.. n%

UNITED STATES (E"

h NUCLEAR REGULATORY COMMISSION WASHING TON, D. C. 20555 g

9,

    1. y PUBLIC SERVICE ELECTRIC AND GAS COMPANY PHILADELPHIA ELECTRIC COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-272 SALEM NUCLEAR GENERATING STATION, UNIT N0. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 42 License No. DPR-70 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Public Service Electric and Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and Atlantic City Electric Company (the licensees) dated March 13, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable re,wirements have been satisfied.

8205140063 820423 PDR ADOCK 05000272 P

PDR

. 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of facility Operating License No. DPR-70 is hereby amended to read as follows; (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 42, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

R THE NUCLEAR REGULATORY COMMISSION N

i l

f Operating Reactors Branch No. 1 Division of Liceni g

Attachment:

Changes to the Technical Specifications Date of Issuance:

April 23, 1982

ATTACHMENT TO LICENSE AMENDMENT NO. 42 i

FACILITY OPERATING LICENSE NO. DPR-70 DOCKET NO. 50-272 Revise Appendix A as follows:

Remove Pages Insert Pages 3/4 4-33 3/4 4 4 t

i i

+

r i

i i

f(

f REACTOR COOLANT SYSTEM SURVEILLANCE REQUIREMENTS (Continued)

In addition to the requirerents of Specification 4.0.5, each Reactor Coolant Pump flywheel shall be inspected per the recomendations of Regulatory Position C.4.b of Regulatory Guide 1.14. Revision 1 August 1975.

4.4.10.1.2 Augmented Inservice Inspection Program for Steam Cenerator Channel l'eads - The steam generator channel heads shall be ultrasonically inspected during each of the first three refueling outages using the same ultrasonic inspection procedures and equipment used to generate the baseline data.

These inservice ultrasonic inspections shall verify that the cracks observed in the stainless steel cladding prior to operation have not propagated into the base material.

The stainless steel clad surfaces of the steam generator channel heads shall also be visually inspected during the above outages.

This may be accomplished by direct visual examination or by remote means such as televison camera.

If the visual exae.ination, either direct or remote, reveals detectable cladding indi-cations, a record shall be made by means of a video tape recording or photographs for comparison purposes.

l i

SALEv. - UNIT 1 3/4 4-33 Amendment No. // 42