Text

.

Browns Ferry Nuclear Plant Unit 3 In-Service Inspection In accordance with paragraph IWA-6220(c) and (d) of Ecction XI of the ASME Boiler and Pressure Vessel Code (1974 edition, Summer through Summer 1975 addenda), the following information is provided.

1.

Date: December 1981 2.

Name of owner and address of corporate of fices:

Tennessee Valley Authority Chattanooga, Tennessee 3/401 3.

Name and address of nuclear generating plant in which the nuclear plant unit is located:

Browns Ferry Nuclear Plant P. O.

Box 2000 Decatur, Alabama 35601 4.

Name or number assigned to the nuclear power system by the owner:

Browns Ferry Nuclear Plant unit 3 5.

Commercial service date assigned to the nuclear power system by the owner:

Fbrch 1,19 77 6.

The number assigned to t he "hoiler," " pressure vessel," or components l

of the nuclear power system by the state, nunicipality, or province:

Does not apply l

7.

National board number assigned by the manuf acturer to the " boiler,"

l

" pressure vessel," or components:

No number assigned 8.

Name of the components or parts of the components for wl.ich this is l

a record, including such information regarding size, capacity, material, l

location, and drawings as may aid accurate identification.

The components examined as part of this in-service inspection l

are listed in the abstract.

l l

8205280416

. 9.

Name of the manufacturer of the components or parts for which this is a record, including the manufacturer's components or part numbers and such information regarcing the manuf acturer's corporate of fice or manufacturing plant locations as may aid in gaining access to the manufacturer records regarding the components or parts that the manufacturer is maintaining in accordance with requirements of Section III.

The majority of the components examined were supplied by:

General Electric Company Atomic Power Equipment Departtent San Jose, California 95103 under TVA contract No. 66C60-90744 10.

Date of completion of the in-service inspection: December 4,1980 11.

Name of inspectors:

The Tennessee Valley Authority acts as its own inspectors.

12.

Name and mailing address of the employer of the inapectors:

Tennessee Valley Authority 1630 Chestnut Street Tower II Chattanooga, Tennessee 37401 13.

Abstract of examinations performed, conditions observed, corrective measures recommended and taken.

Refer to attached sheet for weld numbers and conditions observed. No repairs were necessary as a result of this inspection.

l l

l l

l

Rosbrt Ns. 88-3d5T Table VI i

Evaluations Sectiobage. /nf]

Summarized ISI Results

\\

Weld or

.PT No.

System Component No.

Remarks R-001 RWCU DSRWC-3-1 No apparent discontinuities R-002 RWCU DSRWC-3-2 No apparent discontinuitics R- 003 RWCU DSRWC-3-3 No apparent discontinuities R-004 RWCU DSRWC-3-1A No apparent discontinuitics R-005 RWCU DSRWC-3-2 No apparent discontinuities R-006 RWCU DSRWC-3-3 No apparent discontinuitics R-007 RWCU D SRWC-3-4 No apparent discontinuities R-008 RWCU DSRWC-3-5 No apparent discontinuities R-009

RWCU D SRWC-3-6 No apparent discontinuities R-0010 RWCU DSRW-3-7 No apparent discontinuities R-00ll RWCU DSRW-3-4 No apparent discontinuities R- 0012 RWCU DSRWC-3-1 No apparent discontinuitics R-0013 RWCU DRWC-3-2 No apparent discontinuities R- 0014 RWCU DRWC-3 3 No apparent discontinuities 1:-0015 RWCU DSRWC-3-1A No apparent discontinuitics

(,

R-0016 RWCU DSRWC-3-2 No apparent discontinuities R-0017 RWCU D SRWC-3-3 No apparent discontinuities R-0018 RWCU D SRWC-3-4 No apparent discontinuities R-0019 RWCU DSRWC-3-5 No apparent discontinuities R-0020 RWCU D SRWC-3-6 No apparent discontinuitics R-0021 RWCU D SRWC-3-7 No apparent discontinuities

(

R- 0022 RWCU DRWC 4 No apparent discontinuitics R-0023 HPCI Tit PC I-3-66 207. DAC - Apparent (Nonmetallic j

inclusions) i R-0024 RWCU DRWC-3-lA No apparent discontinuities R-0025 RWCU DRWC-1-1 No apparent discontinuities R-0026 HPCI THPC I-3-66 No apparent discontinuities R-0027 RWCU D RWC 1 No apparent discontinuities R-0028 PWCU D RWC 1A No apparent discontinuities I

s i

l 1

b r--,_

,y

. _. _ ~..

_.- _,,