THE CLEVELAND ELECTRIC ILLUMIN ATING COMPANY P O BOX 5000 m CLEVEL AND. OHIO 44101 m TELEPHONE (216) 622-9800 m ILLUMINATING BLDG e 55 PUBLIC SdUARE Serving The Best Location in the Nation Dalwyn R. Davidson V1CE F RE90E NT April 8, 1982 SYSTF M E NGINE EHtNG AND CONSTRUCTION CD T

Cb 9

p r -

r.,3.,

Q Mr. James G. Keppler

[

/1 D9 bO2A $

Director, Region III k. g g, [,'7f.;"~ qa Office of Inspection and Enforcement I;.

l.; ~ - ' M p

U. S. Nuclear Regulatory Commission

-s 799 Roosevelt Road 6

y Glen Ellyn, Illinois 60137 g.e RE:

Perry Nuclear Power Plant Docket Nos. 50-440; 50-441, Interim Report on Reactor Pressure Vessel Water Level Transmitters (RDC 49(82))

Dear Mr. Keppler:

This letter will serve as the interim report pursuant to 10CFR50.55(e) concerning incorrectly sized water level transmitters in the Units 1 and 2 reactor pressure vessels. On March 12, 1982, Mr. E. Riley of The Cleveland Electric Illuminating Company notified Mr. J. H. Neisler of your office that this deficiency had been identified.

This report contains a description of the deficiency, the planned corrective action, and the date scheduled for submittal of our final report.

DESCRIPTION OF DEFICIENCY The water level transmitters installed in the reactor pressure vessels have been determined to be wide range instead of narrow range as required by design. The transmitters installed are not capable of being adjusted to the required range and thus, cannot provide the intended safety signal. This equipment was supplied by General Electric as part of the Nuclear Steam Supply System. Notification of the reportable condition was received by The Cleveland Electric Illuminating Company in a letter from General Electric dated February 10, 1982.

l

/

/ S O

e 8204160292 820408 APR 12 1982 PDR ADOCK 05000440 S

PDR

r Mr. James G. Keppler April 8, 1982

/

CORRECTIVE ACTION General Electric is preparing a Field Disposition Instruction to cover replacement of these transmitters The numbers assigned to these FDIs areWNOMforUnit1andWRLDforhnit2.

This activity is scheduled to be completed by May 1, 1983,.and our final report will be filed by that date.

Sincerely, M

M Dalwyn Davidson Vice President System Engineering and Construction l

DRD/11p cc:

Mr. M, L. Gildner NRC Site Director, Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D.C.

20555 U. S. Nuclear Regulatory Commission c/o Document Management Branch Washington, D.C.

20555 i

I

\\

t