Interim Deficiency Rept Re Emergency Diesel Generator Governor Lube Oil Cooler,Initially Reported 820126. Governor Lube Oil Cooler Will Be Moved to Elevation Below Governor Oil Level.Also Reportable Per Part 21
ML20052C261
Person / Time
Site: Washington Public Power Supply System
Issue date: 04/20/1982
From: Root R
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To: Faulkenberry R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
REF-PT21-82 10CFR-050.55E, 10CFR-50.55E, 82-33, GO-1-82-0150, GO-1-82-150, NUDOCS 8205040545
Download: ML20052C261 (1)


Text

-

DockOt Nos. 50-460/513

,I g 50.55(e) Report yfl'ED Washington Public Power Supply System P.O. Box 968 3000 GeorgeWashingtonWay Richland, Washington 9935)2 509)372-5000

/t'26 gf// //.

April 20, 1982 G0-1 0150 00Gio;jy".

Nuclear Regulatory Commission 0

a ia Lane, Suite 210 Walnut Creek, California 94596 m

g

-i n;D Attention:

Mr. R. H. Faulkenberry

_/

Chief, Reactor Construction Cj 17932-T2

' ~ '

Projects Branch

] e ty.

e,r.

h d

Subject:

NUCLEAR PROJECTS 1 AND 4 DOCKET N05. 50-460 AND 50-513

/K REPORTABLE CONDITION oN

\\"

%n EMERGENCY DIESEL GENERATOR GOVERNOR LUBE OIL COOLER

Reference:

1)

Telecon ME Rodin, Supply System to PP Narbut, Region V, Nuclear Regulatory Commission, dated January 26, 1982.

2)

Letter, DW Mazur, Supply System to RH Faulkenberry, NRC, dated February 26, 1982.

In reference 1) the Supply System informed your office of a reportable deficiency under 10CFR50.55(e) and reference 2) was an interim report on'the subject condition.

Attachment A to this letter, provides an update to our original response on the subject deficiency. The attachment includes a restatement of the identified condition and some additional information under the heading Corrective Action.

It is still anticipated that the rework of the system will be completed by August 31, 1982.

Because all essential actions have been completed with the exception of the physical rework we will not report again until September 1982, wherein we will provide our final report.

If you have any questions or desire further information, plase advise.

R. W. Root Acting Program Director RWR:MER:lm Attachment cc: CR Bryant, BPA/399 EW Edwards /860 V. Mani/897 A. Toth, NRC 7

V. Stello, Director of Inspection, NRC 1

FOCC/899 8205040545 820420 PDR ADOCK 05000460 Q-33 S

pDR

1 r

ATTACHMENT A WNP-1/4 DOCKET NOS. 50-460 AND 50-513 REPORTABLE CONDITION PER 10CFR50.55(e)

EMERGENCY DIESEL GENERATOR GOVERNOR LUBE OIL COOLER BACKGROUND The Supply System purchased Emergency Diesel Generators, two per plant, from Transamerica Delaval. A problem exists in the Governor Lube Oil Cooler Assembly which could result in loss of engine availability.

Transamerica Delaval has reported this deficiency under the requirements of 10CFR Part 21.

The Governor and Governor Lube Oil Cooler were manufactured by Woodward Governor Company of Fort Collins, Colorado and installed and piped on the engine by Transamerica Delaval.

DESCRIPTION OF THE DEFICIENCY The design deficiency is in the Governor Lube Oil System and concerns the orientation of the Governor and Lube Oil Cooler as installed on each engine.

If the Governor Lube Oil Cooler is installed above (elevation) the oil level of the Governor, as is the case for Units 1 and 4 there is a possibility of air being trapped in the system when the oil level in the Governor is low.

SAFETY IMPLICATIONS If air is trapped in the Governor's Oil System, engine starting relia-bility may be affected.

CORRECTIVE ACTION The deficiency will be eliminated by moving the Governor Lube Oil Cooler to an elevation below the Governor oil level. Transamerica Delaval has issued detailed drawings and instructions to the Supply System.

A field change is in the process of being prepared and approved by the Architect Engineer. Actual rework of the system by the site mechanical installation contractor will be coupleted by August 31, 1982. Upon completion of the rework, Supply System Project QA will verify that the relocation of the lube oil cooler is in accordance with the Delaval instructions and drawings. The site mechanical installation contractor will incorporate the new location of the lube oil cooler in their As-built drawings.

,