROS/php Attachment cc:
Mr. James P. O'Reilly, Regional Administrator U. S. Nuc1 car Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 Mr. P. K. Van Doorn NRC Resident Inspector Catawba Nuclear Station Mr. Robert Guild, Esq.
QCI Attorney-at-Law 314 Pall Mall Columbia, South Carolina 29201 8207080311 820628 PDR ADOCK 05000413 A
Mr. Harold R. Denton, Director June 28, 1982 Page 2 cc: Palmetto Alliance 2135h Devine Street Columbia, South Carolina 29205 Mr. Jesse L. Riley Carolina Environmental Study Group 854 Henley Place Charlotte, North Carolina 29207 Mr. Henry A. Presler, Chairman Charlotte-Mecklenburg Environmental Coalition 943 Henley Place Charlotte, North Carolina 28207 w
Catawba Nuclear Station Containment Pressure Boundary Fracture Toughness Data
- 1) Fabrication Code
- f a) Containment Vessel Plate: ASME Code 1971 Edition through Summer 1972 j
addenda, Subsection NE, paragraph NE-2350 b) Containment Vessel Welds: ASME Code (as above), Subsection NE, paragraph NE-4335 c) Personnel Locks: ASME Code (as above), Subsection NE, paragraph 2350 d) Equipment Hatch: ASME Code (as above), Subsection NE, paragraph NE-2300 e) Piping Penetrations: ASME Code 1974 Edition through Summer 1974 addenda, Subsection NC, paragraph NC-2311
- 2) Materials Test Data:
In storage at the Catawba site
- 3) Lowest Service Metal Temperatures Item Specification Actual Charpy Test 0
Containment plates 10 F 49 F
-30 F Containment welds 10 49
-20 Personnel Locks 48 49 18 Equipment flatch 0
49
-30 Piping Penetrations (stubends) 10 49
-30
- 4) As-Built Information for Flued Heads This data is given on the following drawings.
Penetration Drawing Type I CNM-1206.00-0010 Type II CNM-1206.00-0011 Type III Ser. 1 CNM-1206.00-0012 Type III Ser. 3 CNM-1206.00-0048 Revised June 28, 1982